22-Elec-B7 Power Systems Engineering · Undated paper
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2019 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”, each carrying printed sub-part splits that total 20 points; the rubric states that any five questions constitute a complete paper, that only the first five questions as they appear in your answer book will be marked, and that all questions are of equal value. All seven are solved in full here, because the set is a study resource rather than a three-hour sitting. page 1 reads “National Exams May 2019” and every page footer reads “16-Elec-B7/May 2019”.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; P. M. Anderson, Analysis of Faulted Power Systems; P. Kundur, Power System Stability and Control. Canadian practice context (grounding philosophy, protection coordination) follows CSA C22.1 and IEEE Std 142 as applied by Canadian utilities and industrial plants.
Note on the printed values. Every number used below is the one the paper prints, including B = j70, Xeq = 3.0 Ω, a utility X0 of 0.1 and a grounding resistor of 8 Ω; the printed paper governs throughout.
Check — three engineering readings that a marker may take differently.
(1) Problem 5. The prose says “the voltage at both sources is 1 p.u.” above a Figure (3) that plainly draws four generators, G1 to G4. Every drawn source is taken at 1.0 pu, which is the only reading that closes the network.
(2) Problem 6. Figure (4-c) draws the 5 000 kVA generator alongside the resistance-grounded utility transformer, while the sentence introducing it mentions only the transformer. The generator is retained for part (e), consistent with the figure. It is ungrounded either way, so it changes only the positive- and negative-sequence networks; the zero-sequence answer is identical under both readings.
(3) Problem 2. “Neglecting armature reaction” cannot mean discarding xd and xq, which are the armature-reaction reactances — the question would then have no data. It is read here in its usual examination sense: neglect saturation and armature resistance, and use the ideal two-reaction model.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — why reactive power must be supplied locally, and from where. Reactive power is not consumed in the thermodynamic sense; it oscillates between the magnetic and electric energy stores of the network twice per cycle. What matters operationally is that it must nevertheless be supplied, because the series inductance of every line, cable and transformer absorbs $I^2X$ vars in proportion to the square of the current it carries, and because the load itself — induction motors above all — needs magnetising vars to establish its air-gap flux.
The first reason it must be supplied locally is voltage. On a predominantly inductive network the voltage drop along a branch is governed almost entirely by the reactive flow, $\Delta V \approx (RP + XQ)/V \approx XQ/V$ when $X \gg R$. Reactive power therefore cannot be transported far without collapsing the very voltage it is trying to support: shipping vars over a long line consumes more vars than it delivers. The second reason is loss. Reactive current occupies conductor cross-section and produces real $I^2R$ heating without delivering any useful energy, so a poor system power factor inflates both losses and the thermal loading of every element in the path. The third, and the one that ends in blackouts, is voltage stability: as loading rises the network approaches the nose of its P–V curve, where the incremental vars needed to hold voltage grow without bound. A system short of local reactive reserve slides down the lower branch of that curve and suffers voltage collapse, which is what took down the eastern interconnection in August 2003.
The major sources are, in rough order of controllability: synchronous generators, which can both generate and absorb vars by adjusting excitation within the limits of the capability curve, and which are the system's principal continuously-controlled reserve; shunt capacitor banks, switched in blocks at distribution and transmission buses — cheap, but their output falls with the square of voltage exactly when it is most needed; shunt reactors, which absorb vars on lightly loaded EHV lines and cables to control the Ferranti rise; synchronous condensers, unloaded synchronous machines run purely for var control, now returning to service for their inertia and short-circuit contribution; static var compensators and STATCOMs, thyristor- and IGBT-based devices giving continuous, sub-cycle control; series capacitors, which reduce the effective $X$ and so cut the var demand of a long line at source; on-load tap-changing transformers, which redistribute rather than create vars; and the lines and cables themselves, whose distributed shunt capacitance generates vars at light load.
Given. A salient-pole machine on an infinite bus.
| Quantity | Value |
|---|---|
| Infinite-bus voltage $V$ | 1.00 pu |
| Direct-axis reactance $x_d$ | 0.6 pu |
| Quadrature-axis reactance $x_q$ | 0.3 pu |
| Condition A | $P = 2.05$ pu, $\delta = 45^\circ$ — find $E$, $Q_2$ |
| Condition B | $E = 1.27$ pu, $\delta = 47^\circ$ — find $P$, $Q_2$ |
| Condition C | $E = 1.35$ pu, $Q_2 = 0$ — find $\delta$, $P$ |
Find. The six missing table entries, using the two-reaction (Blondel) model.
Approach. Write the two-reaction expressions for $P$ and $Q$ at the machine terminals, then treat each row as the algebra it happens to be: linear in $E$ for condition A, a direct evaluation for condition B, and a quadratic in $\cos\delta$ for condition C.
| Condition | $P$ | $Q_2$ | $E$ | $\delta$ |
|---|---|---|---|---|
| A | 2.05 (given) | −1.2833 | 1.0324 | 45.0 (given) |
| B | 2.3793 | −1.1146 | 1.27 (given) | 47.0 (given) |
| C | 1.6888 | 0.0 (given) | 1.35 (given) | 26.87 |
| Quantity | Value |
|---|---|
| Reluctance-power coefficient $V^2(x_d-x_q)/2x_dx_q$ | 0.8333 pu |
| Condition C quadratic | $c^2 + 1.35c - 2 = 0$; roots $+0.89204$, $-2.24204$ (rejected) |
| Synchronising coefficients $dP/d\delta$ (A, B, C) | 1.217, 1.327, 2.993 pu/rad — all stable |