22-Mec-B2 Environmental Control in Buildings · May 2016
Question 2 of 8: Winter plant with preheat, mixing, reheat and steam humidification
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional
Engineers of Ontario / Engineers Canada annual examination
07-Mec-B2 Environmental Control in Buildings, May 2016,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same
value. Psychrometric charts and an R-134a p-h diagram are appended to the
paper. All eight problems are solved here, because the set is intended
as a study resource rather than an examination script.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this
examination code; Ch. 2–3 (psychrometry), Ch. 5–6 (heating
and cooling loads), Ch. 10 (cooling towers), Ch. 15 (fans and duct
design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3
(moist air), Ch. 6 (heating loads and infiltration), Ch. 8 (energy
estimating and the degree-day method), Ch. 12–13 (fluid flow, fans
and duct design).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering
Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression
refrigeration, multistage systems and heat pumps).
ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air
Quality; ANSI/ASHRAE Standard 55, Thermal Environmental
Conditions for Human Occupancy.
Canadian frame: National Building Code of Canada 2020
and its Appendix C design temperatures; National Energy Code of Canada
for Buildings 2020; Environment and Climate Change Canada heating
degree-day normals; CSA B52 Mechanical Refrigeration Code;
Canadian federal halocarbon regulations (SOR/2003-289) for the
refrigerant discussion in Problem 7.
Check: assumptions carried through this
paper. Cover-page instruction 1 invites a clear statement of any
assumption. Standard barometric pressure of 101.325 kPa is used throughout;
moist-air properties follow the ASHRAE Handbook — Fundamentals Ch. 1
formulation (Hyland–Wexler saturation pressure, so results agree with
the appended chart to chart-reading accuracy rather than being read off it);
R-134a properties are on the IIR datum and agree with the appended p-h
diagram. Problem-specific assumptions — climate data, fuel prices,
emission factors, air-change rates, occupant density, duct roughness and the
coil bypass factor — are stated where they are first used.
Question 2: Winter plant with preheat, mixing, reheat and steam
humidification (20 marks)
Given. A winter air-handling plant serving a space held
at 21 °C dry bulb and 35 % relative humidity against a total
heating load of 215 kW; outdoor air enters a preheater at
−14 °C and 0 % relative humidity and leaves it at
16 °C, is mixed with return air in the ratio 25 % outdoor by
mass, and the mixture is then heated and steam-humidified to a supply state
of 40 °C dry bulb and 30 % relative humidity.
Given data
Quantity
Symbol
Value
Room dry bulb and relative humidity
$t_3,\ \phi_3$
21 $^\circ$C, 35 %
Outdoor air at the preheater inlet
$t_1,\ \phi_1$
−14 $^\circ$C, 0 %
Preheater outlet dry bulb
$t_2$
16 $^\circ$C
Supply dry bulb and relative humidity
$t_5,\ \phi_5$
40 $^\circ$C, 30 %
Outdoor-air fraction by mass
$x$
0.25
Total space heating load
$q$
215 kW
Humidifying steam
—
saturated vapour at 2 psig
Find. (a) the plant arrangement, (b) the six state points
with their dry- and wet-bulb temperatures plotted on the psychrometric chart,
(c) the supply air volume flow, (d) the duty of the preheater and of the
heater separately, and (e) the steam flow rate to the humidifier.
(a) Diagram of the system
Plant arrangement. Outdoor air is preheated (1 to 2), mixed with return air (2 + 3 to 4), heated (4 to 4′) and steam humidified (4′ to 5) before being supplied to the space.
The preheater sits upstream of the mixing box, which is the point of the
arrangement: it lifts the outdoor air from −14 °C to
16 °C before it can meet the return air, so no part of the
mixing box, filter or downstream coil ever sees an air stream below freezing.
Face-and-bypass or freeze-stat protection on the preheater is what keeps the
plant safe on a design night.
(b) State points and the operating cycle
Approach. Fix each state from its two given properties
using the ASHRAE moist-air relations, take the mixed state from exact
moisture and enthalpy balances, obtain the mass flow from the room load and
the supply-to-room enthalpy difference, and split the last process into a
sensible coil duty plus the enthalpy carried in by the injected steam.
Humidity ratio and enthalpy of each fixed state. For any
moist-air state,
$$W=0.621945\,\frac{\phi\,p_{ws}(t)}{p-\phi\,p_{ws}(t)}
\qquad
h=1.006\,t+W\,(2501+1.86\,t)$$
At the room state, $p_{ws}(21\,{}^\circ\text{C})=2.488$ kPa, so
$W_3=0.005391$ kg/kg and $h_3=34.82$ kJ/kg. At the supply state,
$p_{ws}(40\,{}^\circ\text{C})=7.384$ kPa, giving $W_5=0.013900$ kg/kg and
$h_5=76.04$ kJ/kg. The outdoor air is dry, so $W_1=W_2=0$ and
$h_1=-14.08$ kJ/kg, $h_2=16.10$ kJ/kg.
