NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2018

Question 3 of 8: Summer plant — mixing, chilled-water coil, reheat and plant energy

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, December 2018 — 16-Mec-B2 Environmental Control in Buildings. Three hours, open book (an environmental-control text and steam tables are expected; any non-communicating calculator is permitted). Eight problems are printed and candidates solve five: Problem 1 carries 30 points, Problem 2 carries 10 points and Problems 3–8 carry 20 points each, so the printed paper totals 160 points and a graded script totals 100. Psychrometric charts (SI and IP) and an R-134a pressure–enthalpy diagram are attached to the paper. All eight problems are worked below.

Reference texts for this subject.

Question 3: Summer plant — mixing, chilled-water coil, reheat and plant energy (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantityValue
Zone sensible / latent load22.5 kW / 9.8 kW
Zone condition (state R)$24\,{}^{\circ}\text{C}$, 50% RH
Supply air (state S)2.0 kg s$^{-1}$ at $13\,{}^{\circ}\text{C}$, 60% RH
Outdoor design (state O)$27\,{}^{\circ}\text{C}$, 70% RH
Mixing ratio, recirculated : fresh3 : 1 (so 25% outdoor air)
Cooling-coil apparatus dew point$5\,{}^{\circ}\text{C}$
Refrigeration plant overall COP2.0
Simplificationssea level (101.325 kPa); friction, fan and pump work neglected

Find. The plant diagram and cycle, every state point with dry- and wet-bulb temperature, the total room air-conditioning load, the total plant energy input, and the reduced input when the reheat is taken from condenser cooling water.

MIXINGBOXoutdoor air27 °C, 70% RHCOOLINGcoilHEATINGcoilFANCONDITIONED ZONEsensible + latent loadsupply airrecirculated air — 3 parts recirculated to 1 part freshexhaustOMCSR
Figure 3.1 (part a) — The plant. Return air from the zone splits, three parts by mass recirculating to the mixing box against one part fresh; the mixture is cooled and dehumidified to the coil condition C and then reheated to the supply state S.

Approach. Fix O, R and S from their dry-bulb and relative-humidity pairs; obtain the mixed state from exact moisture and enthalpy balances at 25% outdoor air; use the given apparatus dew point with the supply humidity ratio to find the coil by-pass factor and hence the off-coil state; then take the coil and reheat duties as enthalpy differences on the 2.0 kg/s supply flow, and divide the refrigeration duty by the COP.

