22-Mec-B2 Environmental Control in Buildings · May 2018
Question 8 of 8: Carbon dioxide dilution and thermal comfort (20 marks)
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Eight problems, three hours, open book.
Problem 1 carries 30 marks, Problem 2 carries 10 marks and Problems 3 to 8
carry 20 marks each; candidates answer any five, and indicate their choice on
the cover of the first workbook. Psychrometric charts (SI and inch-pound) and
an R-134a pressure–enthalpy diagram are appended to the paper.
All eight problems are solved below, because the set as a whole
is the study resource.
Reference texts.
ASHRAE, Handbook — Fundamentals (2021): Ch.1 psychrometrics,
Ch.16 ventilation and infiltration, Ch.18 heating and cooling load
calculations, Ch.21 duct design, Ch.26 heat, air and moisture transmission.
McQuiston, Parker and Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed. — loads, psychrometric
processes, duct and air distribution design.
W. P. Jones, Air Conditioning Engineering, 5th ed. — the
percentage-saturation convention, apparatus dew point and coil by-pass factor,
face-and-by-pass plant.
Shan K. Wang, Handbook of Air Conditioning and Refrigeration, 2nd
ed. — single-duct reheat and VAV systems, discriminator (zone-demand)
control.
ASHRAE Standard 55-2023, Thermal Environmental Conditions for Human
Occupancy; ASHRAE Standard 62.1-2022, Ventilation for Acceptable
Indoor Air Quality.
National Building Code of Canada 2020 and NRCan / Environment and Climate
Change Canada climatic design data for the Canadian design conditions used in
Problems 5 and 7.
Check: two readings taken from the printed
paper.
(1) The length label on the Problem 6 duct sketch is printed as
“L1 = =100 ft == 6ft”. The equation editor
has dropped the symbols after each equals sign; the pattern
“something = something = 100 ft” and
“something = something = 6 ft” means four named
lengths in two equal pairs, and the sketch shows exactly four duct runs. The
solution therefore takes L1 = L2 = 100 ft
(plenum to tee, and tee to elbow) and L3 = L4 =
6 ft (the two drops to the ceiling diffusers), and states the reading
as an assumption under cover-page instruction 1. Only the pressure totals in
parts (c) and (d) depend on it; the duct diameters in part (a) do not.
(2) Problem 1 gives the outdoor air as “percentage saturation
50 %” but the room as “RH 50 %”. These are different
quantities and the difference is deliberate: percentage saturation is
$\mu = W/W_{s}$, relative humidity is $\phi = p_{w}/p_{ws}$. At 26 °C
the 50 % saturation state is 50.8 % RH, so treating them as
interchangeable shifts the outdoor humidity ratio by about
0.2 g/kg.
Question 8: Carbon dioxide dilution and thermal comfort
(20 marks)
Find. (a) the occupancy at which the space just reaches
1,000 ppm, and (b) a comfort assessment of the stated state for three
different occupant groups.
Approach. Part (a) is a steady-state contaminant mass
balance on a completely mixed space; part (b) plots the room state against the
ASHRAE Standard 55 comfort envelopes and then adjusts for the mean radiant
temperature, the metabolic rate and the occupant group.
Part (a) — write the steady-state balance. At steady
state the carbon dioxide generated in the space equals the net amount carried
out by the ventilating air:
$$N\,\dot{V}_{\text{CO}_{2}} = \dot{V}_{\text{air}}\,(C_{\text{space}}
- C_{\text{supply}})$$
This is the same “source equals removal” statement as a dilution
ventilation calculation for any contaminant; the ppm are volume fractions, so no
unit conversion is needed on the right-hand side beyond the factor
$10^{-6}$.
Part (a) — substitute and solve. With
$\dot{V}_{\text{CO}_{2}} = 0.005\ \text{L/s} = 5 \times 10^{-6}\
\text{m}^{3}/\text{s}$ per person,
$$N = \frac{\dot{V}_{\text{air}}\,(C_{\text{space}} - C_{\text{supply}})}
{\dot{V}_{\text{CO}_{2}}}
= \frac{3.2 \times (1000 - 260) \times 10^{-6}}{5 \times 10^{-6}}
= \frac{2.368 \times 10^{-3}}{5 \times 10^{-6}} = 473.6$$
Occupancy is an integer and the limit must not be exceeded, so
$$\boxed{N = 473\ \text{persons}}$$
Part (a) — check it against the ventilation standard.
At 473 people the outdoor air per person is
$3.2 \times 1000/473 = 6.8\ \text{L/s}$, which sits neatly between the
5 L/s per person of the older ventilation standards and the
8 to 10 L/s that ASHRAE Standard 62.1 requires for an assembly
space once the floor-area component is included. In other words the
1,000 ppm criterion and the prescriptive ventilation rate are two
expressions of the same requirement — which is exactly why 1,000 ppm
became the conventional indoor limit. Two caveats belong with the answer: the
result assumes complete mixing (a real room with an air-distribution
effectiveness of 0.8 would support only about 380 people at the same limit), and
1,000 ppm is an odour and ventilation-adequacy criterion, not a health
limit — the occupational exposure limit is 5,000 ppm.
