NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · May 2017

Question 1 of 8: Winter heating and humidifying plant — preheat, adiabatic spray, reheat

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. Professional Engineers of Ontario / Engineers Canada annual examination 16-Mec-B2 Environmental Control in Buildings, May 2017, three hours, open book. Eight problems of 20 points each; candidates are required to solve five, and all questions carry the same value. ASHRAE psychrometric charts (SI and inch-pound) and an R-717 pressure–enthalpy diagram are appended to the paper. All eight problems are solved here.

Reference texts for this subject.

Conventions used throughout. Moist-air properties are computed from the ASHRAE Handbook — Fundamentals Ch. 1 formulation at a barometric pressure of 101.325 kPa, so that every state point can be checked against the charts appended to the paper. Enthalpy is referred to dry air at $0^{\circ}\text{C}$ and liquid water at $0^{\circ}\text{C}$, i.e. $h = 1.006\,t + W\,(2501 + 1.86\,t)$ in kJ per kilogram of dry air. Problems 3 and 6 to 8 are worked in the inch-pound units in which they are set, as the examination directs.

Question 1: Winter heating and humidifying plant — preheat, adiabatic spray, reheat (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A once-through winter plant that mixes equal volumes of return and outdoor air, preheats the mixture, humidifies it adiabatically in a spray cabinet, reheats it and delivers it to a room whose entire load is sensible.

Design data, Problem 1
QuantitySymbolValue
Room heating load (all sensible)$Q_{s}$58 kW
Room dry bulb / wet bulb$t_{R}$ / $t_{R}^{*}$20 / 15 $^{\circ}\text{C}$
Outdoor dry bulb / dew point$t_{O}$ / $t_{d,O}$7 / 4 $^{\circ}\text{C}$
Supply air temperature to the room$t_{S}$40 $^{\circ}\text{C}$
Mixing proportion—equal volumes of O and R
Barometric pressure$p$101.325 kPa

Find. The plant diagram and its cycle on the psychrometric chart with every state point characterised, then the total air mass flow, the preheater and reheater duties, the saturation efficiency of the spray cabinet and the make-up water rate.

outdoor air O recirculated R mixing M preheater sensible 2 adiabatic spray cabinet make-up water 3 reheater sensible fan room S S state points: O outdoor, R room/return, M mixed, 2 off preheater, 3 off washer, S supply
Part (a) — plant arrangement. Equal volumes of outdoor air O and recirculated room air R are mixed to state M, warmed sensibly in the preheater to state 2, humidified along a line of constant wet bulb in the adiabatic spray cabinet to state 3, warmed sensibly again in the reheater and delivered at state S. The make-up water replaces exactly what the cabinet evaporates.
0 5 10 15 20 25 30 35 40 45 0 2 4 6 8 10 12 dry-bulb temperature, °C humidity ratio W, g/kg dry air 50% RH saturation O R M 2 3 S winter cycle: O + R to M, preheat M-2, adiabatic spray 2-3, reheat 3-S
Part (b) — the cycle on the psychrometric chart. O–R is the mixing line (M divides it in the ratio of the two mass flows); M–2 and 3–S are horizontal sensible-heating lines; 2–3 climbs the constant wet-bulb line of state 2 towards saturation. Note that the constant wet-bulb line through M itself reaches only 7.92 g/kg at saturation, short of the 8.58 g/kg the room needs — which is exactly why a preheater is present.

Approach. Fix the room and outdoor states from the ASHRAE moist-air relations; mix them on a mass basis obtained from their specific volumes; size the airflow from the sensible balance (the room load is entirely sensible, so the supply humidity ratio must equal the room humidity ratio); then walk the plant backwards from the required supply state to find how much preheat the washer needs in order to deliver that moisture.

