22-Mec-B2 Environmental Control in Buildings · May 2018
Question 1 of 8: Summer plant with cooling coil, reheat and a face-and-by-pass rebuild (30 marks)
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Eight problems, three hours, open book.
Problem 1 carries 30 marks, Problem 2 carries 10 marks and Problems 3 to 8
carry 20 marks each; candidates answer any five, and indicate their choice on
the cover of the first workbook. Psychrometric charts (SI and inch-pound) and
an R-134a pressure–enthalpy diagram are appended to the paper.
All eight problems are solved below, because the set as a whole
is the study resource.
Reference texts.
ASHRAE, Handbook — Fundamentals (2021): Ch.1 psychrometrics,
Ch.16 ventilation and infiltration, Ch.18 heating and cooling load
calculations, Ch.21 duct design, Ch.26 heat, air and moisture transmission.
McQuiston, Parker and Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed. — loads, psychrometric
processes, duct and air distribution design.
W. P. Jones, Air Conditioning Engineering, 5th ed. — the
percentage-saturation convention, apparatus dew point and coil by-pass factor,
face-and-by-pass plant.
Shan K. Wang, Handbook of Air Conditioning and Refrigeration, 2nd
ed. — single-duct reheat and VAV systems, discriminator (zone-demand)
control.
ASHRAE Standard 55-2023, Thermal Environmental Conditions for Human
Occupancy; ASHRAE Standard 62.1-2022, Ventilation for Acceptable
Indoor Air Quality.
National Building Code of Canada 2020 and NRCan / Environment and Climate
Change Canada climatic design data for the Canadian design conditions used in
Problems 5 and 7.
Check: two readings taken from the printed
paper.
(1) The length label on the Problem 6 duct sketch is printed as
“L1 = =100 ft == 6ft”. The equation editor
has dropped the symbols after each equals sign; the pattern
“something = something = 100 ft” and
“something = something = 6 ft” means four named
lengths in two equal pairs, and the sketch shows exactly four duct runs. The
solution therefore takes L1 = L2 = 100 ft
(plenum to tee, and tee to elbow) and L3 = L4 =
6 ft (the two drops to the ceiling diffusers), and states the reading
as an assumption under cover-page instruction 1. Only the pressure totals in
parts (c) and (d) depend on it; the duct diameters in part (a) do not.
(2) Problem 1 gives the outdoor air as “percentage saturation
50 %” but the room as “RH 50 %”. These are different
quantities and the difference is deliberate: percentage saturation is
$\mu = W/W_{s}$, relative humidity is $\phi = p_{w}/p_{ws}$. At 26 °C
the 50 % saturation state is 50.8 % RH, so treating them as
interchangeable shifts the outdoor humidity ratio by about
0.2 g/kg.
Question 1: Summer plant with cooling coil, reheat and a
face-and-by-pass rebuild (30 marks)
Given. A once-through-plus-recirculation summer
plant is fully specified by its two end states, its mixing ratio and the coil
performance.
Given data, Problem 1
Quantity
Symbol
Value
Room (design) state
R
20 °C dry bulb, 50 % RH
Outdoor state
O
26 °C dry bulb, 50 % percentage saturation
Supply state to the room
S
15 °C dry bulb, 2 kg/s dry air
Mixing ratio (first plant)
—
3 parts recirculated : 1 part fresh
Cooling-coil apparatus dew point
ADP
4 °C
Coil by-pass factor
BF
0.10
Fan and duct temperature rise
Δt
2 K
Mixing ratio (rebuilt plant)
—
1 part fresh : 1 part recirculated
Barometric pressure
p
101.325 kPa (sea level)
Find. (a) the plant diagram; (b) the cycle on the
psychrometric chart; (c) the dry- and wet-bulb temperature of every significant
state point; (d) the cooling-coil duty in kW; (e) the heating-coil duty; and
(f) the percentage saturation of the air supplied by the rebuilt
face-and-by-pass plant.
