NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · May 2018

Question 7 of 8: Design heat loss from a Toronto conference room (20 marks)

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. Eight problems, three hours, open book. Problem 1 carries 30 marks, Problem 2 carries 10 marks and Problems 3 to 8 carry 20 marks each; candidates answer any five, and indicate their choice on the cover of the first workbook. Psychrometric charts (SI and inch-pound) and an R-134a pressure–enthalpy diagram are appended to the paper. All eight problems are solved below, because the set as a whole is the study resource.

Reference texts.

Check: two readings taken from the printed paper.

(1) The length label on the Problem 6 duct sketch is printed as “L1 =  =100 ft  == 6ft”. The equation editor has dropped the symbols after each equals sign; the pattern “something = something = 100 ft” and “something = something = 6 ft” means four named lengths in two equal pairs, and the sketch shows exactly four duct runs. The solution therefore takes L1 = L2 = 100 ft (plenum to tee, and tee to elbow) and L3 = L4 = 6 ft (the two drops to the ceiling diffusers), and states the reading as an assumption under cover-page instruction 1. Only the pressure totals in parts (c) and (d) depend on it; the duct diameters in part (a) do not.

(2) Problem 1 gives the outdoor air as “percentage saturation 50 %” but the room as “RH 50 %”. These are different quantities and the difference is deliberate: percentage saturation is $\mu = W/W_{s}$, relative humidity is $\phi = p_{w}/p_{ws}$. At 26 °C the 50 % saturation state is 50.8 % RH, so treating them as interchangeable shifts the outdoor humidity ratio by about 0.2 g/kg.

Question 7: Design heat loss from a Toronto conference room (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A single conditioned room with two exposed walls, no floor, ceiling or party-wall loss, and infiltration driven by a stated pressure difference.

Given data, Problem 7
QuantityValue
Room dimensions120 ft × 60 ft × 20 ft high
Exposed wallstwo, each 120 ft long × 20 ft high
Windows15 per exposed wall, 3 ft × 5 ft, double-hung wood sash, single glazed, non-weather-stripped, average fit, frame joint caulked
Wall build-up (outside to inside)4 in. face brick / 12 in. sand-and-aggregate concrete block / 4 in. fibreglass board / vapour barrier / ½ in. plaster board
Pressure difference across the windward wall0.2 in. water, outside higher
Adjacent spacesconditioned left, right, above and below — no heat transfer assumed

Find. (a) the indoor and outdoor design conditions, with justification, and (b) the design heat loss from the room.

Approach. Choose the design conditions from Canadian climatic design data, build the wall U-value from the layer resistances, take the glazing from published fenestration data, compute infiltration by the crack method on the stated pressure difference, and sum the three.

