22-Mec-B2 Environmental Control in Buildings · May 2017
Question 1 of 8: Winter heating and humidifying plant — preheat, adiabatic spray, reheat
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of
Ontario / Engineers Canada annual examination 16-Mec-B2 Environmental
Control in Buildings, May 2017, three hours, open book.
Eight problems of 20 points each; candidates are required to solve five, and all
questions carry the same value. ASHRAE psychrometric charts (SI and inch-pound)
and an R-717 pressure–enthalpy diagram are appended to the paper.
All eight problems are solved here.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination
code; Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6
(air-conditioning plant cycles), Ch. 9 (cooling towers), Ch. 15 (fans and
duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist
air), Ch. 5 (heat transmission in building structures), Ch. 8 (energy
estimating and the degree-day method), Ch. 12–13 (fluid flow, fans and
duct design).
ASHRAE Handbook — Fundamentals (2021) — Ch. 1
(psychrometrics), Ch. 14 (climatic design information), Ch. 18
(non-residential cooling and heating load calculations), Ch. 21 (duct
design), Ch. 25–27 (thermal and moisture performance of the building
envelope).
Çengel & Boles, Thermodynamics: An Engineering Approach,
9th ed., McGraw-Hill — Ch. 11 (refrigeration cycles, including
multistage compression with a flash chamber) and Ch. 14 (gas–vapour
mixtures and air conditioning).
National Energy Code of Canada for Buildings (NECB 2020) and CSA
F280 — the Canadian regulatory frame for envelope U-factors
and heating-load calculation.
Conventions used throughout. Moist-air properties are
computed from the ASHRAE Handbook — Fundamentals Ch. 1 formulation at a
barometric pressure of 101.325 kPa, so that every state point can be checked
against the charts appended to the paper. Enthalpy is referred to dry air at
$0^{\circ}\text{C}$ and liquid water at $0^{\circ}\text{C}$, i.e.
$h = 1.006\,t + W\,(2501 + 1.86\,t)$ in kJ per kilogram of dry air. Problems 3
and 6 to 8 are worked in the inch-pound units in which they are set, as the
examination directs.
Given. A once-through winter plant that mixes equal
volumes of return and outdoor air, preheats the mixture, humidifies it
adiabatically in a spray cabinet, reheats it and delivers it to a room whose
entire load is sensible.
Design data, Problem 1
Quantity
Symbol
Value
Room heating load (all sensible)
$Q_{s}$
58 kW
Room dry bulb / wet bulb
$t_{R}$ / $t_{R}^{*}$
20 / 15 $^{\circ}\text{C}$
Outdoor dry bulb / dew point
$t_{O}$ / $t_{d,O}$
7 / 4 $^{\circ}\text{C}$
Supply air temperature to the room
$t_{S}$
40 $^{\circ}\text{C}$
Mixing proportion
—
equal volumes of O and R
Barometric pressure
$p$
101.325 kPa
Find. The plant diagram and its cycle on the psychrometric
chart with every state point characterised, then the total air mass flow, the
preheater and reheater duties, the saturation efficiency of the spray cabinet
and the make-up water rate.
Part (a) — plant arrangement. Equal volumes of
outdoor air O and recirculated room air R are mixed to state M, warmed
sensibly in the preheater to state 2, humidified along a line of constant wet
bulb in the adiabatic spray cabinet to state 3, warmed sensibly again in the
reheater and delivered at state S. The make-up water replaces exactly what the
cabinet evaporates.
Part (b) — the cycle on the psychrometric chart.
O–R is the mixing line (M divides it in the ratio of the two mass flows);
M–2 and 3–S are horizontal sensible-heating lines; 2–3 climbs
the constant wet-bulb line of state 2 towards saturation. Note that the
constant wet-bulb line through M itself reaches only 7.92 g/kg at saturation,
short of the 8.58 g/kg the room needs — which is exactly why a
preheater is present.
Approach. Fix the room and outdoor states from the ASHRAE
moist-air relations; mix them on a mass basis obtained from their specific
volumes; size the airflow from the sensible balance (the room load is entirely
sensible, so the supply humidity ratio must equal the room humidity ratio);
then walk the plant backwards from the required supply state to find how much
preheat the washer needs in order to deliver that moisture.
Part (c) — fix the room state R. The humidity ratio
follows from the wet-bulb temperature through the adiabatic-saturation
relation, with $W_{s}^{*} = 0.010648$ kg/kg at $15^{\circ}\text{C}$:
$$W_{R}=\frac{(2501-2.326\,t^{*})W_{s}^{*}-1.006\,(t-t^{*})}{2501+1.86\,t-4.186\,t^{*}}
=\frac{(2501-34.89)(0.010648)-1.006(20-15)}{2501+37.2-62.79}$$
which gives $W_{R}=0.008575$ kg/kg (8.58 g/kg), and hence
$h_{R}=1.006(20)+0.008575(2501+37.2)=41.89$ kJ/kg, a relative humidity of
58.9 % and a dew point of $11.73^{\circ}\text{C}$. The humid volume is
$v_{R}=0.8419\ \text{m}^{3}/\text{kg}$.
