Question 2 of 7: Excitation state and the salient-pole generated voltage
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2015 — 07-Elec-B7 Power Systems
Engineering. Open-book, three hours, seven problems of equal value; any five constitute a
complete paper. Every problem is answered here, because the set is intended as a study
resource rather than an exam script.
Reference texts for this subject.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed.,
IEEE Press / Wiley — the syllabus text for 07-Elec-B7. Chapters 4 (transmission lines),
5 (synchronous machines), 3 (transformers), 6 (load flow), 7 (fault analysis) and
8 (system stability) map one-to-one onto the seven problems below.
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design,
6th ed., Cengage — parallel treatment of the ABCD long-line model, symmetrical
components and the equal-area criterion.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed., McGraw-Hill —
salient-pole two-reaction theory and transformer loss/frequency behaviour.
CSA C22.3 No. 1, Overhead Systems, and CAN/CSA C22.2 standards give the
Canadian equipment and clearance framework these calculations feed into.
Question 2: Excitation state and the salient-pole generated voltage
Excitation state is defined by comparing the internal generated voltage $E$ with the
terminal voltage $V_t$. A machine is over-excited when the field current is large
enough that $E\cos\delta$ exceeds $V_t$; it is under-excited when the field current is
reduced until $E\cos\delta$ falls below $V_t$. The dividing case, $E\cos\delta = V_t$, is unity
power factor, where the machine exchanges only real power with the system.
The consequence for reactive power follows from the round-rotor relation
$$Q=\frac{E V_t \cos\delta - V_t^{2}}{X_d}$$
which is positive when $E\cos\delta > V_t$ and negative when it is less. An over-excited
generator therefore delivers reactive power to the system and operates at a lagging power
factor; an under-excited generator absorbs reactive power and operates at a leading power
factor. The same machine is thus a continuously adjustable source or sink of vars, controlled
entirely by the field rheostat or the automatic voltage regulator, with no switching and no
discrete steps.
To make a synchronous machine appear as a pure source of reactive power, it is run at or
near zero real load and heavily over-excited — the classical synchronous condenser.
Uncoupled from any prime mover, the machine draws only enough real power to cover its own
losses, so $\delta \approx 0$, $P\approx 0$ and $Q \approx (E-V_t)V_t/X_d$, which is large and
positive when $E$ is pushed well above $V_t$. Reversing the argument, reducing the field until
$E$ falls below $V_t$ makes the same machine absorb vars, which is how synchronous condensers
and under-excited generators hold down voltage on lightly loaded transmission at night.
Because the response is continuous and inherently fast, and because a rotating machine also
contributes short-circuit current and inertia, synchronous condensers remain in service at
converter terminals and at the ends of long lines even where static compensators are
cheaper.
Two limits bound this freedom, and both appear on the machine's capability curve: the field
winding's thermal rating caps over-excitation, and under-excitation is limited by armature-end
heating and, ultimately, by the steady-state stability limit as $E$ becomes too small to hold
synchronism.
Parts (b) and (c) — generated voltage by two-reaction theory
Given. A salient-pole synchronous generator operating at rated terminal
voltage and rated apparent power, with the two axis reactances listed below.
Machine data (per unit on the machine rating)
Quantity
Symbol
Value
Direct-axis synchronous reactance
Xd
1.0 pu
Quadrature-axis synchronous reactance
Xq
0.6 pu
Armature resistance
Ra
neglected
Terminal voltage
Vt
1.0 pu ∡0°
Armature current (rated kVA)
Ia
1.0 pu at 0.8 power factor
Find. The per-unit generated (excitation) voltage E and the power angle
δ for 0.8 lagging power factor, and again for 0.8 leading power factor.
Figure 2 — Two-reaction construction for the
lagging case. The auxiliary phasor Vt + jXqIa establishes the
q-axis; E is then found by extending along that axis by
(Xd − Xq)Id.