Approach. Fix the two given end states from the ASHRAE
property relations, mix them by mass to reach the coil face, cut the coil line
at the by-pass factor to get the leaving state, then take the two coil duties
as enthalpy differences at the constant 2 kg/s dry-air flow; the rebuild is the
same arithmetic run backwards, with the unknown split between coil air and
by-pass air chosen so that the blend lands on the temperature the fan needs.
Problem 1 (a): the plant as first specified. Fresh air is mixed 3:1 with room air, cooled, reheated, and blown into the room; the fan and ductwork add the last 2 K.
Part (a) — describe the plant. Outdoor air O meets
recirculated room air R in the mixing box; the mixture M crosses the cooling
coil, leaving at C; a heating coil raises it sensibly to H; the fan and the
supply ductwork add the last 2 K to give the supply state S, which then
picks up the room load and returns as R. The diagram above is the answer to
part (a) — every state point that the rest of the question refers to is
labelled on it.
Fix the room state R. Relative humidity is the ratio of
partial pressures, so the humidity ratio follows from the ASHRAE saturation
pressure at 20 °C.
$$W = 0.621945\,\frac{\phi\,p_{ws}(t)}{p - \phi\,p_{ws}(t)}$$
With $p_{ws}(20^\circ\text{C}) = 2.339\ \text{kPa}$ and $\phi = 0.50$,
$$W_{R} = 0.621945 \times \frac{0.50 \times 2.339}{101.325 - 1.170}
= 0.007262\ \text{kg/kg}$$
and the moist-air enthalpy on the ASHRAE datum is
$$h = 1.006\,t + W\,(2501 + 1.86\,t) = 38.55\ \text{kJ/kg dry air}$$
Solving the adiabatic-saturation relation for this state gives a wet bulb of
13.78 °C.
Fix the outdoor state O — percentage saturation, not relative
humidity. The paper specifies $\mu = 50\ \%$, and percentage saturation
is defined on the humidity ratio directly:
$$\mu = \frac{W}{W_{s}(t)} \quad\Longrightarrow\quad
W_{O} = 0.50 \times W_{s}(26^\circ\text{C}) = 0.50 \times 0.021352
= 0.010676\ \text{kg/kg}$$
so $h_{O} = 53.37\ \text{kJ/kg}$ and the outdoor wet bulb is
18.85 °C. (The same state expressed as a relative humidity is
50.8 %, which is the small but real difference flagged in the note above.)
Mix three parts room air with one part fresh air. Adiabatic
mixing conserves dry-air mass, moisture and enthalpy exactly, so both $W$ and
$h$ are mass-weighted:
$$W_{M} = 0.75\,W_{R} + 0.25\,W_{O} = 0.75(0.007262) + 0.25(0.010676)
= 0.008115\ \text{kg/kg}$$
$$h_{M} = 0.75(38.55) + 0.25(53.37) = 42.26\ \text{kJ/kg}$$
The dry bulb is then derived from those two, not weighted separately,
because the $W t$ cross term in the enthalpy relation makes direct
temperature-weighting inconsistent:
$$t_{M} = \frac{h_{M} - 2501\,W_{M}}{1.006 + 1.86\,W_{M}}
= \frac{42.26 - 20.30}{1.0211} = \boxed{21.51\ ^\circ\text{C}}$$
Weighting the dry bulb instead would have given 21.50 °C — a
hundredth of a degree, but it is the derived value that satisfies
$h(t_{M}, W_{M}) = h_{M}$ identically, which is what makes the rest of the
arithmetic close. The mixed-air wet bulb is 15.15 °C.
Cut the coil line at the by-pass factor to reach C. A
cooling coil is modelled as a stream that fully saturates at the apparatus dew
point mixed with a fraction BF that slips through untouched, so the leaving
state lies on the straight line from M to the ADP, a fraction BF of the way back
from the ADP:
$$t_{C} = \text{ADP} + \text{BF}\,(t_{M} - \text{ADP})
= 4 + 0.10(21.51 - 4) = 5.75\ ^\circ\text{C}$$
$$W_{C} = W_{s}(\text{ADP}) + \text{BF}\,\bigl(W_{M} - W_{s}(\text{ADP})\bigr)
= 0.005034 + 0.10(0.008115 - 0.005034) = 0.005342\ \text{kg/kg}$$
giving $h_{C} = 19.20\ \text{kJ/kg}$, a wet bulb of 5.31 °C and a
relative humidity of 93.9 % — a realistic off-coil condition, which
is the first sign the model is being applied sensibly.
