22-Mec-B2 Environmental Control in Buildings · May 2017
Question 3 of 8: Induced-draught counter-flow cooling tower
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of
Ontario / Engineers Canada annual examination 16-Mec-B2 Environmental
Control in Buildings, May 2017, three hours, open book.
Eight problems of 20 points each; candidates are required to solve five, and all
questions carry the same value. ASHRAE psychrometric charts (SI and inch-pound)
and an R-717 pressure–enthalpy diagram are appended to the paper.
All eight problems are solved here.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination
code; Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6
(air-conditioning plant cycles), Ch. 9 (cooling towers), Ch. 15 (fans and
duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist
air), Ch. 5 (heat transmission in building structures), Ch. 8 (energy
estimating and the degree-day method), Ch. 12–13 (fluid flow, fans and
duct design).
ASHRAE Handbook — Fundamentals (2021) — Ch. 1
(psychrometrics), Ch. 14 (climatic design information), Ch. 18
(non-residential cooling and heating load calculations), Ch. 21 (duct
design), Ch. 25–27 (thermal and moisture performance of the building
envelope).
Çengel & Boles, Thermodynamics: An Engineering Approach,
9th ed., McGraw-Hill — Ch. 11 (refrigeration cycles, including
multistage compression with a flash chamber) and Ch. 14 (gas–vapour
mixtures and air conditioning).
National Energy Code of Canada for Buildings (NECB 2020) and CSA
F280 — the Canadian regulatory frame for envelope U-factors
and heating-load calculation.
Conventions used throughout. Moist-air properties are
computed from the ASHRAE Handbook — Fundamentals Ch. 1 formulation at a
barometric pressure of 101.325 kPa, so that every state point can be checked
against the charts appended to the paper. Enthalpy is referred to dry air at
$0^{\circ}\text{C}$ and liquid water at $0^{\circ}\text{C}$, i.e.
$h = 1.006\,t + W\,(2501 + 1.86\,t)$ in kJ per kilogram of dry air. Problems 3
and 6 to 8 are worked in the inch-pound units in which they are set, as the
examination directs.
Given. An induced-draught counter-flow tower rejecting the
condenser heat of a refrigeration plant, worked in inch-pound units as the
question is set.
Design data, Problem 3
Quantity
Symbol
Value
Entering air, dry bulb / wet bulb
$t_{1}$ / $t_{1}^{*}$
70 / 55 $^{\circ}\text{F}$
Leaving air, dry bulb / relative humidity
$t_{2}$ / $\phi_{2}$
90 $^{\circ}\text{F}$ / 95 %
Water flow
$\dot m_{w}$
3 200 lb/min
Water on / off (range 30 $^{\circ}\text{F}$)
$t_{w1}$ / $t_{w2}$
105 / 75 $^{\circ}\text{F}$
Drift loss
—
0.3 % of the circulating water
Find. The tower sketch and its control scheme; then the
entering-air enthalpy, specific volume and relative humidity, the inlet
volumetric flow, the evaporative loss as a percentage of the circulating water,
and the total make-up rate.
Induced-draught counter-flow tower serving a
refrigeration condenser. Air is drawn in through louvres at the base, passes
upwards through the fill against the falling water and is discharged by the fan
at the top through drift eliminators. Control: a temperature transmitter (TT)
in the cold-water line to the condenser signals the controller (TC), which
stages or modulates the fan — two-speed motor, or a variable-frequency
drive — to hold the leaving-water temperature at set point. A basin
by-pass valve maintains condensing head in cold weather when the fan alone
cannot be throttled far enough.
Approach. Fix both air states psychrometrically; write the
steady-flow energy balance across the tower, remembering that the evaporated
water leaves in the air stream and must be replaced by make-up entering at the
cold-water temperature; solve for the air mass flow, then convert to volume at
the inlet state.
