22-Mec-B2 Environmental Control in Buildings · December 2018
Question 5 of 8: Cooling load of an east-facing office at 15:00 in July
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2018 —
16-Mec-B2 Environmental Control in Buildings. Three hours, open book
(an environmental-control text and steam tables are expected; any non-communicating calculator is
permitted). Eight problems are printed and candidates solve five: Problem 1 carries
30 points, Problem 2 carries 10 points and Problems 3–8 carry 20 points each, so the printed
paper totals 160 points and a graded script totals 100. Psychrometric charts (SI and IP) and an
R-134a pressure–enthalpy diagram are attached to the paper. All eight problems are worked
below.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — the CLTD/SCL/CLF cooling-load method, duct design and the
degree-day/bin energy methods.
Jones, Air Conditioning Engineering, 5th ed. — plant psychrometry, percentage
saturation, apparatus dew point and coil by-pass factor.
Incropera & DeWitt, Fundamentals of Heat and Mass Transfer, 8th ed., Ch. 3 —
one-dimensional composite-wall conduction; Table A.3 for building-material conductivities.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour
compression cycles, compressor displacement and volumetric efficiency.
ASHRAE Refrigerant Tables for R-134a (datum hf = sf
= 0 at −40 °F, the datum of the attached chart).
Canadian context: National Energy Code of Canada for Buildings (NECB 2020), Canada Green
Building Council (CAGBC) LEED v4 and Zero Carbon Building Standard, and Environment and Climate
Change Canada Canadian Climate Normals for degree-day data.
Question 5: Cooling load of an east-facing office at 15:00 in July (20 marks)
Find. The room cooling load at 15:00 in July from the glass wall, the lights and
the occupants, with the assumptions stated.
Approach. Use the ASHRAE CLTD/SCL/CLF method. The glass contributes two separate
terms — transmitted solar radiation as $A\cdot SC\cdot SCL$ and conduction as
$A\cdot U\cdot CLTD_{\text{corr}}$ — while the lights and the sensible part of the occupant gain
are multiplied by cooling load factors that account for the room's thermal storage. Latent gain
becomes load immediately and takes no factor.
Establish the design conditions and check the sun. Ottawa's 2.5% summer design
condition is $86\,{}^{\circ}\text{F}$ dry bulb with a mean daily range of $20\,{}^{\circ}\text{F}$. At
15:00 solar time in July ($\delta = 20.6\,{}^{\circ}$, hour angle $45\,{}^{\circ}$) the solar altitude
is $\beta = 45.7\,{}^{\circ}$ and the azimuth is $71.4\,{}^{\circ}$ west of south. For a wall facing
east the wall-solar azimuth is therefore $161\,{}^{\circ}$: greater than $90\,{}^{\circ}$, so
the glass receives no direct beam at 15:00. Its instantaneous solar gain is diffuse and
ground-reflected only, $E_t = 39.7$ Btu h$^{-1}$ft$^{-2}$, which would transmit just
$240\times 0.55\times 0.87\times 39.7 = 4560$ Btu/hr. The load at 15:00 will be larger than
that, because the mass of the room is still re-releasing energy stored during the intense morning
sun — and capturing exactly that lag is what the SCL table is for.
Glass solar cooling load. For east glass at $40\,{}^{\circ}$N in July, hour 15,
in a medium-weight (zone type B) space with no interior shade, the solar cooling load factor is
$SCL = 56$ Btu h$^{-1}$ft$^{-2}$, and heat-absorbing outer pane with clear inner pane in a
double unit gives a shading coefficient $SC = 0.55$:
$$q_{\text{solar}}=A\cdot SC\cdot SCL = 240\times 0.55\times 56 = \boxed{\;7392\ \text{Btu}\,\text{h}^{-1}\;}$$
As anticipated in step 1 this exceeds the instantaneous transmitted gain by 62%, the difference being
stored morning energy re-emerging — the dominant term in this room by a wide margin.
Glass conduction load. A double-glazed unit with a 1/2 in air space has
$U = 0.55$ Btu h$^{-1}$ft$^{-2}$°F$^{-1}$ in summer conditions, and the tabulated glass
cooling load temperature difference at hour 15 is $CLTD = 13\,{}^{\circ}\text{F}$. The table is
published for a $78\,{}^{\circ}\text{F}$ room and an $85\,{}^{\circ}\text{F}$ mean outdoor
temperature, so it must be corrected:
$$CLTD_{\text{corr}} = CLTD + (78-t_{\text{in}}) + (t_{o,\text{mean}}-85)$$
with $t_{o,\text{mean}} = 86-20/2 = 76\,{}^{\circ}\text{F}$, giving
$CLTD_{\text{corr}} = 13+3-9 = 7\,{}^{\circ}\text{F}$. Hence
$$q_{\text{cond}}=A\,U\,CLTD_{\text{corr}} = 240\times 0.55\times 7 = 924\ \text{Btu}\,\text{h}^{-1}$$
a small term: at 15:00 the outdoor air is barely warmer than the room, so conduction through the glass
is almost irrelevant compared with the radiation passing through it.