  1. Part (c) — fix the room state R. The humidity ratio follows from the wet-bulb temperature through the adiabatic-saturation relation, with $W_{s}^{*} = 0.010648$ kg/kg at $15^{\circ}\text{C}$: $$W_{R}=\frac{(2501-2.326\,t^{*})W_{s}^{*}-1.006\,(t-t^{*})}{2501+1.86\,t-4.186\,t^{*}} =\frac{(2501-34.89)(0.010648)-1.006(20-15)}{2501+37.2-62.79}$$ which gives $W_{R}=0.008575$ kg/kg (8.58 g/kg), and hence $h_{R}=1.006(20)+0.008575(2501+37.2)=41.89$ kJ/kg, a relative humidity of 58.9 % and a dew point of $11.73^{\circ}\text{C}$. The humid volume is $v_{R}=0.8419\ \text{m}^{3}/\text{kg}$.
  2. Fix the outdoor state O. A dew point of $4^{\circ}\text{C}$ fixes the moisture directly, because the humidity ratio is saturated at that temperature: $$W_{O}=\frac{0.621945\,p_{ws}(4^{\circ}\text{C})}{p-p_{ws}(4^{\circ}\text{C})} =\frac{0.621945(813.4)}{101325-813.4}=0.005034\ \text{kg/kg}$$ so $h_{O}=1.006(7)+0.005034(2501+13.0)=19.70$ kJ/kg, 81.2 % saturated, with a wet bulb of $5.56^{\circ}\text{C}$ and $v_{O}=0.8001\ \text{m}^{3}/\text{kg}$.
  3. Mix on a mass basis, not a volume basis. "Equal volumes" is a statement about volumetric flow, and the two streams have different densities, so the mass fractions must come from the specific volumes. For a common volume flow $\dot V$ in each branch, $$x_{O}=\frac{\dot V/v_{O}}{\dot V/v_{O}+\dot V/v_{R}} =\frac{1/0.8001}{1/0.8001+1/0.8419}=0.5127$$ The colder outdoor air is denser, so it contributes slightly more than half the mass. Adiabatic mixing is exact in moisture and in enthalpy, so those are the two properties to weight: $$W_{M}=0.5127(0.005034)+0.4873(0.008575)=0.006759\ \text{kg/kg}$$ $$h_{M}=0.5127(19.70)+0.4873(41.89)=30.51\ \text{kJ/kg}$$ The dry bulb then follows from the enthalpy definition rather than from a weighted average of the two dry bulbs: $$t_{M}=\frac{h_{M}-2501\,W_{M}}{1.006+1.86\,W_{M}} =\frac{30.51-16.91}{1.0186}=\boxed{13.36^{\circ}\text{C}\ \text{dB},\ \ 10.54^{\circ}\text{C}\ \text{wB}}$$
  4. Part (d) — total air mass flow. The room gains no moisture, so the supply air must carry the room humidity ratio, $W_{S}=W_{R}=0.008575$ kg/kg, and the whole 58 kW is absorbed by cooling the supply air from $40^{\circ}\text{C}$ to the room temperature: $$\dot m=\frac{Q_{s}}{(c_{pa}+c_{pv}W_{R})(t_{S}-t_{R})} =\frac{58}{(1.006+1.86\times0.008575)(40-20)}=\boxed{2.838\ \text{kg/s}}$$ As a check, the same figure comes from the enthalpy difference, $58/(62.33-41.89)=2.838$ kg/s. At the supply state this is 2.55 $\text{m}^{3}/\text{s}$, and 2.33 $\text{m}^{3}/\text{s}$ entering the plant at the mixed state — the two branches therefore handle about 1.16 $\text{m}^{3}/\text{s}$ each.
  5. Test the washer before assuming a preheater duty. An adiabatic spray cabinet moves air along a line of constant thermodynamic wet bulb, so the wettest air it can possibly deliver is saturated air at the adiabatic saturation temperature of what enters it. For state M that temperature is $10.54^{\circ}\text{C}$, at which saturated air holds only $$W_{s}(10.54^{\circ}\text{C})=0.007916\ \text{kg/kg}\ \lt\ W_{R}=0.008575\ \text{kg/kg}$$ The mixture is 0.66 g/kg short of the room moisture even if the washer were perfect. Preheat is therefore genuinely required, and its purpose is to raise the wet bulb of the air offered to the cabinet, not to warm the supply air.
  6. Fix state 3 leaving the cabinet. A single-bank spray cabinet does not saturate the air completely; taking the usual design figure of 95 % saturation at exit (see the callout below), the leaving state has $W_{3}=W_{R}=0.008575$ kg/kg at 95 % relative humidity, which is $t_{3}=12.51^{\circ}\text{C}$ and $h_{3}=1.006(12.51)+0.008575(2501+23.3)=34.23$ kJ/kg.
  7. Work back through the cabinet to state 2. The cabinet is adiabatic, so the only energy crossing its boundary is the enthalpy of the make-up water, taken in at the leaving air temperature: $$h_{2}=h_{3}-(W_{3}-W_{2})\,c_{pw}t_{3}=34.23-(0.008575-0.006759)(4.186)(12.51)=34.14\ \text{kJ/kg}$$ Because the preheater is sensible, $W_{2}=W_{M}$ and $$t_{2}=\frac{34.14-2501(0.006759)}{1.006+1.86(0.006759)}=16.92^{\circ}\text{C}$$ whose adiabatic saturation temperature is $12.06^{\circ}\text{C}$ — and saturated air at that temperature holds 8.76 g/kg, comfortably more than the 8.58 g/kg required. The preheater has done its job.
  8. Part (e) — preheater and reheater duties. Both are straightforward enthalpy rises at the plant mass flow: $$Q_{pre}=\dot m\,(h_{2}-h_{M})=2.838(34.14-30.51)=\boxed{10.3\ \text{kW}}$$ $$Q_{re}=\dot m\,(h_{S}-h_{3})=2.838(62.33-34.23)=\boxed{79.7\ \text{kW}}$$ The reheater carries almost the whole 90 kW of plant duty, which is the characteristic signature of this cycle: the preheater exists only to make the humidification possible, while the reheater does the heating.
  9. Part (f) — saturation efficiency and make-up water. The adiabatic (saturation) efficiency of a washer compares the moisture it actually adds with the moisture full saturation at the same wet bulb would add: $$\eta=\frac{W_{3}-W_{2}}{W_{s}(t_{2}^{*})-W_{2}} =\frac{0.008575-0.006759}{0.008763-0.006759}=\boxed{90.7\ \%}$$ The temperature form of the same definition, $\eta=(t_{2}-t_{3})/(t_{2}-t_{2}^{*})=(16.92-12.51)/(16.92-12.06)=90.6\,\%$, agrees to within a tenth of a per cent, which confirms that states 2 and 3 lie on one wet-bulb line. The water evaporated — and therefore the make-up required — is $$\dot m_{w}=\dot m\,(W_{3}-W_{2})=2.838(0.008575-0.006759)=0.00515\ \text{kg/s}=\boxed{18.6\ \text{kg/h}}$$
  10. Check the whole plant. Everything entering the plant must balance what leaves it: $\dot m(h_{S}-h_{M}) - \dot m_{w}c_{pw}t_{3} = 2.838(62.33-30.51)-0.00515(4.186)(12.51)=90.02$ kW, against $Q_{pre}+Q_{re}=10.3+79.7=90.0$ kW. Independently, the make-up water must equal the moisture that the outdoor-air branch is short of the room condition, $\dot m\,x_{O}(W_{R}-W_{O})=2.838(0.5127)(0.003541)=0.00515$ kg/s — the same figure, reached without using the washer analysis at all.

