22-Mec-B2 Environmental Control in Buildings · May 2017
Question 2 of 8: Summer cooling and dehumidifying plant — mixed state, coil duty, ADP and by-pass factor
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of
Ontario / Engineers Canada annual examination 16-Mec-B2 Environmental
Control in Buildings, May 2017, three hours, open book.
Eight problems of 20 points each; candidates are required to solve five, and all
questions carry the same value. ASHRAE psychrometric charts (SI and inch-pound)
and an R-717 pressure–enthalpy diagram are appended to the paper.
All eight problems are solved here.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination
code; Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6
(air-conditioning plant cycles), Ch. 9 (cooling towers), Ch. 15 (fans and
duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist
air), Ch. 5 (heat transmission in building structures), Ch. 8 (energy
estimating and the degree-day method), Ch. 12–13 (fluid flow, fans and
duct design).
ASHRAE Handbook — Fundamentals (2021) — Ch. 1
(psychrometrics), Ch. 14 (climatic design information), Ch. 18
(non-residential cooling and heating load calculations), Ch. 21 (duct
design), Ch. 25–27 (thermal and moisture performance of the building
envelope).
Çengel & Boles, Thermodynamics: An Engineering Approach,
9th ed., McGraw-Hill — Ch. 11 (refrigeration cycles, including
multistage compression with a flash chamber) and Ch. 14 (gas–vapour
mixtures and air conditioning).
National Energy Code of Canada for Buildings (NECB 2020) and CSA
F280 — the Canadian regulatory frame for envelope U-factors
and heating-load calculation.
Conventions used throughout. Moist-air properties are
computed from the ASHRAE Handbook — Fundamentals Ch. 1 formulation at a
barometric pressure of 101.325 kPa, so that every state point can be checked
against the charts appended to the paper. Enthalpy is referred to dry air at
$0^{\circ}\text{C}$ and liquid water at $0^{\circ}\text{C}$, i.e.
$h = 1.006\,t + W\,(2501 + 1.86\,t)$ in kJ per kilogram of dry air. Problems 3
and 6 to 8 are worked in the inch-pound units in which they are set, as the
examination directs.
Question 2: Summer cooling and dehumidifying plant — mixed state, coil duty, ADP and by-pass factor (20 marks)
Given. A recirculating single-coil plant serving a space
with both sensible and latent gains, with a fixed ventilation rate and a fixed
supply dry-bulb temperature.
Find. The plant diagram and chart cycle with all state
points, the state of the air entering the coil, the coil duty, apparatus dew
point and by-pass factor, and the room and grand sensible heat factors.
Part (a) — plant arrangement. Ventilation air O
joins the recirculated fraction of the return air at M; the mixture passes the
filter, the cooling and dehumidifying coil and the supply fan and enters the
space at S. The balance of the return air is relieved to outside, so that the
relief flow equals the ventilation flow.
Approach. The room moisture balance fixes the supply
humidity ratio once the airflow is known from the sensible balance; the
ventilation fraction then fixes the mixed state entering the coil; the coil
duty is the enthalpy drop across it. The apparatus dew point is found by
extending the coil process line to saturation — and here that
construction has something instructive to say.
Part (c) — fix the space and outdoor states. From
25 / 18 $^{\circ}\text{C}$, the adiabatic-saturation relation gives
$W_{R}=0.010018$ kg/kg, so $h_{R}=1.006(25)+0.010018(2501+46.5)=50.67$ kJ/kg at
50.7 % relative humidity and a dew point of $14.07^{\circ}\text{C}$. From
35 / 25 $^{\circ}\text{C}$, $W_{O}=0.015842$ kg/kg and $h_{O}=75.86$ kJ/kg at
44.7 % relative humidity.
