NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · May 2015

Question 7 of 7: Equal-area criterion and the critical clearing angle

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, May 2015 — 07-Elec-B7 Power Systems Engineering. Open-book, three hours, seven problems of equal value; any five constitute a complete paper. Every problem is answered here, because the set is intended as a study resource rather than an exam script.

Reference texts for this subject.

Question 7: Equal-area criterion and the critical clearing angle

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A machine of internal voltage E behind a transient reactance, feeding an infinite bus through line 1 and then two parallel lines, with a three-phase fault at F on line 3 immediately adjacent to the receiving busbar.

Circuit data (per unit)
ElementReactanceQuantityValue
Machine (transient)j0.20Internal voltage E1.2 pu
Line 1j0.05Infinite-bus voltage V1.00 ∡0° pu
Line 2j0.50Mechanical input Pm1.0 pu
Line 3 (faulted)j0.40Fault typebolted three-phase at F
Receiving transformerj0.05Clearing actionopen line 3

Find. The initial power angle at 1.0 pu load; the power-angle curve while the fault is on; the power-angle curve after line 3 is opened; and the critical clearing angle.

~E = 1.2 puj0.2j0.05line 1line 2 j0.5line 3 j0.4three-phase fault Fj0.05V = 1.0 ∡0°Machine feeding an infinite bus through two parallel lines
Figure 8 — Circuit of Figure (4). The fault at F sits at the receiving end of line 3, so it holds the parallel-line receiving busbar at zero voltage until line 3 is opened.

Approach. Each of the three network conditions — pre-fault, during-fault and post-fault — reduces to a single transfer reactance between E and V, and each therefore has its own sinusoidal power-angle curve $P = (EV/X)\sin\delta$. The initial angle comes from the pre-fault curve at $P = P_m$, and the critical clearing angle follows from equating the accelerating area under the during-fault curve to the maximum decelerating area available under the post-fault curve.

  1. Part (a), reduce the pre-fault network. With both parallel lines in service they combine in parallel and add to the two series reactances: $$X_{\text{pre}}=0.20+0.05+\frac{(0.50)(0.40)}{0.50+0.40}+0.05=0.20+0.05+0.22222+0.05=0.52222\ \text{pu}$$ $$P_{\max,1}=\frac{EV}{X_{\text{pre}}}=\frac{(1.2)(1.0)}{0.52222}=2.29787\ \text{pu}$$
  2. Solve for the initial angle. In the steady state the electrical output equals the mechanical input, $P_e = P_m = 1.0$ pu, so $$\sin\delta_0=\frac{P_m}{P_{\max,1}}=\frac{1.0}{2.29787}=0.43519$$ $$\boxed{\delta_0 = 25.80^\circ = 0.45025\ \text{rad}}$$
  3. Part (b), examine the network during the fault. The fault at F sits at the receiving end of line 3, that is at the busbar where lines 2 and 3 come together. A bolted three-phase fault there holds that busbar at zero voltage. Both parallel lines then terminate on a short circuit, and the infinite bus behind the receiving transformer is also connected to that same zero-voltage point, so there is no path from E to V that does not pass through the fault. The transfer reactance is infinite and

