22-Mec-B2 Environmental Control in Buildings · May 2016
Question 5 of 8: Induced-draft counterflow cooling tower
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional
Engineers of Ontario / Engineers Canada annual examination
07-Mec-B2 Environmental Control in Buildings, May 2016,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same
value. Psychrometric charts and an R-134a p-h diagram are appended to the
paper. All eight problems are solved here, because the set is intended
as a study resource rather than an examination script.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this
examination code; Ch. 2–3 (psychrometry), Ch. 5–6 (heating
and cooling loads), Ch. 10 (cooling towers), Ch. 15 (fans and duct
design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3
(moist air), Ch. 6 (heating loads and infiltration), Ch. 8 (energy
estimating and the degree-day method), Ch. 12–13 (fluid flow, fans
and duct design).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering
Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression
refrigeration, multistage systems and heat pumps).
ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air
Quality; ANSI/ASHRAE Standard 55, Thermal Environmental
Conditions for Human Occupancy.
Canadian frame: National Building Code of Canada 2020
and its Appendix C design temperatures; National Energy Code of Canada
for Buildings 2020; Environment and Climate Change Canada heating
degree-day normals; CSA B52 Mechanical Refrigeration Code;
Canadian federal halocarbon regulations (SOR/2003-289) for the
refrigerant discussion in Problem 7.
Check: assumptions carried through this
paper. Cover-page instruction 1 invites a clear statement of any
assumption. Standard barometric pressure of 101.325 kPa is used throughout;
moist-air properties follow the ASHRAE Handbook — Fundamentals Ch. 1
formulation (Hyland–Wexler saturation pressure, so results agree with
the appended chart to chart-reading accuracy rather than being read off it);
R-134a properties are on the IIR datum and agree with the appended p-h
diagram. Problem-specific assumptions — climate data, fuel prices,
emission factors, air-change rates, occupant density, duct roughness and the
coil bypass factor — are stated where they are first used.
Given. An induced-draft counterflow tower cooling
5.5 L/s of water entering at 44 °C, with a fan drawing
9 m³/s of air and absorbing 4.75 kW; air enters at
18 °C and 60 % relative humidity and leaves saturated at
26 °C, with the pressure constant at 1.013 bar throughout.
Given data
Quantity
Symbol
Value
Water volume flow, entering
$\dot V_w$
5.5 L/s
Water inlet temperature
$t_{w1}$
44 $^\circ$C
Air volume flow induced
$\dot V_a$
9 m³/s
Fan power absorbed
$\dot W_{fan}$
4.75 kW
Air entering
$t_{a1},\ \phi_1$
18 $^\circ$C, 60 %
Air leaving
$t_{a2},\ \phi_2$
26 $^\circ$C, saturated
Barometric pressure
$p$
1.013 bar
Find. The temperature of the water leaving the tower, and
the make-up water rate needed to replace what evaporates.
Induced-draft counterflow tower serving a refrigeration plant condenser. Water falls through the fill against the rising air; a temperature controller on the leaving water modulates fan speed, which is how the tower regulates condensing pressure.
Approach. Treat the tower as one control volume. A
moisture balance on the air stream gives the evaporation directly, which is
also the make-up; an energy balance on the same control volume, with the
water stream reduced by that evaporation and the fan work booked into the
air, gives the leaving water temperature.
Regulating the refrigeration plant
The tower rejects the condenser heat of the refrigeration plant, and the
temperature of the water it returns sets the condensing pressure and hence
the compressor's pressure ratio and power. Control is therefore exercised on
the leaving water temperature, and there are three usual means, shown on the
sketch in order of preference. Fan speed is the primary control: a
variable-frequency drive modulates the air flow so that the leaving water is
held at set point, and because fan power varies roughly with the cube of
speed, the energy saving in mild weather is large. Fan cycling, or
staging multiple cells, is the cruder version of the same idea and is used
where a drive cannot be justified. A bypass valve around the tower
returns a fraction of the warm water straight to the condenser, and is the
control of last resort in freezing weather, where it also keeps water moving
through the basin. The set point itself should float downwards with the
outdoor wet bulb rather than being fixed: a lower condensing temperature
reduces compressor power by roughly 2 –3 % per kelvin, so
letting the tower produce the coldest water it can, down to the chiller's
minimum permitted condensing pressure, is usually worth far more than the fan
energy it costs.
