22-Mec-B2 Environmental Control in Buildings · December 2018
Question 2 of 8: Preheat, adiabatic saturation and reheat on 100% outdoor air
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2018 —
16-Mec-B2 Environmental Control in Buildings. Three hours, open book
(an environmental-control text and steam tables are expected; any non-communicating calculator is
permitted). Eight problems are printed and candidates solve five: Problem 1 carries
30 points, Problem 2 carries 10 points and Problems 3–8 carry 20 points each, so the printed
paper totals 160 points and a graded script totals 100. Psychrometric charts (SI and IP) and an
R-134a pressure–enthalpy diagram are attached to the paper. All eight problems are worked
below.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — the CLTD/SCL/CLF cooling-load method, duct design and the
degree-day/bin energy methods.
Jones, Air Conditioning Engineering, 5th ed. — plant psychrometry, percentage
saturation, apparatus dew point and coil by-pass factor.
Incropera & DeWitt, Fundamentals of Heat and Mass Transfer, 8th ed., Ch. 3 —
one-dimensional composite-wall conduction; Table A.3 for building-material conductivities.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour
compression cycles, compressor displacement and volumetric efficiency.
ASHRAE Refrigerant Tables for R-134a (datum hf = sf
= 0 at −40 °F, the datum of the attached chart).
Canadian context: National Energy Code of Canada for Buildings (NECB 2020), Canada Green
Building Council (CAGBC) LEED v4 and Zero Carbon Building Standard, and Environment and Climate
Change Canada Canadian Climate Normals for degree-day data.
Question 2: Preheat, adiabatic saturation and reheat on 100% outdoor air (10 marks)
preheat coil → adiabatic saturator → reheat coil → space
Find. The plant diagram, the supply air temperature, the five state points with
their dry- and wet-bulb temperatures, the preheat and reheat coil duties in Btu/hr, and the
humidification water make-up in US gpm.
Figure 2.1 (part a) — The plant. Because the process demands 100% outdoor
air there is no return-air path: all 7000 scfm is drawn in at state O, conditioned through states 2
and 3, delivered at state S and exhausted from the space. Make-up water enters the saturator sump at
the saturator temperature.
Approach. The room load is entirely sensible, so the supply air must carry the
room's own humidity ratio and be delivered hot enough to offset 200 000 Btu/hr. Working backwards,
the saturator temperature fixes the $60\,{}^{\circ}\text{F}$ thermodynamic wet-bulb line: the preheat
coil raises the outdoor air at constant humidity ratio until it reaches that line, the saturator moves
it along the line up to the required humidity ratio, and the reheat coil then raises it at constant
humidity ratio to the supply temperature.
Convert the ventilation rate to a dry-air mass flow. "Standard" cubic feet are
referred to standard air at $0.075$ lb ft$^{-3}$, so
$$\dot m_{da}=7000\ \text{ft}^3\text{min}^{-1}\times 60\ \frac{\text{min}}{\text{h}}\times 0.075\ \frac{\text{lb}}{\text{ft}^3}=31\,500\ \text{lb}_{da}\,\text{h}^{-1}$$
Every duty below is this one mass flow multiplied by an enthalpy or humidity-ratio difference.
Fix the room and outdoor states. With $p = 14.696$ psia,
$W = 0.621945\,p_w/(p-p_w)$ and $h = 0.240\,t + W(1061 + 0.444\,t)$. At the room, $p_{ws}(75) = 0.4300$
psia and $\phi = 0.50$ give $W_R = 0.00924$ lb/lb (64.7 grains per pound) and
$h_R = 28.11$ Btu/lb$_{da}$. Outdoor air saturated at $20\,{}^{\circ}\text{F}$ has
$W_O = 0.002144$ lb/lb and $h_O = 7.09$ Btu/lb$_{da}$; being saturated, its wet bulb equals its dry
bulb at $20\,{}^{\circ}\text{F}$.