    $$\boxed{P_{e,\text{fault}} = 0\ \text{for all }\delta}$$ Physically the machine still delivers current, but into a purely reactive short circuit, so the real power it exports is zero. This is the worst case for stability: the full 1.0 pu of mechanical input goes into accelerating the rotor from the instant the fault appears.
  4. Part (c), reduce the post-fault network. Clearing opens line 3 at both ends, removing both the fault and that line. Only line 2 remains in the parallel section: $$X_{\text{post}}=0.20+0.05+0.50+0.05=0.80\ \text{pu}$$ $$P_{\max,3}=\frac{EV}{X_{\text{post}}}=\frac{1.2}{0.80}=1.500\ \text{pu}$$ so the post-fault characteristic is $$\boxed{P_{e,\text{post}}=1.500\sin\delta\ \text{pu}}$$ It still peaks above the 1.0 pu mechanical input, so a stable post-fault equilibrium exists at $\delta = \sin^{-1}(1/1.5) = 41.81^\circ$; had $P_{\max,3}$ fallen below 1.0 pu the machine could not have been stabilised at any clearing time.
  5. Part (d), fix the limit of the decelerating swing. The largest angle from which the rotor can still be pulled back is the unstable equilibrium on the post-fault curve, $$\delta_{\max}=180^\circ-\sin^{-1}\frac{P_m}{P_{\max,3}}=180^\circ-41.81^\circ=138.19^\circ=2.41188\ \text{rad}$$ Beyond this the post-fault electrical power again falls below $P_m$ and the rotor accelerates without limit.
  6. Write the equal-area condition. The accelerating area between $\delta_0$ and the clearing angle, and the decelerating area between clearing and $\delta_{\max}$, must be equal: $$\int_{\delta_0}^{\delta_{cr}}\left(P_m-0\right)d\delta=\int_{\delta_{cr}}^{\delta_{\max}}\left(P_{\max,3}\sin\delta-P_m\right)d\delta$$ Evaluating both integrals and collecting the terms in $\delta_{cr}$ gives the closed-form result $$\cos\delta_{cr}=\frac{P_m\left(\delta_{\max}-\delta_0\right)+P_{\max,3}\cos\delta_{\max}}{P_{\max,3}}$$ where $\delta_{\max}$ and $\delta_0$ are in radians.
  7. Evaluate the critical clearing angle. Substituting the numbers, $$\cos\delta_{cr}=\frac{(1.0)(2.41188-0.45025)+(1.500)(-0.74536)}{1.500}=\frac{1.96163-1.11803}{1.500}=0.56239$$ $$\boxed{\delta_{cr} = 55.78^\circ}$$ Checking the answer by direct integration, the accelerating area is $A_1 = P_m(\delta_{cr}-\delta_0) = 0.52328$ pu-rad and the decelerating area available between $55.78^\circ$ and $138.19^\circ$ is also $0.52328$ pu-rad, so the two balance exactly.
  8. Interpret the result. The rotor may swing a further $55.78^\circ - 25.80^\circ = 29.98^\circ$ beyond its initial position before the breakers must have opened. Converting that to a clearing time requires the swing equation, $M\,d^{2}\delta/dt^{2}=P_m$ during a zero-output fault, which integrates to $t_{cr}=\sqrt{4H(\delta_{cr}-\delta_0)/(\pi f_0P_m)}$; for a typical inertia constant $H = 4$ MJ/MVA at 60 Hz this gives 0.211 s, or roughly 13 cycles — comfortably within the reach of modern protection, which clears a transmission fault in three to five cycles.
δP0°30°60°90°120°150°180°Pmδ0 = 25.8°δcr = 55.8°δmax = 138.2°A1A2Equal-area criterion: sustained zero-output fault, cleared by opening line 3pre-faultpost-fault
Figure 9 — Equal-area construction. The during-fault curve lies on the δ axis, so the accelerating area A1 is simply the rectangle Pm(δcr − δ0).

Check: Figure (4) draws F on line 3 at its receiving-end terminal, and the question states the fault is cleared by opening that line — the standard idealisation of a fault immediately outside the busbar, on the line side of the breaker. The during-fault transfer reactance is therefore infinite and the during-fault power is zero. Had the fault been located a distance along line 3 rather than at its end, a wye-delta transformation of the (source-node, receiving-bus, fault) triangle would be needed; with the whole 0.40 pu of line 3 acting as the shunt arm this would give a transfer reactance of 1.14375 pu, a during-fault peak of 1.049 pu and a critical clearing angle of 102.95°. The location as drawn gives the more conservative answer, and it is the one reported above.

Question 7 — final results
QuantityResult
Pre-fault transfer reactance0.52222 pu
Pre-fault power-angle curveP = 2.29787 sin δ pu
Initial power angle δ025.80°
During-fault power-angle curveP = 0 (transfer reactance infinite)
Post-fault transfer reactance0.80 pu
Post-fault power-angle curveP = 1.500 sin δ pu
Post-fault stable equilibrium41.81°
Limit angle δmax138.19°
Critical clearing angle δcr55.78°
Equal areas A1 = A20.5233 pu-rad
Back to the paper →