22-Elec-B7 Power Systems Engineering · Undated paper
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2019 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”, each carrying printed sub-part splits that total 20 points; the rubric states that any five questions constitute a complete paper, that only the first five questions as they appear in your answer book will be marked, and that all questions are of equal value. All seven are solved in full here, because the set is a study resource rather than a three-hour sitting. page 1 reads “National Exams May 2019” and every page footer reads “16-Elec-B7/May 2019”.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; P. M. Anderson, Analysis of Faulted Power Systems; P. Kundur, Power System Stability and Control. Canadian practice context (grounding philosophy, protection coordination) follows CSA C22.1 and IEEE Std 142 as applied by Canadian utilities and industrial plants.
Note on the printed values. Every number used below is the one the paper prints, including B = j70, Xeq = 3.0 Ω, a utility X0 of 0.1 and a grounding resistor of 8 Ω; the printed paper governs throughout.
Check — three engineering readings that a marker may take differently.
(1) Problem 5. The prose says “the voltage at both sources is 1 p.u.” above a Figure (3) that plainly draws four generators, G1 to G4. Every drawn source is taken at 1.0 pu, which is the only reading that closes the network.
(2) Problem 6. Figure (4-c) draws the 5 000 kVA generator alongside the resistance-grounded utility transformer, while the sentence introducing it mentions only the transformer. The generator is retained for part (e), consistent with the figure. It is ungrounded either way, so it changes only the positive- and negative-sequence networks; the zero-sequence answer is identical under both readings.
(3) Problem 2. “Neglecting armature reaction” cannot mean discarding xd and xq, which are the armature-reaction reactances — the question would then have no data. It is read here in its usual examination sense: neglect saturation and armature resistance, and use the ideal two-reaction model.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — a 50 Hz transformer run at 60 Hz. The governing statement is the transformer EMF equation, $V \approx 4.44\,f\,N\,\Phi_{max}$. At a fixed applied voltage, peak flux is inversely proportional to frequency, so raising the frequency from 50 to 60 Hz drops the flux to $50/60 = 83.3\ \%$ of its design value. Everything else follows from that one line, and the practical shorthand is the volts-per-hertz ratio: the machine was designed for $V/f$ at 50 Hz and is now being run at five sixths of it.
Flux and magnetising requirement. With the core working 17 % further down its B–H curve, the core is de-saturated and the magnetising current falls more than proportionately — the relation is strongly non-linear near the knee. In circuit terms the magnetising reactance $X_m = 2\pi f L_m$ rises both because $f$ has risen and because the reduced flux places the core on a higher-permeability part of the curve, so $I_\phi = V/X_m$ falls on both counts. The magnetising reactive demand therefore drops.
Reactive power overall. Pulling the other way, every leakage reactance also scales with frequency, $X_{eq} \propto f$, rising by 20 %. At unchanged load current the leakage reactive demand $I^2X_{eq}$ therefore rises by 20 %, and the voltage regulation worsens. In a distribution transformer the magnetising branch dominates at light load and the leakage branch at full load, so the net reactive requirement falls at light load and rises at heavy load.
Losses. Copper loss $I^2R$ is essentially unchanged, since the load and hence the current are unchanged (skin and proximity effects add a percent or so at 60 Hz). Core loss splits: hysteresis loss follows $k_h f B_{max}^{n}$ with $n \approx 1.6$–2.0, and since $B_{max} \propto 1/f$ the product falls roughly as $f^{1-n}$, i.e. by about 15 % here; eddy-current loss follows $k_e f^2 B_{max}^2$, which is independent of frequency at constant applied voltage because the two effects cancel exactly. Total core loss therefore falls modestly.
Efficiency. With copper loss constant and core loss slightly reduced, the efficiency at any given loading improves by a few tenths of a percent. The transformer is also thermally and magnetically safe in this direction. The reverse operation is the dangerous one: a 60 Hz transformer on a 50 Hz supply is asked to carry 20 % more flux, drives the core into saturation, and draws a grossly distorted magnetising current with an enormous peak — which is why nameplate ratings are always quoted with their design frequency and why derating by the $V/f$ ratio is mandatory when a machine is moved to a lower-frequency system.
Given. A single-phase distribution transformer, all parameters referred to the 2400 V side.
| Quantity | Value |
|---|---|
| Rating / ratio / frequency | 50 kVA, 2400/240 V, 60 Hz |
| Series arm $R_{eq}$, $X_{eq}$ | 0.5 Ω, 3.0 Ω (HV referred) |
| Core-loss resistance $R_c$ | 30 000 Ω |
| Magnetising reactance $X_m$ | 4 500 Ω |
| Load | 40 kVA at 0.8 pf lagging |
| Secondary voltage held at | 240 V, i.e. $V_2' = 2400$ V referred |
Find. Primary voltage, primary current, input real and reactive power, primary power factor and efficiency at this loading.
Approach. In the cantilever model the excitation branch hangs across the primary terminals, so the series arm carries the load current alone. Work outward from the known secondary: find $I_2$, add the series drop to get $V_1$, put $V_1$ across the excitation branch to get $I_0$, and sum the currents. Nothing iterates.
| Quantity | Value |
|---|---|
| (i) Primary voltage $V_1$ | $2436.9\angle 0.823^\circ$ V (regulation 1.538 %) |
| (ii) Primary current $I_1$ | $17.066\angle -38.14^\circ$ A |
| (iii) Active power input $P_1$ | 32.337 kW |
| (iv) Reactive power input $Q_1$ | 26.153 kvar |
| (v) Primary power factor | 0.7775 lagging |
| (vi) Efficiency | 98.96 % |
| Excitation current $I_0$ | $0.5476\angle -80.65^\circ$ A |
| Core loss / copper loss | 197.95 W / 138.89 W (total 336.84 W) |