Size the supply air on the sensible balance. The supply
enters at $15^{\circ}\text{C}$ and leaves at the room temperature, so
$$\dot m=\frac{q_{s}}{(c_{pa}+c_{pv}W_{R})(t_{R}-t_{S})}
=\frac{25}{(1.006+1.86\times0.010018)(25-15)}=\boxed{2.440\ \text{kg/s}}$$
which is 2.02 $\text{m}^{3}/\text{s}$ (about 4 300 cfm) at the supply state.
The room moisture balance fixes the supply humidity ratio.
Every kilogram of moisture released in the space must leave in the air stream:
$$W_{S}=W_{R}-\frac{\dot m_{w}}{\dot m}=0.010018-\frac{0.005556}{2.440}
=0.007741\ \text{kg/kg}$$
so the supply state is $15^{\circ}\text{C}$ dry bulb, $12.25^{\circ}\text{C}$
wet bulb, 73.0 % relative humidity, $h_{S}=34.67$ kJ/kg, with a dew point of
$10.21^{\circ}\text{C}$. The room total load is then
$\dot m(h_{R}-h_{S})=2.440(50.67-34.67)=39.05$ kW, of which 25 kW is sensible
and 14.05 kW latent.
Part (f), first half — room sensible heat factor.
$$\mathrm{RSHF}=\frac{q_{s}}{q_{s}+q_{l}}=\frac{25.0}{39.05}=\boxed{0.640}$$
A room factor this low is the whole character of the problem: for every three
units of cooling, more than one is spent condensing water.
Part (d) — the state entering the coil. The
ventilation air is 0.480 kg/s, so 1.960 kg/s is recirculated (19.7 % outdoor
air by mass). Weighting moisture and enthalpy,
$$W_{M}=\frac{0.480(0.015842)+1.960(0.010018)}{2.440}=0.011164\ \text{kg/kg},
\qquad h_{M}=\frac{0.480(75.86)+1.960(50.67)}{2.440}=55.63\ \text{kJ/kg}$$
and recovering the dry bulb from the enthalpy definition,
$$t_{M}=\frac{55.63-2501(0.011164)}{1.006+1.86(0.011164)}
=\boxed{26.98^{\circ}\text{C}\ \text{dB},\ \ 19.54^{\circ}\text{C}\ \text{wB}}$$
Part (e), first part — coil capacity. The coil takes
the mixture down to the supply state, so
$$Q_{c}=\dot m\,(h_{M}-h_{S})=2.440(55.63-34.67)=\boxed{51.1\ \text{kW}}$$
This is exactly the room load plus the outdoor-air load,
$39.05+0.480(75.86-50.67)=39.05+12.09=51.14$ kW — a check that costs one
line and catches most mixing errors.
Part (f), second half — grand sensible heat factor.
The sensible part of the coil duty is the dry-bulb drop at the entering
moisture content,
$\dot m(c_{pa}+c_{pv}W_{M})(t_{M}-t_{S})=2.440(1.0268)(26.98-15)=30.02$ kW, so
$$\mathrm{GSHF}=\frac{30.02}{51.14}=\boxed{0.587}$$
The coil factor is lower than the room factor because the outdoor air brings in
a further 7.1 kW of latent load on top of the room's own 14.05 kW.
Part (e), second part — the apparatus dew point. The
apparatus dew point is where the straight coil process line M–S, extended
below S, meets the saturation curve. Extending it here:
$$W(t)=W_{S}+\frac{W_{M}-W_{S}}{t_{M}-t_{S}}\,(t-t_{S})
=0.007741+0.0002856\,(t-15)$$
At $10^{\circ}\text{C}$ this line lies at 6.31 g/kg against 7.66 g/kg on the
saturation curve; at $5^{\circ}\text{C}$, 4.89 against 5.42; at
$0^{\circ}\text{C}$, 3.46 against 3.79. The line never reaches
saturation. Its closest approach is 0.30 g/kg, at about
$-1.2^{\circ}\text{C}$, so there is no apparatus dew point and no by-pass
factor for the process as literally specified. The physical statement of the
same fact is that a state of $15^{\circ}\text{C}$ at 73 % relative humidity is
far drier than any real coil leaves its air — coils leave air at 90 to
95 % saturation.
