NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings: May 2018

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

  1. Question 1 Summer plant with cooling coil, reheat and a face-and-by-pass rebuild (30 marks)
  2. Question 2 Condensation on the walls of an enclosed balcony (10 marks)
  3. Question 3 Terminal reheat and VAV with discriminator control (20 marks)
  4. Question 4 Ground-water heat pump with R-134a (20 marks)
  5. Question 5 The zero net energy building (20 marks)
  6. Question 6 Equal-friction duct design for a conference centre (20 marks)
  7. Question 7 Design heat loss from a Toronto conference room (20 marks)
  8. Question 8 Carbon dioxide dilution and thermal comfort (20 marks)

Start with Question 1 →

Paper format. Eight problems, three hours, open book. Problem 1 carries 30 marks, Problem 2 carries 10 marks and Problems 3 to 8 carry 20 marks each; candidates answer any five, and indicate their choice on the cover of the first workbook. Psychrometric charts (SI and inch-pound) and an R-134a pressure–enthalpy diagram are appended to the paper. All eight problems are solved below, because the set as a whole is the study resource.

Reference texts.

Check: two readings taken from the printed paper.

(1) The length label on the Problem 6 duct sketch is printed as “L1 =  =100 ft  == 6ft”. The equation editor has dropped the symbols after each equals sign; the pattern “something = something = 100 ft” and “something = something = 6 ft” means four named lengths in two equal pairs, and the sketch shows exactly four duct runs. The solution therefore takes L1 = L2 = 100 ft (plenum to tee, and tee to elbow) and L3 = L4 = 6 ft (the two drops to the ceiling diffusers), and states the reading as an assumption under cover-page instruction 1. Only the pressure totals in parts (c) and (d) depend on it; the duct diameters in part (a) do not.

(2) Problem 1 gives the outdoor air as “percentage saturation 50 %” but the room as “RH 50 %”. These are different quantities and the difference is deliberate: percentage saturation is $\mu = W/W_{s}$, relative humidity is $\phi = p_{w}/p_{ws}$. At 26 °C the 50 % saturation state is 50.8 % RH, so treating them as interchangeable shifts the outdoor humidity ratio by about 0.2 g/kg.