Fix the outdoor state O. A dew point of
$4^{\circ}\text{C}$ fixes the moisture directly, because the humidity ratio is
saturated at that temperature:
$$W_{O}=\frac{0.621945\,p_{ws}(4^{\circ}\text{C})}{p-p_{ws}(4^{\circ}\text{C})}
=\frac{0.621945(813.4)}{101325-813.4}=0.005034\ \text{kg/kg}$$
so $h_{O}=1.006(7)+0.005034(2501+13.0)=19.70$ kJ/kg, 81.2 % saturated, with a
wet bulb of $5.56^{\circ}\text{C}$ and $v_{O}=0.8001\ \text{m}^{3}/\text{kg}$.
Mix on a mass basis, not a volume basis. "Equal volumes"
is a statement about volumetric flow, and the two streams have different
densities, so the mass fractions must come from the specific volumes. For a
common volume flow $\dot V$ in each branch,
$$x_{O}=\frac{\dot V/v_{O}}{\dot V/v_{O}+\dot V/v_{R}}
=\frac{1/0.8001}{1/0.8001+1/0.8419}=0.5127$$
The colder outdoor air is denser, so it contributes slightly more than half the
mass. Adiabatic mixing is exact in moisture and in enthalpy, so those are the
two properties to weight:
$$W_{M}=0.5127(0.005034)+0.4873(0.008575)=0.006759\ \text{kg/kg}$$
$$h_{M}=0.5127(19.70)+0.4873(41.89)=30.51\ \text{kJ/kg}$$
The dry bulb then follows from the enthalpy definition rather than from a
weighted average of the two dry bulbs:
$$t_{M}=\frac{h_{M}-2501\,W_{M}}{1.006+1.86\,W_{M}}
=\frac{30.51-16.91}{1.0186}=\boxed{13.36^{\circ}\text{C}\ \text{dB},\ \ 10.54^{\circ}\text{C}\ \text{wB}}$$
Part (d) — total air mass flow. The room gains no
moisture, so the supply air must carry the room humidity ratio,
$W_{S}=W_{R}=0.008575$ kg/kg, and the whole 58 kW is absorbed by cooling the
supply air from $40^{\circ}\text{C}$ to the room temperature:
$$\dot m=\frac{Q_{s}}{(c_{pa}+c_{pv}W_{R})(t_{S}-t_{R})}
=\frac{58}{(1.006+1.86\times0.008575)(40-20)}=\boxed{2.838\ \text{kg/s}}$$
As a check, the same figure comes from the enthalpy difference,
$58/(62.33-41.89)=2.838$ kg/s. At the supply state this is 2.55
$\text{m}^{3}/\text{s}$, and 2.33 $\text{m}^{3}/\text{s}$ entering the plant at
the mixed state — the two branches therefore handle about 1.16
$\text{m}^{3}/\text{s}$ each.
Test the washer before assuming a preheater duty. An
adiabatic spray cabinet moves air along a line of constant thermodynamic wet
bulb, so the wettest air it can possibly deliver is saturated air at the
adiabatic saturation temperature of what enters it. For state M that
temperature is $10.54^{\circ}\text{C}$, at which saturated air holds only
$$W_{s}(10.54^{\circ}\text{C})=0.007916\ \text{kg/kg}\ \lt\ W_{R}=0.008575\ \text{kg/kg}$$
The mixture is 0.66 g/kg short of the room moisture even if the washer were
perfect. Preheat is therefore genuinely required, and its purpose is
to raise the wet bulb of the air offered to the cabinet, not to warm the
supply air.
Fix state 3 leaving the cabinet. A single-bank spray
cabinet does not saturate the air completely; taking the usual design figure
of 95 % saturation at exit (see the callout below), the leaving state has
$W_{3}=W_{R}=0.008575$ kg/kg at 95 % relative humidity, which is
$t_{3}=12.51^{\circ}\text{C}$ and
$h_{3}=1.006(12.51)+0.008575(2501+23.3)=34.23$ kJ/kg.
