22-Mec-B2 Environmental Control in Buildings · December 2018
Question 4 of 8: R-134a refrigeration plant — COP, mass flow and compressor size
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2018 —
16-Mec-B2 Environmental Control in Buildings. Three hours, open book
(an environmental-control text and steam tables are expected; any non-communicating calculator is
permitted). Eight problems are printed and candidates solve five: Problem 1 carries
30 points, Problem 2 carries 10 points and Problems 3–8 carry 20 points each, so the printed
paper totals 160 points and a graded script totals 100. Psychrometric charts (SI and IP) and an
R-134a pressure–enthalpy diagram are attached to the paper. All eight problems are worked
below.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — the CLTD/SCL/CLF cooling-load method, duct design and the
degree-day/bin energy methods.
Jones, Air Conditioning Engineering, 5th ed. — plant psychrometry, percentage
saturation, apparatus dew point and coil by-pass factor.
Incropera & DeWitt, Fundamentals of Heat and Mass Transfer, 8th ed., Ch. 3 —
one-dimensional composite-wall conduction; Table A.3 for building-material conductivities.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour
compression cycles, compressor displacement and volumetric efficiency.
ASHRAE Refrigerant Tables for R-134a (datum hf = sf
= 0 at −40 °F, the datum of the attached chart).
Canadian context: National Energy Code of Canada for Buildings (NECB 2020), Canada Green
Building Council (CAGBC) LEED v4 and Zero Carbon Building Standard, and Environment and Climate
Change Canada Canadian Climate Normals for degree-day data.
Question 4: R-134a refrigeration plant — COP, mass flow and compressor size (20 marks)
$9\,{}^{\circ}\text{F}$ (so state 1 at $29\,{}^{\circ}\text{F}$)
Subcooling before the valve
$9\,{}^{\circ}\text{F}$ (so state 3 at $81\,{}^{\circ}\text{F}$)
Compression
isentropic
Volumetric efficiency
$\eta_v = 70\%$
Compressor
2 cylinders, vertical, $L = 1.5D$, 900 rpm
Find. The system diagram and the cycle on the attached p–h chart, the
coefficient of performance, the refrigerant mass flow, and the bore and stroke.
Figure 4.1 — The four-component vapour-compression plant with the state
points numbered as used below.
Approach. Read the four state points off the attached R-134a chart, then form the
refrigerating effect and compressor work per pound to get the COP; divide the capacity by the
refrigerating effect for the mass flow; convert that to a suction volume with the specific volume at
state 1, inflate it by the volumetric efficiency to a swept volume, and solve the cylinder geometry.
Fix the two pressures. Saturation pressures for R-134a are 33.1 psia at
$20\,{}^{\circ}\text{F}$ and 119.0 psia at $90\,{}^{\circ}\text{F}$, a pressure ratio of 3.60. These
locate the two horizontal lines of the cycle on the chart.
State 1 — compressor suction. Superheated $9\,{}^{\circ}\text{F}$ at the
evaporating pressure, so $29\,{}^{\circ}\text{F}$ and 33.1 psia:
$h_1 = 107.85$ Btu/lb, $s_1 = 0.2273$ Btu/lb °R, and the specific volume that will size the
compressor, $v_1 = 1.445$ ft$^3$/lb.
State 2 — compressor discharge. Following the constant-entropy line from
state 1 up to 119.0 psia gives $h_2 = 119.57$ Btu/lb at a discharge temperature of
$107.7\,{}^{\circ}\text{F}$, comfortably below any R-134a discharge limit.
States 3 and 4 — condenser exit and valve exit. Subcooling
$9\,{}^{\circ}\text{F}$ below $90\,{}^{\circ}\text{F}$ puts state 3 at $81\,{}^{\circ}\text{F}$ in the
liquid region, where $h_3 = 38.51$ Btu/lb. The expansion valve is a throttle, so it is isenthalpic and
$h_4 = h_3 = 38.51$ Btu/lb. At 33.1 psia the saturation enthalpies are
$h_f = 18.47$ and $h_g = 105.99$ Btu/lb, so the valve delivers a wet mixture of quality
$x_4 = (38.51-18.47)/(105.99-18.47) = 0.229$.
