NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2018

Question 5 of 8: Cooling load of an east-facing office at 15:00 in July

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, December 2018 — 16-Mec-B2 Environmental Control in Buildings. Three hours, open book (an environmental-control text and steam tables are expected; any non-communicating calculator is permitted). Eight problems are printed and candidates solve five: Problem 1 carries 30 points, Problem 2 carries 10 points and Problems 3–8 carry 20 points each, so the printed paper totals 160 points and a graded script totals 100. Psychrometric charts (SI and IP) and an R-134a pressure–enthalpy diagram are attached to the paper. All eight problems are worked below.

Reference texts for this subject.

Question 5: Cooling load of an east-facing office at 15:00 in July (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantityValue
Location / month / hourOttawa, Ontario ($45.3\,{}^{\circ}$N); July; 15:00
Room dry bulb, summer$75\,{}^{\circ}\text{F}$
East glass wall, no internal shading12 ft × 20 ft = 240 ft$^2$
Glazingdouble pane, 1/2 in air space, heat-absorbing outer + clear inner
Other five surfacesinterior, adiabatic (no gain or loss)
Occupants6 office workers, light physical work, 08:00–18:00
Lighting5 fixtures × 2 × 40 W = 400 W, 08:00–18:00

Find. The room cooling load at 15:00 in July from the glass wall, the lights and the occupants, with the assumptions stated.

Approach. Use the ASHRAE CLTD/SCL/CLF method. The glass contributes two separate terms — transmitted solar radiation as $A\cdot SC\cdot SCL$ and conduction as $A\cdot U\cdot CLTD_{\text{corr}}$ — while the lights and the sensible part of the occupant gain are multiplied by cooling load factors that account for the room's thermal storage. Latent gain becomes load immediately and takes no factor.

