22-Elec-B7 Power Systems Engineering · Undated paper
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2019 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”, each carrying printed sub-part splits that total 20 points; the rubric states that any five questions constitute a complete paper, that only the first five questions as they appear in your answer book will be marked, and that all questions are of equal value. All seven are solved in full here, because the set is a study resource rather than a three-hour sitting. page 1 reads “National Exams May 2019” and every page footer reads “16-Elec-B7/May 2019”.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; P. M. Anderson, Analysis of Faulted Power Systems; P. Kundur, Power System Stability and Control. Canadian practice context (grounding philosophy, protection coordination) follows CSA C22.1 and IEEE Std 142 as applied by Canadian utilities and industrial plants.
Note on the printed values. Every number used below is the one the paper prints, including B = j70, Xeq = 3.0 Ω, a utility X0 of 0.1 and a grounding resistor of 8 Ω; the printed paper governs throughout.
Check — three engineering readings that a marker may take differently.
(1) Problem 5. The prose says “the voltage at both sources is 1 p.u.” above a Figure (3) that plainly draws four generators, G1 to G4. Every drawn source is taken at 1.0 pu, which is the only reading that closes the network.
(2) Problem 6. Figure (4-c) draws the 5 000 kVA generator alongside the resistance-grounded utility transformer, while the sentence introducing it mentions only the transformer. The generator is retained for part (e), consistent with the figure. It is ungrounded either way, so it changes only the positive- and negative-sequence networks; the zero-sequence answer is identical under both readings.
(3) Problem 2. “Neglecting armature reaction” cannot mean discarding xd and xq, which are the armature-reaction reactances — the question would then have no data. It is read here in its usual examination sense: neglect saturation and armature resistance, and use the ideal two-reaction model.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — the three bus types. A power-flow bus carries four quantities — $|V|$, $\delta$, $P$ and $Q$ — of which exactly two are specified and two are solved for. Which two are specified defines the type.
The slack (swing, reference) bus specifies $|V|$ and $\delta$, and solves for $P$ and $Q$. There is exactly one in a conventional formulation, and it serves two distinct purposes. It provides the angular reference, because the power-flow equations involve only angle differences and would otherwise be under-determined. And it absorbs the mismatch: network losses are not known until the solution exists, so one generator must be left free to make up whatever the rest of the system does not supply. It is normally assigned to the largest generator or the strongest interconnection.
The generator or voltage-controlled bus (PV bus) specifies $P$ and $|V|$, and solves for $Q$ and $\delta$. Real power is set by the turbine governor and the dispatch, while voltage magnitude is held by the automatic voltage regulator acting on excitation — so those are the two the operator actually commands. The reactive output is whatever the machine must produce to hold that voltage, and it is checked after each iteration against the excitation and stator limits of the capability curve; if a limit binds, the bus is converted to a PQ bus with $Q$ fixed at the limit and $|V|$ released.
The load or PQ bus specifies $P$ and $Q$, and solves for $|V|$ and $\delta$. Nearly every bus in a real network is of this type: a load draws a known real and reactive demand from a forecast, and what its voltage settles to is precisely what the study is meant to discover. A bus with no injection at all is a PQ bus with $P = Q = 0$.
Applying that classification here: bus 1 is the slack bus, since $|V|$ and $\delta$ are both given and both injections are asked for; bus 2 is a PQ load bus, drawing 2.5 pu; and bus 3 is a PV generator bus, holding 1.05 pu. The table hands us the converged angles, which is what turns a normally iterative problem into one line of algebra.
Given. Two purely reactive branches, $x_{12} = 0.1$ pu and $x_{23} = 0.08$ pu, with $V_1 = 1.00\angle 0^\circ$, $\delta_2 = -3.5^\circ$, $P_2 = -2.5$ pu, $|V_3| = 1.05$ pu and $\delta_3 = +5.5^\circ$.
Find. $|V_2|$, and then all six remaining injections $P_1$, $Q_1$, $Q_2$, $P_3$, $Q_3$.
Approach. On a lossless network the real-power injection at a bus has no self-term, so $P_2$ is exactly linear in $|V_2|$ once every angle is known. One division gives the missing magnitude; every other entry then follows by direct substitution.
| Bus | Type | $|V|$ | $\delta$ (deg) | $P$ | $Q$ |
|---|---|---|---|---|---|
| Bus 1 | Slack | 1.0000 (given) | 0.0 (given) | +0.57297 | +0.63202 |
| Bus 2 | PQ (load) | 0.93855 | −3.5 (given) | −2.5 (given) | −1.71512 |
| Bus 3 | PV (generator) | 1.0500 (given) | +5.5 (given) | +1.92703 | +1.61446 |
| Check | Value |
|---|---|
| $\sum P_i$ (must vanish, lossless) | 0.00000 |
| $\sum Q_i$ | 0.53136 pu |
| $\sum |I|^2 x$ over the two branches | 0.53136 pu |
| Branch currents $|I_{12}|$, $|I_{23}|$ | 0.85308, 2.39424 pu |