Work back through the cabinet to state 2. The cabinet is
adiabatic, so the only energy crossing its boundary is the enthalpy of the
make-up water, taken in at the leaving air temperature:
$$h_{2}=h_{3}-(W_{3}-W_{2})\,c_{pw}t_{3}=34.23-(0.008575-0.006759)(4.186)(12.51)=34.14\ \text{kJ/kg}$$
Because the preheater is sensible, $W_{2}=W_{M}$ and
$$t_{2}=\frac{34.14-2501(0.006759)}{1.006+1.86(0.006759)}=16.92^{\circ}\text{C}$$
whose adiabatic saturation temperature is $12.06^{\circ}\text{C}$ — and
saturated air at that temperature holds 8.76 g/kg, comfortably more than the
8.58 g/kg required. The preheater has done its job.
Part (e) — preheater and reheater duties. Both are
straightforward enthalpy rises at the plant mass flow:
$$Q_{pre}=\dot m\,(h_{2}-h_{M})=2.838(34.14-30.51)=\boxed{10.3\ \text{kW}}$$
$$Q_{re}=\dot m\,(h_{S}-h_{3})=2.838(62.33-34.23)=\boxed{79.7\ \text{kW}}$$
The reheater carries almost the whole 90 kW of plant duty, which is the
characteristic signature of this cycle: the preheater exists only to make the
humidification possible, while the reheater does the heating.
Part (f) — saturation efficiency and make-up water.
The adiabatic (saturation) efficiency of a washer compares the moisture it
actually adds with the moisture full saturation at the same wet bulb would add:
$$\eta=\frac{W_{3}-W_{2}}{W_{s}(t_{2}^{*})-W_{2}}
=\frac{0.008575-0.006759}{0.008763-0.006759}=\boxed{90.7\ \%}$$
The temperature form of the same definition,
$\eta=(t_{2}-t_{3})/(t_{2}-t_{2}^{*})=(16.92-12.51)/(16.92-12.06)=90.6\,\%$,
agrees to within a tenth of a per cent, which confirms that states 2 and 3 lie
on one wet-bulb line. The water evaporated — and therefore the make-up
required — is
$$\dot m_{w}=\dot m\,(W_{3}-W_{2})=2.838(0.008575-0.006759)=0.00515\ \text{kg/s}=\boxed{18.6\ \text{kg/h}}$$
Check the whole plant. Everything entering the plant must
balance what leaves it:
$\dot m(h_{S}-h_{M}) - \dot m_{w}c_{pw}t_{3} = 2.838(62.33-30.51)-0.00515(4.186)(12.51)=90.02$ kW,
against $Q_{pre}+Q_{re}=10.3+79.7=90.0$ kW. Independently, the make-up water
must equal the moisture that the outdoor-air branch is short of the room
condition, $\dot m\,x_{O}(W_{R}-W_{O})=2.838(0.5127)(0.003541)=0.00515$ kg/s
— the same figure, reached without using the washer analysis at all.
Check: the split between preheat and reheat
depends on one stated assumption. The paper fixes states O, R and S
and the mixing ratio, but it does not say how closely the spray cabinet
approaches saturation, and the preheat duty depends on that. Two readings
bracket the answer, and both are quoted here under the examination's own
instruction to state assumptions:
As solved above — a real single-bank cabinet leaving the air
at 95 % saturation: preheater 10.3 kW, reheater 79.7 kW, cabinet efficiency
90.7 %.
An idealised full adiabatic saturator (exit on the saturation
curve at $11.73^{\circ}\text{C}$): preheater 8.1 kW, reheater 82.0 kW, and the
cabinet efficiency is then 100 % by construction — which makes part (f)
vacuous, and is the reason the 95 % reading is preferred.
The make-up water rate, 18.6 kg/h, and the total plant duty, 90.0 kW, are
the same under either reading, because both are fixed by the moisture and
energy balances rather than by the washer performance.
Problem 1 — results
Point
Dry bulb
Wet bulb
$W$, g/kg
$h$, kJ/kg
RH
O — outdoor air
7.00 $^{\circ}\text{C}$
5.56 $^{\circ}\text{C}$
5.03
19.70
81.2 %
R — room / return
20.00 $^{\circ}\text{C}$
15.00 $^{\circ}\text{C}$
8.58
41.89
58.9 %
M — mixed
13.36 $^{\circ}\text{C}$
10.54 $^{\circ}\text{C}$
6.76
30.51
71.1 %
2 — off preheater
16.92 $^{\circ}\text{C}$
12.06 $^{\circ}\text{C}$
6.76
34.14
56.5 %
3 — off spray cabinet
12.51 $^{\circ}\text{C}$
12.06 $^{\circ}\text{C}$
8.58
34.23
95.0 %
S — supply
40.00 $^{\circ}\text{C}$
21.6 $^{\circ}\text{C}$
8.58
62.33
18.7 %
(d) total air mass flow $\dot m = 2.838$ kg/s (2.55 $\text{m}^{3}/\text{s}$ at supply)