Part (a) — coefficient of performance. The refrigerating effect is the
enthalpy the refrigerant picks up in the evaporator and the work is the rise across the compressor:
$$q_{ref}=h_1-h_4=107.85-38.51=69.33\ \text{Btu/lb},\qquad w_c=h_2-h_1=119.57-107.85=11.72\ \text{Btu/lb}$$
$$\boxed{\;\text{COP}=\frac{q_{ref}}{w_c}=\frac{69.33}{11.72}=5.91\;}$$
The Carnot bound between the same two temperatures is
$T_e/(T_c-T_e) = 479.67/(549.67-479.67) = 6.85$, so this cycle achieves 86% of Carnot — high, as
it should be for a modest 3.6 pressure ratio with isentropic compression assumed.
Part (b) — refrigerant mass flow. Dividing the required capacity by the
refrigerating effect per pound,
$$\dot m=\frac{144\,000}{69.33}=\boxed{\;2077\ \text{lb}\,\text{h}^{-1}=34.6\ \text{lb}\,\text{min}^{-1}\;}$$
The compressor power follows as $\dot m w_c = 2077\times 11.72 = 24\,340$ Btu/hr, that is 9.57 hp, and
the condenser must reject $\dot m (h_2-h_3) = 2077\times 81.06 = 168\,400$ Btu/hr — which is the
capacity plus the work, as it must be.
Convert mass flow to a swept volume. The compressor ingests actual vapour at state
1, so the volume it must handle at suction is
$$\dot V_{suc}=\dot m v_1 = 34.6\times 1.445 = 50.0\ \text{ft}^3\text{min}^{-1}$$
and the volumetric efficiency relates that to the geometric displacement:
$$\dot V_{disp}=\frac{\dot V_{suc}}{\eta_v}=\frac{50.0}{0.70}=71.44\ \text{ft}^3\text{min}^{-1}$$
Part (c) — bore and stroke. Two cylinders, each of bore $D$ and stroke
$L = 1.5D$, turning at $N = 900$ rev/min sweep
$$\dot V_{disp}=n\,\frac{\pi D^2}{4}\,L\,N = 2\cdot\frac{\pi D^2}{4}\cdot 1.5D\cdot 900 = 2120.6\,D^3$$
with $D$ in feet. Solving for $D$,
$$D^3=\frac{71.44}{2120.6}=0.033674\ \text{ft}^3 \quad\Rightarrow\quad D = 0.3232\ \text{ft}$$
$$\boxed{\;\text{bore }D = 3.88\ \text{in},\qquad \text{stroke }L = 1.5D = 5.81\ \text{in}\;}$$
Substituting back, $2(\pi/4)(0.3232)^2(0.4848)(900) = 71.44$ ft$^3$/min, so the geometry reproduces the
required displacement exactly. A piston speed of $2LN/60 = 14.5$ ft/s is normal for a machine of this
size and rating.
Figure 4.2 — The cycle on the attached pressure–enthalpy diagram.
1→2 isentropic compression; 2→3 desuperheating, condensation and $9\,{}^{\circ}\text{F}$ of
subcooling at 119 psia; 3→4 the isenthalpic throttle (vertical); 4→1 evaporation followed by
$9\,{}^{\circ}\text{F}$ of superheat at 33.1 psia.
Result
Value
Evaporating / condensing pressure
33.1 / 119.0 psia (ratio 3.60)
$h_1$, $h_2$, $h_3 = h_4$
107.85, 119.57, 38.51 Btu/lb
Discharge temperature
$107.7\,{}^{\circ}\text{F}$
Refrigerating effect / compressor work
69.33 / 11.72 Btu/lb
(a) Coefficient of performance
5.91 (86% of the Carnot value 6.85)
(b) Refrigerant mass flow
2077 lb h$^{-1}$ (34.6 lb min$^{-1}$)
Suction / swept volume
50.0 / 71.44 ft$^3$ min$^{-1}$
(c) Bore
3.88 in
(c) Stroke
5.81 in
Compressor power / condenser duty
9.57 hp / 168 400 Btu h$^{-1}$
Check: property values are chart or table reads. The four enthalpies and $v_1$ are
quoted from the ASHRAE R-134a tables on the same datum as the attached diagram
($h_f = s_f = 0$ at $-40\,{}^{\circ}\text{F}$). Reading them by hand off the printed chart is good to
roughly $\pm 0.5$ Btu/lb, which propagates to about $\pm 0.1$ on the COP, $\pm 15$ lb/hr on the mass
flow and $\pm 0.02$ in on the bore — so a script whose numbers sit within those bands is
correct. One ton of refrigeration is taken as 200 Btu/min.