Part (b) — the supply temperature. The room adds no moisture, so
$W_S = W_R$ and the whole room load appears as a dry-bulb difference. With
$c_p = 0.240 + 0.444W_R = 0.2441$ Btu lb$^{-1}$°F$^{-1}$,
$$t_S=t_R+\frac{q_s}{\dot m_{da}c_p}=75+\frac{200\,000}{31\,500\times 0.2441}$$
$$\boxed{\;t_S = 101.0\,{}^{\circ}\text{F dry bulb},\ W_S = 0.00924\ \text{lb/lb}\ (22.0\%\ \text{RH})\;}$$
The familiar rule of thumb agrees: $t_S = 75 + 200\,000/(1.10\times 7000) = 101.0\,{}^{\circ}\text{F}$,
which it must, because the 1.10 coefficient is built from the same standard density used in step 1.
Locate state 2, the preheat coil exit. A preheat coil adds no moisture, so state 2
lies on the vertical $W_O = 0.002144$ line; the saturator can only move air along a
$60\,{}^{\circ}\text{F}$ wet-bulb line, so state 2 must already be on that line. Saturated air
at the saturator temperature has $W^{*} = W_{sat}(60) = 0.011041$ lb/lb and $h^{*} = 26.41$ Btu/lb, and
the adiabatic-saturation energy balance (the sump water enters at $t^{*}$, so $h_f = t^{*}-32 = 28$
Btu/lb) gives the enthalpy anywhere on that line as
$$h = h^{*}-(W^{*}-W)\,h_f \quad\Rightarrow\quad h_2 = 26.41-(0.011041-0.002144)(28)=26.16\ \text{Btu/lb}$$
Inverting $h = 0.240t + W(1061+0.444t)$ at $W = W_O$,
$$t_2=\frac{h_2-1061\,W_O}{0.240+0.444\,W_O}=\frac{26.16-2.275}{0.24095}=99.1\,{}^{\circ}\text{F}$$
so the preheat coil must lift the outdoor air all the way to $99.1\,{}^{\circ}\text{F}$ before the
washer will do any good. Its relative humidity there is only 5.5% — hot, bone-dry air, which is
precisely what an adiabatic humidifier needs.
Locate state 3, the saturator exit. The saturator must deliver the room's humidity
ratio, $W_3 = W_R = 0.00924$ lb/lb. Moving along the same line,
$h_3 = h_2 + (W_3-W_O)h_f = 26.16 + (0.007096)(28) = 26.36$ Btu/lb, and inverting the enthalpy
relation at $W_3$ gives
$$\boxed{\;t_3 = 67.8\,{}^{\circ}\text{F dry bulb},\ 63.7\%\ \text{RH},\ t_{wb}=60.0\,{}^{\circ}\text{F}\;}$$
The cabinet is therefore not saturating the air fully; its saturating efficiency is
$$\eta_{sat}=\frac{W_3-W_O}{W^{*}-W_O}=\frac{0.007096}{0.008897}=79.7\%$$
which is a realistic single-bank spray performance and confirms that the plant as specified is
physically achievable.
Part (c) — the five state points. Plotting states O, 2, 3, S and R on the IP
chart gives the cycle in Figure 2.2, with dry- and wet-bulb temperatures as tabulated:
Point
Where
Dry bulb (°F)
Wet bulb (°F)
$W$ (lb/lb)
$h$ (Btu/lb)
O
outdoor air, saturated
20.0
20.0
0.002144
7.09
2
preheat coil exit
99.1
60.0
0.002144
26.16
3
saturator exit
67.8
60.0
0.00924
26.36
S
supply to space
101.0
70.8
0.00924
34.46
R
room / exhaust
75.0
62.6
0.00924
28.11
The signature of the cycle is that states 2 and 3 share a wet bulb of exactly
$60\,{}^{\circ}\text{F}$ — that is what "adiabatic" means on this chart.
Figure 2.2 (part c) — The cycle on the IP chart. O→2 is horizontal
(preheat, no moisture added); 2→3 runs down the $60\,{}^{\circ}\text{F}$ wet-bulb line
(adiabatic saturation); 3→S is horizontal again (reheat); S→R is the sensible room
process.