Work back from the supply state to size the reheat. The fan
and ductwork add 2 K after the heating coil, so the heating coil must
deliver
$$t_{H} = t_{S} - \Delta t_{\text{fan}} = 15 - 2 = 13\ ^\circ\text{C}$$
Reheat is a sensible process, so $W_{H} = W_{C} = 0.005342\ \text{kg/kg}$ and
$h_{H} = 26.57\ \text{kJ/kg}$; the wet bulb rises to 8.83 °C. The
supply state itself is 15 °C at the same humidity ratio, i.e.
50.6 % RH and a 9.74 °C wet bulb.
Part (d) — cooling-coil capacity. The coil sees the
whole 2 kg/s of dry air, and its duty is the enthalpy drop across it:
$$\dot{Q}_{c} = \dot{m}_{a}\,(h_{M} - h_{C}) = 2.0\,(42.26 - 19.20)
= \boxed{46.1\ \text{kW}}$$
Of this, $\dot{m}_{a} c_{pa}(t_{M} - t_{C}) = 2.0 \times 1.006 \times 15.76
= 31.7\ \text{kW}$ is sensible and the remaining 14.4 kW is latent, a
sensible heat ratio of 0.69 across the coil.
Part (e) — heating-coil load. Along $C \rightarrow H$
the humidity ratio is unchanged, so the duty is again an enthalpy difference:
$$\dot{Q}_{h} = \dot{m}_{a}\,(h_{H} - h_{C}) = 2.0\,(26.57 - 19.20)
= \boxed{14.7\ \text{kW}}$$
This is the price of dehumidifying to 4 °C ADP and then reheating: a
third of the cooling energy is thrown straight back in, which is exactly why
part (f) proposes removing the heating coil.
Part (c) — the state points. Collecting the six
significant points, with the mixing and coil arithmetic above:
Dry- and wet-bulb temperature at each significant point
Point
Description
Dry bulb, °C
Wet bulb, °C
W, g/kg
h, kJ/kg
O
outdoor air
26.00
18.85
10.68
53.37
R
room / recirculated air
20.00
13.78
7.26
38.55
M
after mixing, on to the coil
21.51
15.15
8.12
42.26
C
off the cooling coil
5.75
5.31
5.34
19.20
H
off the heating coil
13.00
8.83
5.34
26.57
S
supply to the room
15.00
9.74
5.34
28.60
The apparatus dew point itself is the auxiliary point at 4.00 °C
saturated, $W = 5.03\ \text{g/kg}$.
Part (b) is the plot of those six points, with the mixing line
$O\!-\!M\!-\!R$ straight, the coil line $M\!-\!C$ aimed at the apparatus dew
point, and the two horizontal sensible processes $C\!-\!H\!-\!S$.
Problem 1 (b), (c): the cycle on the ASHRAE chart. O and R mix to M, the coil line M-ADP is cut at C by the 0.1 by-pass factor, C-H is sensible reheat, H-S is the fan and duct gain, and S-R is the room process.
The remaining part removes the heating coil altogether. Because the room
humidity no longer has to be held, the plant may deliver drier or wetter air so
long as the temperature is right; blending untreated room air back into the
cold coil discharge does the reheating for nothing.
Problem 1 (f): the heating coil removed and replaced by a face-and-by-pass arrangement, room air being blended back in at mixing box 2 to lift the supply to its former temperature.
Part (f), first mixing box. The ratio is now one part fresh
to one part recirculated, so the state entering the coil is the mid-point of
$O\!-\!R$:
$$W_{1} = 0.50(0.010676) + 0.50(0.007262) = 0.008969\ \text{kg/kg},\qquad
h_{1} = 0.50(53.37) + 0.50(38.55) = 45.96\ \text{kJ/kg}$$
$$t_{1} = \frac{45.96 - 22.43}{1.0227} = 23.01\ ^\circ\text{C}$$
which is warmer and wetter than before, as it must be with twice the outdoor
air on the coil face.