Resolve it the way a designer would. The moisture balance
is not negotiable: the coil must deliver $W=0.007741$ kg/kg or the space
humidity will not hold. What can be relaxed is the assumption that the air
reaches the room at exactly the temperature it leaves the coil, because the fan
and the duct run add heat. Taking a normal four-row chilled-water coil with a
by-pass factor $\mathrm{BF}=0.15$, the coil surface state follows from
$W_{S}=W_{adp}+\mathrm{BF}\,(W_{M}-W_{adp})$:
$$W_{adp}=\frac{0.007741-0.15(0.011164)}{0.85}=0.007137\ \text{kg/kg}
\;\Rightarrow\; \mathrm{ADP}=\boxed{9.0^{\circ}\text{C}}$$
$$t_{off}=\mathrm{ADP}+\mathrm{BF}\,(t_{M}-\mathrm{ADP})=9.02+0.15(26.98-9.02)=11.71^{\circ}\text{C}$$
which is 90.5 % saturated — entirely normal. The coil duty on this basis
is $\dot m(h_{M}-h_{off})=2.440(55.63-31.32)=59.3$ kW, and the remaining
$3.3\ \text{K}$ rise to the stated $15^{\circ}\text{C}$, worth 8.2 kW, is made
up by fan and duct gain and, if that is not enough, by a small reheat
coil.
Part (b) — plot it. The chart below carries all five
points. Note that S does not lie on the line from M to the apparatus
dew point; it lies to the right of the off-coil state C, on the same horizontal
line, because the fan and duct gain is a sensible process.
Part (b) — the cycle. O and R mix to M in the ratio
0.197 : 0.803 by mass. The coil line M–C reaches saturation at the
apparatus dew point of $9.0^{\circ}\text{C}$ with a by-pass factor of 0.15;
C–S is the sensible fan and duct pick-up; S–R is the room line,
whose slope is the room sensible heat factor of 0.640.
Check: the paper over-specifies this
plant. Three data fix the supply state twice over: the sensible gain
and the supply dry bulb fix the airflow, and the moisture gain then fixes the
supply humidity ratio — but the resulting state (73 % saturated) cannot
be produced by a cooling coil, since the coil line from the mixed state misses
the saturation curve by 0.30 g/kg. This is a small inconsistency, not an
error in the arithmetic: raising the supply temperature by about a degree, or
reducing the moisture gain from 20 to about 18.9 kg/h, would make the
construction close exactly. Both readings are reported above — the coil
duty as specified, 51.1 kW, and the duty of a realisable coil
holding the same moisture balance, 59.3 kW at an apparatus dew point of
$9.0^{\circ}\text{C}$ with a by-pass factor of 0.15. The examination's
instruction 1 invites exactly this treatment.
Problem 2 — results
Point
Dry bulb
Wet bulb
$W$, g/kg
$h$, kJ/kg
RH
O — outdoor
35.00 $^{\circ}\text{C}$
25.00 $^{\circ}\text{C}$
15.84
75.86
44.7 %
R — space / return
25.00 $^{\circ}\text{C}$
18.00 $^{\circ}\text{C}$
10.02
50.67
50.7 %
M — entering the coil
26.98 $^{\circ}\text{C}$
19.54 $^{\circ}\text{C}$
11.16
55.63
50.1 %
C — off the coil (BF 0.15)
11.71 $^{\circ}\text{C}$
10.9 $^{\circ}\text{C}$
7.74
31.32
90.5 %
S — supply to the space
15.00 $^{\circ}\text{C}$
12.25 $^{\circ}\text{C}$
7.74
34.67
73.0 %
supply air 2.440 kg/s (2.02 $\text{m}^{3}/\text{s}$); outdoor air 0.480 kg/s = 19.7 % by mass
(e) coil duty 51.1 kW as specified, 59.3 kW as realisable; ADP 9.0 $^{\circ}\text{C}$; by-pass factor 0.15