Part (d) — preheat coil duty. The coil raises the air from O to 2 at constant
humidity ratio:
$$Q_{pre}=\dot m_{da}(h_2-h_O)=31\,500\,(26.16-7.09)$$
$$\boxed{\;Q_{pre}= 600\,600\ \text{Btu}\,\text{h}^{-1}\;(176\ \text{kW})\;}$$
This is three times the room load, which is the honest cost of a 100%-outdoor-air process plant on a
$20\,{}^{\circ}\text{F}$ day.
Part (e) — reheat coil duty. From state 3 to state S, again at constant
humidity ratio:
$$Q_{re}=\dot m_{da}(h_S-h_3)=31\,500\,(34.46-26.36)$$
$$\boxed{\;Q_{re}= 255\,100\ \text{Btu}\,\text{h}^{-1}\;(74.8\ \text{kW})\;}$$
Checking sensibly, $1.10\times 7000\times(101.0-67.8) = 255\,600$ Btu/hr, agreeing to 0.2%.
Part (f) — humidification water. The water evaporated is the humidity-ratio
rise across the saturator carried on the dry-air flow:
$$\dot m_w=\dot m_{da}(W_3-W_O)=31\,500\,(0.00924-0.002144)=223.5\ \text{lb}\,\text{h}^{-1}$$
Converting with the density of water at $60\,{}^{\circ}\text{F}$, 8.337 lb per US gallon,
$$\boxed{\;\dot V_w = \frac{223.5}{8.337\times 60}=0.447\ \text{US gpm}\;(27\ \text{US gal per hour})\;}$$
Close the plant on an energy balance. Everything entering the air between O and S
must come from the two coils plus the enthalpy of the make-up water:
$$\dot m_{da}(h_S-h_O)-\dot m_{da}(W_3-W_O)h_f = 31\,500(34.46-7.09)-223.5(28)=855\,700\ \text{Btu}\,\text{h}^{-1}$$
and $Q_{pre}+Q_{re} = 600\,600+255\,100 = 855\,700$ Btu/hr. The two agree exactly, which confirms both
coil duties and the water rate together.
Result
Value
Dry-air mass flow
31 500 lb$_{da}$ h$^{-1}$
(b) Air temperature entering the space
$101.0\,{}^{\circ}\text{F}$ db ($t_{wb}=70.8\,{}^{\circ}\text{F}$)
(c) Preheat exit, state 2
$99.1\,{}^{\circ}\text{F}$ db / $60.0\,{}^{\circ}\text{F}$ wb
(c) Saturator exit, state 3
$67.8\,{}^{\circ}\text{F}$ db / $60.0\,{}^{\circ}\text{F}$ wb (63.7% RH)
Saturator saturating efficiency
79.7%
(d) Preheat coil duty
600 600 Btu h$^{-1}$
(e) Reheat coil duty
255 100 Btu h$^{-1}$
(f) Humidification water
0.447 US gpm (223.5 lb h$^{-1}$)
Total plant heat input
855 700 Btu h$^{-1}$ (4.3× the room load)
Check: what "the temperature of the adiabatic saturator" means. It is read here as
the saturator's adiabatic-saturation temperature — equal to the thermodynamic wet-bulb
temperature of the air everywhere inside the device, and to the sump-water temperature — so
states 2 and 3 both lie on the $60\,{}^{\circ}\text{F}$ wet-bulb line. That is the reading which makes
the device adiabatic, and it is the only one under which the phrase describes the saturator rather than
one of its air streams. The alternative reading, that the air leaves at
$60\,{}^{\circ}\text{F}$ dry bulb, is rejected because at the required humidity ratio that state is
only 84% saturated while sitting on a $57.0\,{}^{\circ}\text{F}$ wet-bulb line, so the cabinet would
not be an adiabatic saturator at $60\,{}^{\circ}\text{F}$ at all. Stated as an assumption under
cover-page instruction 1.