Part (f), the cooling coil. The apparatus dew point and
by-pass factor are unchanged, so the same construction applies to the new
entering state:
$$t_{2} = 4 + 0.10(23.01 - 4) = 5.90\ ^\circ\text{C},\qquad
W_{2} = 0.005034 + 0.10(0.008969 - 0.005034) = 0.005427\ \text{kg/kg}$$
with $h_{2} = 19.57\ \text{kJ/kg}$. The coil leaves the air a little warmer and
a little wetter than in the original plant, because it is fed a heavier outdoor
load.
Part (f), second mixing box — find the split. Let
$\dot{m}_{c}$ be the flow over the coil face and $\dot{m}_{b} = 2 - \dot{m}_{c}$
the room air by-passed into mixing box 2. The blend must leave at
$15 - 2 = 13\ ^\circ\text{C}$ so that the fan gain lands it on the required
supply temperature. Writing the moisture and enthalpy balances and solving for
the fraction $f = \dot{m}_{c}/\dot{m}_{a}$ that satisfies
$t\bigl(h_{3}, W_{3}\bigr) = 13\ ^\circ\text{C}$ gives
$$f = 0.4973 \quad\Longrightarrow\quad
\boxed{\dot{m}_{c} = 0.995\ \text{kg/s},\qquad \dot{m}_{b} = 1.005\ \text{kg/s}}$$
so almost exactly half the air is treated and half by-passed. That is not a
coincidence: the coil discharge is about 7 K below the target and the room
air about 7 K above it.
Part (f) — the supply humidity, and the answer. With
the split known, the humidity ratio of the blend follows from the same mass
balance:
$$W_{3} = f\,W_{2} + (1 - f)\,W_{R} = 0.4973(0.005427) + 0.5027(0.007262)
= 0.006349\ \text{kg/kg}$$
The fan raises the dry bulb to 15 °C at that unchanged humidity ratio,
and the saturation humidity ratio at 15 °C is 0.010647 kg/kg, so
$$\mu_{S} = \frac{W_{S}}{W_{s}(15^\circ\text{C})}
= \frac{0.006349}{0.010647} = \boxed{0.596 \equiv 59.6\ \%\ \text{saturation}}$$
Expressed as a relative humidity the same state is 60.0 %, and its wet bulb
is 10.82 °C.
Check the rebuild is worth having. The coil now handles only
0.995 kg/s, and its duty is
$\dot{m}_{c}(h_{1} - h_{2}) = 0.995(45.96 - 19.57) = 26.3\ \text{kW}$ against
46.1 kW before, with the 14.7 kW reheat abolished. Total plant energy
falls from 60.8 kW to 26.3 kW — a 57 % saving — and
the outdoor-air fraction of the supply is essentially unchanged at
24.9 %, so ventilation is not sacrificed to get it. The price is that the
room humidity now floats, which the question explicitly permits.
Problem 1 (f): the rebuilt cycle. Blending state 2 with room air along the straight line 2-R lands on state 3 at 13 °C; the fan then carries it to 4 at 15 °C on the same humidity ratio.
Problem 1 — results
Part
Quantity
Result
(a)
System diagram
mixing box → cooling coil → heating coil → fan → room, with 3:1 recirculation
(b)
Operating cycle
O–M–R mixing line, M–C coil line to the 4 °C ADP, C–H–S sensible
(c)
State points (db / wb, °C)
O 26.00 / 18.85; R 20.00 / 13.78; M 21.51 / 15.15; C 5.75 / 5.31; H 13.00 / 8.83; S 15.00 / 9.74
(d)
Cooling-coil capacity
46.1 kW (31.7 kW sensible, 14.4 kW latent)
(e)
Heating-coil load
14.7 kW
(f)
Supply percentage saturation, rebuilt plant
59.6 % (60.0 % RH), with 0.995 kg/s over the coil and 1.005 kg/s by-passed