Leaving water temperature and make-up
Entering air state. At 18 °C,
$p_{ws}=2.064$ kPa, so at 60 % relative humidity
$$W_1=0.621945\,\frac{0.60\times 2.064}{101.3-0.60\times 2.064}
=0.007699\ \text{kg/kg}$$
$$h_1=1.006(18)+0.007699\,[2501+1.86(18)]=37.62\ \text{kJ/kg}$$
$$v_1=\frac{0.287(291.15)}{101.3}\,(1+1.6078\times 0.007699)
=0.8352\ \text{m}^3/\text{kg}$$
Dry-air mass flow. The 9 m³/s is measured at
the entering state, so
$$\dot m_a=\frac{\dot V_a}{v_1}=\frac{9}{0.8352}
=10.776\ \text{kg/s of dry air}$$
Leaving air state. Saturated at 26 °C, where
$p_{ws}=3.363$ kPa,
$$W_2=0.621945\,\frac{3.363}{101.3-3.363}=0.021357\ \text{kg/kg}
\qquad h_2=80.60\ \text{kJ/kg}$$
Moisture balance gives the make-up. Every kilogram of
water that leaves in the air must be replaced,
$$\boxed{\;\dot m_{ev}=\dot m_a\,(W_2-W_1)
=10.776\,(0.021357-0.007699)
=0.1472\ \text{kg/s}\;(\approx 0.1476\ \text{L/s},
\ 529.9\ \text{kg/h})\;}$$
That is 2.70 % of the circulating water, which is the classic
result: a cooling tower evaporates roughly 1 % of its throughput for
every 5 –6 K of range.
Water mass flow. At 44 °C the density of water
is 990.7 kg/m³, so
$$\dot m_w=0.0055\times 990.7=5.449\ \text{kg/s}$$
giving a liquid-to-gas ratio of $L/G=0.506$, which is on the air-rich
side for a small tower.
Energy balance on the tower. The air gains
$$\dot m_a\,(h_2-h_1)=10.776\,(80.60-37.62)
=463.19\ \text{kW}$$
but the induced-draft fan sits in that air stream and delivers its
4.75 kW into it, so the heat that actually came out of the water is
$$q_w=463.19-4.75=458.44\ \text{kW}$$
Solve for the leaving water temperature. The water
stream leaving is lighter than the stream entering by the evaporated mass,
$$\dot m_w c_p t_{w1}-(\dot m_w-\dot m_{ev})\,c_p\,t_{w2}=q_w$$
$$5.449(4.18)(44)-(5.449-0.1472)(4.18)\,t_{w2}=458.44$$
$$\boxed{\;t_{w2}=24.53\ ^\circ\text{C}\;}$$
Sanity-check the result against the wet bulb. The
entering air has a thermodynamic wet bulb of 13.41 °C, so the
tower achieves a range of 19.47 K and an approach of
11.12 K. A large approach like this is what one expects when the
leaving air is constrained to only 26 °C: the air leaves far from
equilibrium with the entering water, so the fill is not being used to its
thermodynamic limit. The driving potential remains positive at both ends
— the saturation enthalpy at 24.5 °C is 74.5 kJ/kg against
the entering air's 37.62, and at 44 °C it is 203 kJ/kg
against the leaving air's 80.60 — so the counterflow arrangement is
thermodynamically consistent.
Check: where the fan work is booked.
The 26 °C saturated state is taken to be measured at the tower
discharge, i.e. after the induced-draft fan, so the fan's
4.75 kW is already contained in $h_2$ and must be deducted before the
remainder is charged to the water. If instead the leaving state were measured
at the top of the fill, ahead of the fan, the water would have to supply the
whole 463.19 kW and the leaving water would be
24.32 °C. The difference is 0.21 K and does not affect
any conclusion, but the assumption should be stated.
Two practical riders belong with the make-up figure. The
0.1472 kg/s computed above is evaporation only; a real
tower also loses drift, typically 0.005 –0.2 % of the
circulating flow depending on the eliminators, and must be bled to control the
dissolved solids that the evaporation concentrates. At the common design
figure of three cycles of concentration the blowdown is half the evaporation
again, so the total make-up to specify for the water service would be nearer
0.22 kg/s than 0.1472 kg/s. And because the tower is an open
evaporative device operating at 24 –44 °C, it falls under
provincial Legionella control requirements — in British
Columbia and Ontario, a documented maintenance and water-treatment programme
is mandatory, not optional.