Lighting load. Fluorescent tubes need a ballast allowance, conventionally 1.20
for a two-lamp magnetic ballast, and the lights have been on for 7 of their 10 hours, giving a cooling
load factor $CLF = 0.90$ for a zone-B room:
$$q_{\text{lights}}=W\times 3.412\times F_{\text{ballast}}\times CLF = 400\times 3.412\times 1.20\times 0.90$$
$$q_{\text{lights}}=1474\ \text{Btu}\,\text{h}^{-1}$$
Occupant load. "Light physical work" in an office corresponds to the ASHRAE
moderately-active office entry, 250 Btu/hr sensible and 200 Btu/hr latent per person. The sensible
part is partly radiant and so is delayed; 7 hours into a 10-hour occupancy the factor is
$CLF = 0.92$. The latent part becomes load at once and takes no factor:
$$q_{\text{people,s}}=6\times 250\times 0.92 = 1380\ \text{Btu}\,\text{h}^{-1},\qquad q_{\text{people,l}}=6\times 200 = 1200\ \text{Btu}\,\text{h}^{-1}$$
Sum the components. The five terms add to
$$q_{\text{sens}}=7392+924+1474+1380 = 11\,170\ \text{Btu}\,\text{h}^{-1}$$
$$\boxed{\;q_{\text{total}}=11\,170+1200 = 12\,370\ \text{Btu}\,\text{h}^{-1}= 1.03\ \text{tons}\;}$$
with a room sensible heat factor of $11\,170/12\,370 = 0.903$. Per unit of glass that is 51.5
Btu h$^{-1}$ft$^{-2}$ of facade — a high but entirely typical figure for unshaded
all-glass curtain wall, and the reason such rooms are normally given internal blinds or a lower
shading coefficient at the design stage.
Figure 5.1 — The room cooling load at 15:00 in July by component. The
transmitted solar gain through the unshaded east glass is 60% of the total even though the glass is in
shade at that hour, because the room is still releasing energy stored during the morning.
Component
Basis
Cooling load (Btu h$^{-1}$)
Glass, transmitted solar
$240\times 0.55\times 56$
7392
Glass, conduction
$240\times 0.55\times 7$
924
Fluorescent lighting
$400\times 3.412\times 1.20\times 0.90$
1474
Occupants, sensible
$6\times 250\times 0.92$
1380
Occupants, latent
$6\times 200$
1200
Room sensible
11 170
Room total
RSHF = 0.903
12 370 (1.03 tons)
Check: the assumptions the question asks to be stated. (1) Method: ASHRAE
CLTD/SCL/CLF, tables for $40\,{}^{\circ}$N in July, which is the nearest published latitude to Ottawa's
$45.3\,{}^{\circ}$N and slightly conservative for an east wall. (2) Room mass: zone type B
(medium-weight construction, carpeted slab, suspended ceiling), which sets $SCL = 56$ and the two
cooling load factors; a light zone A would raise the solar term and a heavy zone C lower it, by
roughly $\pm 15\%$. (3) Glazing: $SC = 0.55$ and
$U = 0.55$ Btu h$^{-1}$ft$^{-2}$°F$^{-1}$ for a double unit with heat-absorbing outer and
clear inner pane, no internal shading as stated. (4) Outdoor design: Ottawa 2.5% value
$86\,{}^{\circ}\text{F}$ db with a $20\,{}^{\circ}\text{F}$ daily range, so the mean is
$76\,{}^{\circ}\text{F}$. (5) Wind: the standard 7.5 mph summer exterior film is already
embedded in the tabulated $U$; no separate wind term. (6) Partitions, floor and ceiling:
adiabatic as the question states, so no gain from adjacent conditioned space. (7) Infiltration:
taken as zero — the building is pressurised by its air system and the room is on a middle floor
with no operable glazing. (8) Not included, because the question limits the scope to people,
lights and glass: equipment and plug loads, ventilation air, fan and duct gains. (9) 15:00 is
taken as solar time. (10) Occupants at 250/200 Btu/hr sensible/latent for light office work.