  1. Fix the three stated air states. With $p = 101.325$ kPa, $W = 0.621945\,p_w/(p-p_w)$ and $h = 1.006t + W(2501+1.86t)$ kJ/kg$_{da}$:
    Point$t$ (°C)$\phi$$W$ (g/kg)$h$ (kJ/kg)$t_{wb}$ (°C)
    O outdoor27.0070%15.71567.2522.8
    R zone / return24.0050%9.29947.8117.1
    S supply13.0060%5.56627.139.1
  2. Mix the return and fresh streams. Adiabatic mixing conserves moisture and enthalpy exactly, so with an outdoor-air mass fraction $x = 0.25$ both are mass-weighted: $$W_M=xW_O+(1-x)W_R = 0.25(15.715)+0.75(9.299)=10.903\ \text{g/kg}$$ $$h_M=xh_O+(1-x)h_R = 0.25(67.25)+0.75(47.81)=52.68\ \text{kJ/kg}$$ The dry bulb is then derived from those two, not weighted: $$\boxed{\;t_M=\frac{h_M-2501\,W_M}{1.006+1.86\,W_M}=24.76\,{}^{\circ}\text{C},\quad t_{wb,M}=18.6\,{}^{\circ}\text{C}\;}$$ Weighting the dry bulb directly would give $24.75\,{}^{\circ}\text{C}$ — close, but it makes $h(t_M,W_M)$ disagree with the mass-weighted $h_M$, because of the $Wt$ cross-term in the enthalpy relation. Deriving $t_M$ instead makes $h(t_M,W_M) = h_M$ identically, which is a free check that the mixing arithmetic is right.
  3. Part (d) — total room air-conditioning load. The zone loads are stated directly, and the total load is their sum: $$\boxed{\;Q_{\text{room}} = q_s + q_l = 22.5+9.8 = 32.3\ \text{kW}\quad(\text{SHR}=0.697)\;}$$
  4. Find the coil by-pass factor and the off-coil state. The apparatus dew point is the saturated state the coil surface behaves as, here $5\,{}^{\circ}\text{C}$ with $W_{adp} = 5.402$ g/kg. The by-pass factor is the fraction of the air that leaves the coil untreated, so on humidity ratio $$\text{BF}=\frac{W_S-W_{adp}}{W_M-W_{adp}}=\frac{5.566-5.402}{10.903-5.402}=0.0298$$ and the same fraction applies to the temperature approach: $$t_C = t_{adp}+\text{BF}\,(t_M-t_{adp}) = 5+0.0298(24.76-5)=5.59\,{}^{\circ}\text{C}$$ giving $h_C = 19.60$ kJ/kg at 98.9% RH. A by-pass factor of only 3% means a deep, many-row coil that takes the air almost exactly to its apparatus dew point — which is what the given supply humidity ratio, barely above $W_{adp}$, demands.
  5. Part (c) — the state points. Adding the mixed and off-coil states to the table of step 1 completes the set plotted in Figure 3.2:
    PointWhereDry bulb (°C)Wet bulb (°C)$W$ (g/kg)$h$ (kJ/kg)
    Ooutdoor air27.0022.815.71567.25
    Rzone / return air24.0017.19.29947.81
    Mmixing-box exit / coil face24.7618.610.90352.68
    Coff cooling coil5.595.55.56619.60
    Ssupply to zone13.009.15.56627.13
    ADPapparatus dew point5.005.05.40218.59
05101520253035246810121416182020%40%60%80%saturation (100%)dry-bulb temperature (°C)humidity ratio W (g moisture per kg dry air)Problem 3 cycle on the ASHRAE chart (SI): mix, cool to the coil condition, reheat to supplymix 1:3cooling coilreheatroom loadORMCSADPthe coil line M → C produced to saturation gives the 5 °C apparatus dew point
Figure 3.2 (part b) — The cycle on the SI chart. R and O mix to M one quarter of the way along RO; M→C is the coil process, whose line produced to saturation gives the $5\,{}^{\circ}\text{C}$ apparatus dew point; C→S is the horizontal reheat; S→R is the room process.
  1. Cooling-coil duty. The coil treats the whole 2.0 kg/s from M to C: $$Q_{cool}=\dot m (h_M-h_C)=2.0\,(52.68-19.60)=\boxed{\;66.15\ \text{kW}\;}$$ of which the moisture removed is $\dot m\,\Delta W = 2.0(10.903-5.566)/1000 = 0.01067$ kg/s, or 38.4 kg per hour of condensate.
  2. Reheat-coil duty. From C to S at constant humidity ratio: $$Q_{heat}=\dot m (h_S-h_C)=2.0\,(27.13-19.60)=15.07\ \text{kW}$$ Because no moisture changes, this must also equal $\dot m c_p \Delta t = 2.0(1.0163)(13.00-5.59) = 15.07$ kW, which it does.
  3. Part (e) — total energy input. The refrigeration plant delivers 66.15 kW of cooling at a COP of 2, so it absorbs 33.08 kW; the heating coil, supplied conventionally, absorbs its full 15.07 kW: $$\boxed{\;E_{\text{total}}=\frac{Q_{cool}}{\text{COP}}+Q_{heat}=\frac{66.15}{2}+15.07=48.14\ \text{kW}\;}$$
  4. Part (f) — reheat from condenser cooling water. The condenser must reject everything the plant absorbs plus everything it removes from the air, $Q_{cond} = 66.15+33.08 = 99.23$ kW. That is 6.6 times the 15.07 kW the reheat coil needs, so the reheat is available as waste heat at no additional energy cost and the input collapses to the compressor alone: $$\boxed{\;E_{\text{recovered}}=\frac{Q_{cool}}{\text{COP}}=33.08\ \text{kW}\;}$$ a saving of 15.07 kW, or 31.3% of the total input. The caveat worth stating is one of temperature rather than quantity: condenser water leaving at around $35\,{}^{\circ}\text{C}$ is warm enough to raise air from $5.6$ to $13\,{}^{\circ}\text{C}$ with a comfortable approach, so the recovery is genuinely practical here.
ResultValue
Mixed-air state M$24.76\,{}^{\circ}\text{C}$ db / $18.6\,{}^{\circ}\text{C}$ wb, 10.903 g/kg
Coil by-pass factor0.0298
Off-coil state C$5.59\,{}^{\circ}\text{C}$ db / $5.5\,{}^{\circ}\text{C}$ wb, 98.9% RH
(d) Total room air-conditioning load32.3 kW (22.5 sensible + 9.8 latent, SHR 0.697)
Cooling-coil duty / condensate66.15 kW / 38.4 kg h$^{-1}$
Reheat-coil duty15.07 kW
(e) Total energy input48.14 kW
(f) Energy input with condenser-water reheat33.08 kW (31.3% saving)

Check: the question is over-specified and the two data sets do not close. The paper states the zone loads (22.5 kW sensible, 9.8 kW latent, SHR 0.697) and the supply state and flow (2.0 kg/s at $13\,{}^{\circ}\text{C}$, 60% RH). Taken literally, the supply-to-room process would offset $2.0(47.81-27.13) = 41.36$ kW at SHR 0.541 — 22.36 kW sensible, which matches the stated 22.5 kW to 0.6%, but 18.67 kW latent against the stated 9.8 kW. The sensible half agrees and the latent half does not. Nothing has to be reconciled, because no part of the question needs both sets: part (d) is answered from the stated loads, and parts (e) and (f) from the states plus the mixing ratio and apparatus dew point. Flagged here under cover-page instruction 1.