Check: the split between preheat and reheat depends on one stated assumption. The paper fixes states O, R and S and the mixing ratio, but it does not say how closely the spray cabinet approaches saturation, and the preheat duty depends on that. Two readings bracket the answer, and both are quoted here under the examination's own instruction to state assumptions:

  • As solved above — a real single-bank cabinet leaving the air at 95 % saturation: preheater 10.3 kW, reheater 79.7 kW, cabinet efficiency 90.7 %.
  • An idealised full adiabatic saturator (exit on the saturation curve at $11.73^{\circ}\text{C}$): preheater 8.1 kW, reheater 82.0 kW, and the cabinet efficiency is then 100 % by construction — which makes part (f) vacuous, and is the reason the 95 % reading is preferred.

The make-up water rate, 18.6 kg/h, and the total plant duty, 90.0 kW, are the same under either reading, because both are fixed by the moisture and energy balances rather than by the washer performance.

Problem 1 — results
PointDry bulbWet bulb$W$, g/kg$h$, kJ/kgRH
O — outdoor air7.00 $^{\circ}\text{C}$5.56 $^{\circ}\text{C}$5.0319.7081.2 %
R — room / return20.00 $^{\circ}\text{C}$15.00 $^{\circ}\text{C}$8.5841.8958.9 %
M — mixed13.36 $^{\circ}\text{C}$10.54 $^{\circ}\text{C}$6.7630.5171.1 %
2 — off preheater16.92 $^{\circ}\text{C}$12.06 $^{\circ}\text{C}$6.7634.1456.5 %
3 — off spray cabinet12.51 $^{\circ}\text{C}$12.06 $^{\circ}\text{C}$8.5834.2395.0 %
S — supply40.00 $^{\circ}\text{C}$21.6 $^{\circ}\text{C}$8.5862.3318.7 %
(d) total air mass flow $\dot m = 2.838$ kg/s (2.55 $\text{m}^{3}/\text{s}$ at supply)
(e) preheater 10.3 kW; reheater 79.7 kW; plant total 90.0 kW
(f) spray-cabinet saturation efficiency 90.7 %; make-up water 18.6 kg/h
← Paper overview