  1. Part (a) — outdoor design condition. The heating design temperature for Toronto (Pearson) is 0 °F (−18 °C), taken as the ASHRAE 99.6 % annual heating dry bulb, which for that station is −18.2 °C (−0.7 °F); the National Building Code of Canada 2020 January 2.5 % design temperature for Toronto is the same −18 °C. The percentile matters: a heating plant is sized so that it just meets the load for all but roughly 35 hours a year, and picking a colder record temperature would oversize the plant and force it to cycle at part load for the whole season. Design wind is 15 mph, which is the condition the surface films and the crack-flow coefficients below assume; the outdoor air is taken as saturated, giving $W_{o} = 0.00078\ \text{lb/lb}$.
  2. Part (a) — indoor design condition, and a humidity warning. Take 72 °F (22 °C) dry bulb, the middle of the ASHRAE Standard 55 winter operative-temperature range for sedentary occupants at 1.0 clo, which is what a seated conference audience wears indoors in winter. Humidity has to be chosen against the glazing, not against comfort: with $U_{g} = 0.98$ and an inside film coefficient of $1/0.68 = 1.47\ \text{Btu/h}\cdot\text{ft}^{2}\cdot^\circ\text{F}$, the inner glass surface sits at $$t_{si} = t_{i} - \frac{U_{g}}{h_{i}}(t_{i} - t_{o}) = 72 - \frac{0.98}{1.47}(72) = 24.0\ ^\circ\text{F}$$ so any indoor relative humidity above about 16 % will frost the single glazing. The practical answer is therefore 72 °F at 20 °C–equivalent comfort with the humidity held near the 20 to 25 % that ASHRAE 55 tolerates, accepting some condensation at the glass edge, and to note in the design report that the single glazing — not the humidifier — is the constraint.
  3. Part (b) — areas. Only the two exposed walls lose heat: $$A_{\text{gross}} = 2 \times 120 \times 20 = 4{,}800\ \text{ft}^{2},\qquad A_{\text{win}} = 30 \times 3 \times 5 = 450\ \text{ft}^{2}$$ $$A_{\text{wall}} = 4{,}800 - 450 = 4{,}350\ \text{ft}^{2}$$ The floor, ceiling and the two 60 ft end walls face conditioned space and carry no load by the question's own instruction.
  4. Part (b) — the wall U-value. Summing the layer resistances in $\text{h}\cdot\text{ft}^{2}\cdot^\circ\text{F}/\text{Btu}$:
    Wall thermal resistance
    LayerR
    outside surface film, 15 mph winter0.17
    face brick, 4 in.0.43
    concrete block, sand and aggregate, 12 in.1.28
    fibreglass board insulation, 4 in. at R 4.0 per inch16.00
    vapour barrier (plastic film)0.00
    plaster board, ½ in.0.45
    inside surface film, still air0.68
    Total19.01
    $$U_{\text{wall}} = \frac{1}{19.01} = 0.0526\ \frac{\text{Btu}}{\text{h}\cdot\text{ft}^{2}\cdot{}^\circ\text{F}}$$ The vapour barrier contributes nothing thermally — it is there for moisture control, and the fibreglass board alone carries 84 % of the resistance.
  5. Part (b) — transmission losses. With $\Delta t = 72 - 0 = 72\ ^\circ\text{F}$, and taking $U_{\text{win}} = 0.98$ for a single-glazed, wood-framed, operable window: $$\dot{Q}_{\text{wall}} = U A \Delta t = 0.0526 \times 4{,}350 \times 72 = 16{,}476\ \text{Btu/h}$$ $$\dot{Q}_{\text{win}} = 0.98 \times 450 \times 72 = 31{,}752\ \text{Btu/h}$$ The windows occupy 9 % of the exposed wall area and lose almost twice as much as the other 91 % — a ratio of nineteen to one in loss per square foot.
  6. Part (b) — infiltration by the crack method. A double-hung sash leaks along its perimeter and along the meeting rail, so the crack length per window is $$L_{c} = 2H + 3W = 2(5) + 3(3) = 19\ \text{ft}$$ Only the windward wall infiltrates — the leeward wall exfiltrates — so 15 windows are counted, giving 285 ft of crack. (The alternative convention of taking half the total crack length gives $\tfrac{1}{2}(30)(19) = 285\ \text{ft}$ as well, so the two rules agree here.) The crack flow follows a power law in the pressure difference, $$\frac{\dot{V}}{L_{c}} = K\,(\Delta p)^{n} = 3.4\,(0.2)^{0.65} = 1.194\ \frac{\text{cfm}}{\text{ft}}$$ with $K = 3.4$ and $n = 0.65$ for an average-fit, non-weather-stripped double-hung wood sash; the caulked frame-to-wall joint means no separate frame leakage need be added. Hence $$\dot{V}_{\text{inf}} = 1.194 \times 285 = \boxed{340\ \text{cfm}}$$ which is 0.14 air changes per hour on the 144,000 ft³ room — a believable figure for leaky sash windows, and a useful sanity check that the coefficient has been applied correctly.
  7. Part (b) — the infiltration load and the total. $$\dot{Q}_{\text{inf}} = 1.08\,\dot{V}\,\Delta t = 1.08 \times 340 \times 72 = 26{,}470\ \text{Btu/h}$$ $$\dot{Q}_{\text{total}} = 16{,}476 + 31{,}752 + 26{,}470 = \boxed{74{,}700\ \text{Btu/h}} \equiv 21.9\ \text{kW}$$ Expressed against the floor area that is 10.4 Btu/h per square foot, which is a high but entirely plausible intensity for a 1960s-vintage single-glazed perimeter space.
  8. Interpret the split, and note what has been left out. Windows take 42.5 % of the loss, infiltration 35.4 % and the insulated wall only 22.1 %. Replacing the single glazing with a sealed double unit at $U = 0.49$ would remove 15,900 Btu/h and weather-stripping the sashes would remove roughly half the infiltration — together a 34 % cut, for far less money than any change to the already well-insulated wall. Two deliberate omissions should be declared: the humidification load, which at 20 % indoor relative humidity is a further $4{,}840 \times 340 \times (0.00331 - 0.00078) = 4{,}160\ \text{Btu/h}$ of latent duty and is normally carried by the central plant rather than by the room; and any internal gain from the occupants, which a design heat-loss calculation properly ignores because the plant must be able to bring the room up from cold before they arrive.
outside air filmR 0.174 in. fibreglass boardR 16.00inside air filmR 0.684 in. face brickR 0.43vapour barrierR 0.0012 in. concrete blockR 1.281/2 in. plaster boardR 0.45outdoorsindoorstotal R = 19.01 h·ft²·°F/Btu ⇒ U = 0.0526 Btu/h·ft²·°F
Problem 7 (b): the wall section. The 4 in. of fibreglass board carries 84 % of the thermal resistance; the masonry and the surface films contribute the rest. Layer thicknesses are drawn to scale; the two air films are shown as narrow bands.
Design heat loss, 72 °F indoors against 0 °F outdoors22 %opaque wall16,476 Btu/h43 %windows31,752 Btu/h35 %infiltration26,470 Btu/hdesign heat loss 74,697 Btu/h (21.9 kW)
Problem 7 (b): where the heat goes. The 450 ft² of single glazing loses nearly twice as much as the 4,350 ft² of insulated wall.
Problem 7 — results
PartQuantityResult
(a)Outdoor design temperature0 °F (-18 °C), ASHRAE 99.6 % heating dry bulb / NBC January 2.5 % for Toronto
(a)Indoor design condition72 °F (22 °C), ASHRAE 55 winter zone at 1.0 clo; relative humidity limited to about 16 % by the single glazing
(b)Wall U-value0.0526 Btu/h·ft²·°F (R 19.01)
(b)Wall / window / net areas4,350 / 450 / 4,800 ft²
(b)Transmission, opaque wall16,476 Btu/h
(b)Transmission, windows31,752 Btu/h
(b)Infiltration air flow340 cfm (0.14 ACH)
(b)Infiltration, sensible26,470 Btu/h
(b)Design heat loss74,700 Btu/h (21.9 kW)
—Additional humidification duty at 20 % RH4,160 Btu/h latent