Mixed state, from mass and energy balances. Adiabatic
mixing conserves moisture and enthalpy exactly, so both are mass-weighted,
$$W_4=x\,W_2+(1-x)\,W_3=0.25(0)+0.75(0.005391)=0.004043\ \text{kg/kg}$$
$$h_4=x\,h_2+(1-x)\,h_3=0.25(16.10)+0.75(34.82)
=30.14\ \text{kJ/kg}$$
The dry bulb then follows by inverting the enthalpy relation, not by
weighting the temperatures:
$$t_4=\frac{h_4-2501\,W_4}{1.006+1.86\,W_4}=19.76\ ^\circ\text{C}$$
Wet-bulb temperature of each state. The thermodynamic
wet bulb is the root of the adiabatic-saturation equation
$$W=\frac{(2501-2.326\,t^{*})\,W_s(t^{*})-1.006\,(t-t^{*})}
{2501+1.86\,t-4.186\,t^{*}}$$
solved for $t^{*}$ at each state. The results are collected below.
State points on the psychrometric chart
Point
Dry bulb ($^\circ$C)
Wet bulb ($^\circ$C)
$W$ (kg/kg)
$h$ (kJ/kg)
Dew point ($^\circ$C)
1 — outdoor air, preheater inlet
-14.00
-16.49
0.000000
-14.08
-80.00
2 — preheater outlet
16.00
3.75
0.000000
16.10
-80.00
3 — room and return air
21.00
12.36
0.005391
34.82
4.97
4 — mixed air, heater inlet
19.76
10.44
0.004043
30.14
0.94
4′ — heater outlet, humidifier inlet
38.97
17.80
0.004043
49.61
0.94
5 — supply air to the space
40.00
25.09
0.013900
76.04
19.13
The two dry states carry no moisture at all, so their dew points are
undefined; the table reports the solver's lower bound of −80 °C
for them, which should be read as "bone dry". Their wet bulbs are
nevertheless real: dry air at 16 °C passed through an adiabatic
saturator would cool to 3.75 °C as water evaporated into it, and that
is the number a sling psychrometer would read at state 2.
The winter cycle on the psychrometric chart. 1–2 is sensible preheat at constant moisture, 2 and 3 mix along a straight line to 4, 4–4′ is sensible heating, and 4′–5 is the steep, nearly vertical steam humidification line.
(c) Total air supply volume
Mass flow from the room energy balance. The supply air
must carry the whole 215 kW into the space as it falls from state 5 to
the room state 3,
$$\dot m=\frac{q}{h_5-h_3}=\frac{215}{76.04-34.82}
=5.216\ \text{kg/s of dry air}$$
Convert to volume at the supply state. The humid volume
at 40 °C and $W_5=0.013900$ is
$$v_5=\frac{R_a T}{p}\,(1+1.6078\,W_5)
=\frac{0.287\times 313.15}{101.325}\,(1+1.6078\times 0.013900)
=0.9069\ \text{m}^3/\text{kg}$$
so the volume the fan must handle is
$$\boxed{\;\dot V=\dot m\,v_5=5.216\times 0.9069
=4.731\ \text{m}^3/\text{s}=4,731\ \text{L/s}
\;(10,024\ \text{cfm})\;}$$
Note that the volume must be evaluated at the supply state, where the
fan and ductwork actually see the air; using standard density here would
understate the duct size by about 10 %.
(d) Energy input to each coil
Preheater. Only the outdoor-air stream passes through
it, so
$$\dot m_{oa}=x\,\dot m=0.25\times 5.216=1.3040\ \text{kg/s}$$
$$\boxed{\;q_{pre}=\dot m_{oa}\,(h_2-h_1)
=1.3040\,[16.10-(-14.08)]=39.35\ \text{kW}\;}$$
This is a purely sensible duty, since the outdoor air carries no
moisture.
Total duty of the heating and humidifying section.
Between the mixed state and the supply state the whole air stream gains
$$q_{4\to 5}=\dot m\,(h_5-h_4)=5.216\,(76.04-30.14)
=239.41\ \text{kW}$$
but part of that enthalpy walks in with the steam rather than through the
coil, so this figure must be split before the coil can be selected.
Subtract the enthalpy carried by the steam. Saturated
vapour at 2 psig is at $14.696+2=16.70$ psia $=115.1$ kPa, for which the
steam tables give $t_{sat}=103.59\ ^\circ$C and
$h_g=2,681.2$ kJ/kg. With the steam flow found in part (e),
$$q_{steam}=\dot m_{st}\,h_g=0.05141\times 2,681.2
=137.85\ \text{kW}$$
$$\boxed{\;q_{heater}=q_{4\to 5}-q_{steam}
=239.41-137.85=101.56\ \text{kW}\;}$$
The heater therefore lifts the air from 19.76 °C to
38.97 °C at constant moisture, and the steam supplies the last
degree of dry bulb together with all of the moisture. As a check, the same
duty follows from a pure sensible balance,
$\dot m\,(1.006+1.86\,W_4)(t_{4'}-t_4)=101.56$ kW.
(e) Steam flow rate
Moisture balance across the humidifier. Every kilogram
of moisture that leaves in the supply air above the mixed-air level must have
been injected, so
$$\boxed{\;\dot m_{st}=\dot m\,(W_5-W_4)
=5.216\,(0.013900-0.004043)
=0.05141\ \text{kg/s}=185.1\ \text{kg/h}\;}$$
It is worth reading the two coil duties against each other. The preheater
handles only a quarter of the air but takes it through a 30 K rise, and
still costs only 39.35 kW; the heater handles all of the air
through a 19 K rise and costs 101.56 kW. The steam is the
quiet third player: at 137.85 kW it delivers more than half of the
plant's total input downstream of the mixing box, which is why a steam
humidifier is never a trivial addition to a boiler's load.