Question 4 of 7: Shunt capacitor switching on a two-bus system
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2015 — 07-Elec-B7 Power Systems
Engineering. Open-book, three hours, seven problems of equal value; any five constitute a
complete paper. Every problem is answered here, because the set is intended as a study
resource rather than an exam script.
Reference texts for this subject.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed.,
IEEE Press / Wiley — the syllabus text for 07-Elec-B7. Chapters 4 (transmission lines),
5 (synchronous machines), 3 (transformers), 6 (load flow), 7 (fault analysis) and
8 (system stability) map one-to-one onto the seven problems below.
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design,
6th ed., Cengage — parallel treatment of the ABCD long-line model, symmetrical
components and the equal-area criterion.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed., McGraw-Hill —
salient-pole two-reaction theory and transformer loss/frequency behaviour.
CSA C22.3 No. 1, Overhead Systems, and CAN/CSA C22.2 standards give the
Canadian equipment and clearance framework these calculations feed into.
Question 4: Shunt capacitor switching on a two-bus system
Shunt capacitors are the cheapest source of reactive power on a network, and their
advantages follow from that. They raise voltage at the point of connection by injecting vars
locally instead of importing them over the line, which in turn unloads the line of reactive
current, reduces the $I^{2}R$ loss and releases thermal capacity for real power. They correct
the power factor seen by the upstream network, which defers reinforcement and, on a
distribution utility's tariff, reduces demand charges. They are modular, so banks can be added
in steps as load grows, and they can be switched — automatically on voltage, time or var
flow — to follow the daily load cycle. Losses are low, roughly 0.1 to 0.5 W per kvar,
there are no rotating parts, maintenance is minimal, and installation on an existing
substation is straightforward.
The disadvantages are equally characteristic. Capacitor output falls with the square of
voltage, $Q_C = BV^{2}$, so the support weakens exactly when a voltage collapse makes it most
needed — the opposite of the behaviour wanted from a voltage-control device, and a
recognised contributor to voltage instability. The compensation is fixed in steps rather than
continuous, so voltage is regulated coarsely unless many small banks are used. Capacitors form
a resonant circuit with the system inductance and can amplify harmonics; a bank tuned near a
characteristic harmonic of nearby converters will overheat and fail, so detuning reactors and
a harmonic study are usually needed. Switching a bank produces a large inrush current and a
voltage transient that can trip sensitive loads or reignite in the breaker, and back-to-back
switching between adjacent banks is particularly severe. Over-compensation at light load
raises voltage too far, adding to the Ferranti rise of Question 1. Finally, capacitors can
interact with induction motors on load rejection to give self-excitation, and with series
inductance to give ferroresonance.
In practice, then, shunt capacitors are the workhorse of steady-state var supply while
dynamic support — static var compensators, STATCOMs, or the synchronous condensers of
Question 2 — is reserved for the fast and voltage-independent duty.
Parts (b) to (e) — the two-bus load-flow calculation
Given. The two-bus system of Figure (1), with bus 1 as the slack bus and a
switchable capacitor at bus 2.
System data (per unit)
Quantity
Symbol
Value
Slack-bus voltage
V1
1.00 ∡0° pu
Line admittance
y12
1 − j10 pu
Active load at bus 2
PD
4.3 pu
Reactive load at bus 2
QD
−0.6336 pu
Capacitor susceptance
Bc
0.83 pu
Permitted voltage band at bus 2
|V2|
0.95 to 1.05 pu
Find. Whether the capacitor bank must be in service; the resulting bus-2
voltage magnitude and angle; and the real power, reactive power and power factor supplied by
the slack bus.
Figure 4 — Two-bus system of Figure (1) with
the switchable shunt capacitor at bus 2.
Approach. Write the injected complex power at bus 2 in terms of the two
unknowns $x = |V_2|\cos\delta_2$ and $w = |V_2|\sin\delta_2$. Those two equations are linear in
$x$ and $w$ once $|V_2|^{2}$ is treated as a third variable, and eliminating $x$ and $w$ leaves
one quadratic in $|V_2|^{2}$ — so the flow is solved in closed form, with no iteration,
for both the capacitor-out and capacitor-in cases.
Build the bus admittance matrix. With a single line and a shunt at bus 2,
$$Y_{11}=y_{12}=1-j10,\quad Y_{12}=Y_{21}=-y_{12}=-1+j10,\quad Y_{22}=y_{12}+jB_c$$
The load is a demand, so the injection at bus 2 is $S_2 = -P_D - jQ_D = -4.3 + j0.6336$ pu.