Part (a) — the entering air state. At 70 / 55
$^{\circ}\text{F}$ the inch-pound adiabatic-saturation relation gives
$$W_{1}=\frac{(1093-0.556\,t^{*})W_{s}^{*}-0.240\,(t-t^{*})}{1093+0.444\,t-t^{*}}
=0.005770\ \text{lb/lb}$$
from which
$$h_{1}=0.240(70)+0.005770\,[1061+0.444(70)]=\boxed{23.10\ \text{Btu/lb}}$$
$$v_{1}=\frac{0.370486\,(70+459.67)(1+1.6079\,W_{1})}{14.696}=\boxed{13.48\ \text{ft}^{3}/\text{lb}}$$
$$\phi_{1}=\frac{p\,W_{1}}{(0.621945+W_{1})\,p_{ws}(70^{\circ}\text{F})}=\boxed{37.2\ \%}$$
The leaving air state. At 90 $^{\circ}\text{F}$ and 95 %
relative humidity, $W_{2}=0.029428$ lb/lb and
$h_{2}=0.240(90)+0.029428[1061+0.444(90)]=54.00$ Btu/lb. The air therefore
gains 30.90 Btu per pound of dry air and picks up 0.023658 lb of water per
pound of dry air.
Part (b) — energy balance and air flow. The water
side gives up its sensible heat; the make-up entering at the cold-water
temperature carries back part of what the evaporation removed, so
$$\dot m_{a}\,(h_{2}-h_{1})=\dot m_{w}\,c_{pw}\,(t_{w1}-t_{w2})
+\dot m_{a}\,(W_{2}-W_{1})\,c_{pw}(t_{w2}-32)$$
Substituting,
$$\dot m_{a}\,(30.90)=3200(1.0)(30)+\dot m_{a}(0.023658)(43)$$
$$\dot m_{a}=\frac{96\,000}{30.90-1.017}=\boxed{3\,213\ \text{lb/min of dry air}}$$
and at the inlet specific volume this is
$$\dot V_{1}=\dot m_{a}\,v_{1}=3213(13.48)=\boxed{43\,300\ \text{ft}^{3}/\text{min}}$$
The liquid-to-gas ratio is $L/G = 3200/3213 = 0.996$, squarely in the 0.8 to
1.5 band that counter-flow towers are built for, and the approach to the
entering wet bulb is $75-55=20\ ^{\circ}\text{F}$ — loose, but ordinary
for a condenser-water tower.
Part (c) — evaporative loss. The moisture the air
carries away is
$$\dot m_{ev}=\dot m_{a}(W_{2}-W_{1})=3213(0.023658)=76.0\ \text{lb/min}$$
$$\text{evaporative loss}=\frac{76.0}{3200}\times100=\boxed{2.38\ \%}$$
The familiar rule of thumb — about 1 % of the circulating flow for each
$10\ ^{\circ}\text{F}$ of range — would predict 3 %, so the computed
figure is the right order and slightly lower, as expected when the entering air
is already at 37 % relative humidity rather than bone dry.
Part (d) — total make-up. Drift is water carried out
as entrained droplets, not vapour, and is quoted as a fraction of the
circulating flow:
$$\dot m_{drift}=0.003(3200)=9.6\ \text{lb/min}$$
$$\dot m_{makeup}=\dot m_{ev}+\dot m_{drift}=76.0+9.6=\boxed{85.6\ \text{lb/min}}$$
which is 10.3 US gallons per minute, or 2.68 % of the circulating water.
Check the balance and comment on blowdown. The heat
rejected is $3200(1.0)(30)=96\,000$ Btu/min = 1 688 kW, and the air stream
carries away $3213(30.90)-76.0(43)=96\,000$ Btu/min — identical, as it
must be. In service a third loss, blowdown, is added to control the
concentration of dissolved solids: at $N$ cycles of concentration the blowdown
is $\dot m_{ev}/(N-1)-\dot m_{drift}$, so at four cycles it would be
$76.0/3-9.6=15.7$ lb/min and the make-up would rise to about 101 lb/min. The
question asks only for evaporation and drift, so 85.6 lb/min is the answer, but
the omission is worth naming.