Part (b) — fix the room state. At 70 °F dry
bulb and 64 °F wet bulb the adiabatic-saturation relation gives
$$W = 0.01136\ \text{lb/lb}, \qquad \phi = 72.6\ \%, \qquad
t_{dp} = 60.8\ ^\circ\text{F}, \qquad h = 29.2\ \text{Btu/lb}$$
So the space is cool and distinctly humid: the humidity ratio is right at the
0.012 lb/lb upper bound that ASHRAE Standard 55 places on the comfort zone,
and the dew point is only 1.4 °F below the 62.2 °F
limit.
Part (b)(a) — lightly clothed and sedentary. Light
clothing is about 0.5 clo, which is the summer assumption, and the summer
comfort zone runs roughly 73 to 79 °F operative temperature. With no
information to the contrary the mean radiant temperature equals the air
temperature, so the operative temperature is 70 °F —
3 °F below the bottom of the zone. The group will feel
slightly cool, and the high humidity makes it worse rather than better, because
a nearly saturated environment suppresses evaporative loss at the skin without
providing any warmth. The verdict is that the space is outside the
comfort zone on the cool side, with humidity at its permitted
maximum; more than the 20 % of occupants that Standard 55 allows
would be expected to complain. The remedy is to raise the dry bulb to about
75 °F and dehumidify to 50 % relative humidity, which moves the
state to the middle of the summer zone. (If the group were in fact wearing
winter clothing at 1.0 clo, 70 °F would be acceptable on
temperature — the winter zone runs 68 to 75 °F — and only
the humidity would be marginal; the question specifies light clothing, so the
cool verdict stands.)
Part (b)(b) — radiant temperature 78 °F, light
activity. Two changes act in the same direction. First, comfort
responds to the operative temperature, which for still air is the mean of air
and radiant temperature:
$$t_{o} = \frac{t_{db} + \text{MRT}}{2} = \frac{70 + 78}{2}
= 74\ ^\circ\text{F}$$
so the warm surfaces have moved the effective condition to the lower part of the
summer comfort zone. Second, going from sedentary (1.1 met) to light
activity (about 1.6 met) raises metabolic heat production by roughly a
half, and the neutral temperature falls by about 5 °F for that
increase. The conclusion is that the group is now at or slightly above
neutral rather than cool — the thermal complaint is
resolved — but the moisture problem is aggravated, because a more active
body needs to reject a larger fraction of its heat by evaporation and the
72.6 % relative humidity is precisely what prevents it. They will report
feeling warm and sticky rather than cold. The correct fix is to attack the
humidity: dehumidify to 50 % and, if the surfaces cannot be cooled, add
air movement, since Standard 55 permits an elevated-air-speed offset of up to
about 5 °F at 0.8 m/s for occupants with local control.
Part (b)(c) — a retired group playing cards. The
research finding here is often misquoted, so it is worth stating carefully:
Fanger showed that at the same activity and clothing elderly people
prefer the same thermal environment as young adults, because their lower
metabolic rate is offset by a lower evaporative loss. The reason they usually
need warmer rooms is that their activity is lower. Card playing while
seated is about 1.0 met against the 1.1 to 1.2 of ordinary
sedentary work, so the neutral temperature rises by roughly
2 to 3 °F, and the 70 °F room that was already
3 °F too cool for the first group is now 5 to
6 °F too cool. Older occupants are also more sensitive to
draught and to cold floors, and less able to detect and respond to a slow drift
in temperature.
Part (b)(c) — so, is a change necessary?Yes. Raise the dry bulb to 75 to 76 °F
and reduce the relative humidity to 45 to 50 %, which puts
the state in the centre of the comfort zone for 0.5 clo at 1.0 met and
simultaneously pulls the dew point down from 60.8 to about
54 °F. Keep the air speed below 0.15 m/s (30 fpm) in the
occupied zone and avoid overhead cold-air dumping, keep the vertical air
temperature difference between ankle and head below 5 °F, and keep the
floor surface above 66 °F. If the group cannot be assumed to be lightly
clothed, the alternative of asking them to add a light sweater
(0.3 clo) would recover about 4 °F of the shortfall, but changing
the room condition is the appropriate design response.
Problem 8 (b): the stated room state plotted against the ASHRAE Standard 55 comfort envelopes. It falls inside the winter (1.0 clo) zone but to the LEFT of the summer (0.5 clo) zone that a lightly clothed group needs, and it sits high on humidity.
Problem 8 — results
Part
Quantity
Result
(a)
Maximum occupancy at 1,000 ppm
473 persons (473.6 before rounding down)
(a)
Corresponding outdoor air per person
6.8 L/s, consistent with ASHRAE 62.1
(b)
Room state at 70 °F db / 64 °F wb
W = 0.01136 lb/lb, 72.6 % RH, dew point 60.8 °F, h = 29.2 Btu/lb
(b)(a)
Lightly clothed, sedentary
Uncomfortable — about 3 °F below the summer zone, humidity at its limit
(b)(b)
MRT 78 °F, light activity
to = 74 °F: thermally acceptable, but warm and humid; dehumidify to 50 % RH
(b)(c)
Retired group playing cards
Too cool by 5 to 6 °F — yes, change the room: 75–76 °F and 45–50 % RH, air speed below 30 fpm