Write the injected power in Cartesian form. Putting
$V_2 = x + jw$ and $V_1 = 1$ into $S_2 = V_2\!\left(Y_{21}V_1+Y_{22}V_2\right)^{*}$ and
separating real and imaginary parts gives the pair
$$\begin{aligned} -x+10w+u &= -4.3 \\ -10x-w+(10-B_c)u &= 0.6336 \end{aligned}$$
where $u = |V_2|^{2} = x^{2}+w^{2}$. These are the standard polar power-flow equations
rewritten in rectangular coordinates.
Eliminate to a single quadratic. The first equation gives
$x = 10w+u+4.3$. Substituting into the second removes $x$ and, remarkably, also removes the
$10u$ terms, leaving a linear relation between $w$ and $u$:
$$-101w - B_cu - 43 = 0.6336\quad\Longrightarrow\quad w = \frac{-B_cu-43.6336}{101}$$
Back-substituting both into $u = x^{2}+w^{2}$ produces one quadratic in $u$, which is solved
exactly.
Part (b), test the system with the capacitor out. Setting $B_c = 0$ gives
$w = -0.432016$ and $x = u - 0.020158$, and the quadratic
$u^{2}-1.040316u+0.187044 = 0$ has roots $u = 0.809158$ and $u = 0.231159$. The lower root is
the unstable low-voltage solution and is discarded, so
$$|V_2| = \sqrt{0.809158} = 0.8995\ \text{pu}$$
This is below the 0.95 pu floor, so
$\boxed{\text{the capacitor bank must be switched ON}}$. The margin is not marginal —
the bus is 5.3 per cent below the permitted minimum, and heavy: the 4.3 pu load is being drawn
through a line of only $z = 1/(1-j10) = 0.00990+j0.09901$ pu.
Part (c), solve again with the capacitor in service. With
$B_c = 0.83$ the linear relation becomes $w = -0.0082178u-0.4320158$ and
$x = 0.9178218u-0.0201584$, and the quadratic
$$0.8424644u^{2}-1.0299073u+0.1870440=0$$
has roots $u = 1.000602$ and $u = 0.221887$. Taking the operable high-voltage root,
$$\boxed{|V_2| = 1.0003\ \text{pu}}$$
which sits comfortably inside the 0.95 to 1.05 band, so the single 0.83 pu bank is
sufficient and no second step is needed.
Part (d), recover the angle. From the converged root,
$w = -0.440239$ and $x = 0.898216$, so
$$\delta_2=\tan^{-1}\frac{w}{x}=\tan^{-1}\frac{-0.440239}{0.898216}$$
$$\boxed{\delta_2 = -26.11^\circ}$$
The negative sign is the expected direction: bus 2 lags the slack bus because real power
flows from bus 1 to bus 2. The magnitude is large for a single line, which again reflects how
heavily loaded it is.
Part (e), compute the slack-bus injection. The current leaving bus 1 is
$I_1 = Y_{11}V_1+Y_{12}V_2$, which evaluates to
$$I_1=(1-j10)(1)+(-1+j10)(0.898216-j0.440239)=4.50417-j0.57760\ \text{pu}$$
so, with $V_1 = 1\angle0^\circ$,
$$S_1=V_1I_1^{*}=\boxed{P_1 = 4.5042\ \text{pu},\; Q_1 = 0.5776\ \text{pu}}$$
and the slack-bus power factor is
$$\cos\varphi_1=\cos\left(\tan^{-1}\frac{0.5776}{4.5042}\right)=\boxed{0.9919\ \text{lagging}}$$
Close the balance as a check. The real power delivered exceeds the load
by $4.5042-4.3000 = 0.2042$ pu, and the line loss computed independently is
$|I|^{2}R = (20.621)(0.009901) = 0.20417$ pu, which agrees. On the reactive side the line
absorbs $|I|^{2}X = 2.0417$ pu, the capacitor supplies $B_c|V_2|^{2} = 0.8305$ pu and the load
returns 0.6336 pu, and $2.0417 - 0.8305 - 0.6336 = 0.5776$ pu is exactly the slack-bus
reactive output. Both balances closing is strong evidence the quadratic root was the right
one.
Check: the question text quotes the bus-2 reactive load as
−0.636 pu while Figure (1) prints −0.6336 pu. The figure value is used here as the
more precise statement. The difference is immaterial: with −0.636 pu the answers become
|V2| = 1.0006 pu and δ2 = −26.10°, and the
capacitor-out voltage becomes 0.8999 pu — still below the 0.95 pu limit, so Part (b) is
unaffected.