  1. Establish the design conditions and check the sun. Ottawa's 2.5% summer design condition is $86\,{}^{\circ}\text{F}$ dry bulb with a mean daily range of $20\,{}^{\circ}\text{F}$. At 15:00 solar time in July ($\delta = 20.6\,{}^{\circ}$, hour angle $45\,{}^{\circ}$) the solar altitude is $\beta = 45.7\,{}^{\circ}$ and the azimuth is $71.4\,{}^{\circ}$ west of south. For a wall facing east the wall-solar azimuth is therefore $161\,{}^{\circ}$: greater than $90\,{}^{\circ}$, so the glass receives no direct beam at 15:00. Its instantaneous solar gain is diffuse and ground-reflected only, $E_t = 39.7$ Btu h$^{-1}$ft$^{-2}$, which would transmit just $240\times 0.55\times 0.87\times 39.7 = 4560$ Btu/hr. The load at 15:00 will be larger than that, because the mass of the room is still re-releasing energy stored during the intense morning sun — and capturing exactly that lag is what the SCL table is for.
  2. Glass solar cooling load. For east glass at $40\,{}^{\circ}$N in July, hour 15, in a medium-weight (zone type B) space with no interior shade, the solar cooling load factor is $SCL = 56$ Btu h$^{-1}$ft$^{-2}$, and heat-absorbing outer pane with clear inner pane in a double unit gives a shading coefficient $SC = 0.55$: $$q_{\text{solar}}=A\cdot SC\cdot SCL = 240\times 0.55\times 56 = \boxed{\;7392\ \text{Btu}\,\text{h}^{-1}\;}$$ As anticipated in step 1 this exceeds the instantaneous transmitted gain by 62%, the difference being stored morning energy re-emerging — the dominant term in this room by a wide margin.
  3. Glass conduction load. A double-glazed unit with a 1/2 in air space has $U = 0.55$ Btu h$^{-1}$ft$^{-2}$°F$^{-1}$ in summer conditions, and the tabulated glass cooling load temperature difference at hour 15 is $CLTD = 13\,{}^{\circ}\text{F}$. The table is published for a $78\,{}^{\circ}\text{F}$ room and an $85\,{}^{\circ}\text{F}$ mean outdoor temperature, so it must be corrected: $$CLTD_{\text{corr}} = CLTD + (78-t_{\text{in}}) + (t_{o,\text{mean}}-85)$$ with $t_{o,\text{mean}} = 86-20/2 = 76\,{}^{\circ}\text{F}$, giving $CLTD_{\text{corr}} = 13+3-9 = 7\,{}^{\circ}\text{F}$. Hence $$q_{\text{cond}}=A\,U\,CLTD_{\text{corr}} = 240\times 0.55\times 7 = 924\ \text{Btu}\,\text{h}^{-1}$$ a small term: at 15:00 the outdoor air is barely warmer than the room, so conduction through the glass is almost irrelevant compared with the radiation passing through it.
  4. Lighting load. Fluorescent tubes need a ballast allowance, conventionally 1.20 for a two-lamp magnetic ballast, and the lights have been on for 7 of their 10 hours, giving a cooling load factor $CLF = 0.90$ for a zone-B room: $$q_{\text{lights}}=W\times 3.412\times F_{\text{ballast}}\times CLF = 400\times 3.412\times 1.20\times 0.90$$ $$q_{\text{lights}}=1474\ \text{Btu}\,\text{h}^{-1}$$
  5. Occupant load. "Light physical work" in an office corresponds to the ASHRAE moderately-active office entry, 250 Btu/hr sensible and 200 Btu/hr latent per person. The sensible part is partly radiant and so is delayed; 7 hours into a 10-hour occupancy the factor is $CLF = 0.92$. The latent part becomes load at once and takes no factor: $$q_{\text{people,s}}=6\times 250\times 0.92 = 1380\ \text{Btu}\,\text{h}^{-1},\qquad q_{\text{people,l}}=6\times 200 = 1200\ \text{Btu}\,\text{h}^{-1}$$
  6. Sum the components. The five terms add to $$q_{\text{sens}}=7392+924+1474+1380 = 11\,170\ \text{Btu}\,\text{h}^{-1}$$ $$\boxed{\;q_{\text{total}}=11\,170+1200 = 12\,370\ \text{Btu}\,\text{h}^{-1}= 1.03\ \text{tons}\;}$$ with a room sensible heat factor of $11\,170/12\,370 = 0.903$. Per unit of glass that is 51.5 Btu h$^{-1}$ft$^{-2}$ of facade — a high but entirely typical figure for unshaded all-glass curtain wall, and the reason such rooms are normally given internal blinds or a lower shading coefficient at the design stage.
Problem 5: room cooling load at 15:00 in July, by componentGlass solar gain (SC × SCL)7,392 Btu/hGlass conduction (U × CLTD)924 Btu/hFluorescent lighting1,474 Btu/hOccupants — sensible1,380 Btu/hOccupants — latent1,200 Btu/hRoom cooling load12,370 Btu/h = 1.03 tons
Figure 5.1 — The room cooling load at 15:00 in July by component. The transmitted solar gain through the unshaded east glass is 60% of the total even though the glass is in shade at that hour, because the room is still releasing energy stored during the morning.
ComponentBasisCooling load (Btu h$^{-1}$)
Glass, transmitted solar$240\times 0.55\times 56$7392
Glass, conduction$240\times 0.55\times 7$924
Fluorescent lighting$400\times 3.412\times 1.20\times 0.90$1474
Occupants, sensible$6\times 250\times 0.92$1380
Occupants, latent$6\times 200$1200
Room sensible11 170
Room totalRSHF = 0.90312 370 (1.03 tons)

Check: the assumptions the question asks to be stated. (1) Method: ASHRAE CLTD/SCL/CLF, tables for $40\,{}^{\circ}$N in July, which is the nearest published latitude to Ottawa's $45.3\,{}^{\circ}$N and slightly conservative for an east wall. (2) Room mass: zone type B (medium-weight construction, carpeted slab, suspended ceiling), which sets $SCL = 56$ and the two cooling load factors; a light zone A would raise the solar term and a heavy zone C lower it, by roughly $\pm 15\%$. (3) Glazing: $SC = 0.55$ and $U = 0.55$ Btu h$^{-1}$ft$^{-2}$°F$^{-1}$ for a double unit with heat-absorbing outer and clear inner pane, no internal shading as stated. (4) Outdoor design: Ottawa 2.5% value $86\,{}^{\circ}\text{F}$ db with a $20\,{}^{\circ}\text{F}$ daily range, so the mean is $76\,{}^{\circ}\text{F}$. (5) Wind: the standard 7.5 mph summer exterior film is already embedded in the tabulated $U$; no separate wind term. (6) Partitions, floor and ceiling: adiabatic as the question states, so no gain from adjacent conditioned space. (7) Infiltration: taken as zero — the building is pressurised by its air system and the room is on a middle floor with no operable glazing. (8) Not included, because the question limits the scope to people, lights and glass: equipment and plug loads, ventilation air, fan and duct gains. (9) 15:00 is taken as solar time. (10) Occupants at 250/200 Btu/hr sensible/latent for light office work.