Approach. A salient-pole machine has no single synchronous reactance, so
$E \ne V_t + jX_sI_a$. Instead, construct the auxiliary phasor $E_q = V_t + jX_qI_a$, which
lies exactly along the q-axis and therefore fixes $\delta$; resolve $I_a$ into its d- and
q-axis components using $\psi = \delta + \varphi$; then add the extra direct-axis drop
$(X_d - X_q)I_d$ to reach $E$.
Part (b), fix the terminal phasors for 0.8 lagging. Rated kVA at rated
voltage means $|I_a| = 1.0$ pu, and $\varphi = \cos^{-1}0.8 = 36.87^\circ$ lagging, so
$V_t = 1.0\angle 0^\circ$ and $I_a = 1.0\angle-36.87^\circ$ pu.
Locate the quadrature axis. The whole method rests on the fact that
$V_t + jX_qI_a$ is collinear with $E$, because the q-axis component of the armature reaction
is already fully accounted for by $X_q$:
$$E_q=V_t+jX_qI_a = 1.0 + j(0.6)(1.0\angle-36.87^\circ) = 1.0+(0.36+j0.48)=1.36+j0.48$$
$$\begin{aligned} |E_q| &= 1.44222\ \text{pu} \\ \delta &= \tan^{-1}\!\frac{0.48}{1.36}=19.440^\circ \end{aligned}$$
so $\boxed{\delta = 19.44^\circ}$ for the lagging case.
Resolve the armature current onto the axes. The angle between $I_a$ and
the q-axis is $\psi = \delta + \varphi = 19.440^\circ + 36.870^\circ = 56.310^\circ$, hence
$$\begin{aligned} I_d &= |I_a|\sin\psi = 0.83205\ \text{pu} \\ I_q &= |I_a|\cos\psi = 0.55470\ \text{pu} \end{aligned}$$
Add the saliency term. Along the q-axis the remaining drop is
$(X_d - X_q)I_d$, so
$$E = |E_q| + (X_d-X_q)I_d = 1.44222 + (1.0-0.6)(0.83205) = 1.44222+0.33282$$
$$\boxed{E = 1.775\ \text{pu at }\delta = 19.44^\circ}$$
An independent check is available directly from the axis components:
$E = V_t\cos\delta + X_dI_d = 0.94296 + (1.0)(0.83205) = 1.77504$ pu, and the orthogonality
condition $V_t\sin\delta = X_qI_q$ gives $0.33282 = (0.6)(0.55470)$, which closes exactly.
Part (c), repeat for 0.8 leading. Only the sign of the phase angle
changes: $I_a = 1.0\angle+36.87^\circ$ pu. Rebuilding the auxiliary phasor,
$$E_q = 1.0 + j(0.6)(1.0\angle 36.87^\circ) = 1.0 + (-0.36+j0.48) = 0.64+j0.48$$
$$\begin{aligned} |E_q| &= 0.800\ \text{pu} \\ \delta &= \tan^{-1}\!\frac{0.48}{0.64} = 36.870^\circ \end{aligned}$$
Evaluate the saliency term for the leading case. Now
$\psi = \delta + \varphi = 36.870^\circ - 36.870^\circ = 0^\circ$, so $I_d = \sin 0^\circ = 0$
and the entire armature current lies on the quadrature axis. The saliency correction vanishes
and
$$\boxed{E = 0.800\ \text{pu at }\delta = 36.87^\circ}$$
This clean result is a genuine coincidence of the chosen numbers, not a general rule: with
$\varphi = -\delta$ the current sits exactly on the q-axis, the machine produces no
direct-axis armature reaction at all, and $E$ collapses to $|E_q|$.
Interpret the two operating points. At 0.8 lagging the machine needs
$E = 1.775$ pu, well above terminal voltage, so it is strongly over-excited and exporting vars.
At 0.8 leading it needs only $E = 0.800$ pu, below terminal voltage, so it is under-excited
and absorbing them — the same conclusion Part (a) reaches from the sign of
$E\cos\delta - V_t$, which is $+0.673$ pu in the first case and $-0.360$ pu in the second.
The field current must therefore be cut to roughly 45 per cent of its lagging value to move
between the two points at constant real load.