Question 2 of 7: Post-tensioned prestressed-concrete girder
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, December 2015 — 07-Str-A5 Advanced
Structural Design. Three hours, "closed book" (textbooks and design handbooks permitted, no
notes). Seven questions; any five constitute a complete paper and all are of equal value, the
printed mark split being 20 marks each. All loads shown on Figures 1–4 are unfactored.
All seven questions are answered here.
Design data printed on page 1 and used throughout.
Concrete \(f'_c = 30\ \text{MPa}\); structural steel \(F_y = 350\ \text{MPa}\);
reinforcing steel \(f_y = 400\ \text{MPa}\); prestressed concrete \(f'_{ci} = 35\ \text{MPa}\)
at transfer and \(f'_c = 50\ \text{MPa}\) in service, \(n = 6\);
\(f_{pu} = 1750\ \text{MPa}\), \(f_{py} = 1450\ \text{MPa}\),
\(f_{p,\text{initial}} = 1200\ \text{MPa}\), losses \(= 240\ \text{MPa}\), hence
\(f_{pe} = 960\ \text{MPa}\) and the loss ratio \(\eta = 0.80\).
Check: load factors and figure data. The paper states only that "all loads
shown are unfactored" and gives no load classification, so every printed load is treated as a
specified live load and factored at 1.5, while member and element self weight is
treated as dead and factored at 1.25 (NBCC 2020 Case 2, \(1.25D + 1.5L\)). Resistance factors
are \(\phi = 0.90\) (steel), \(\phi_w = 0.67\) with the additional 0.67 of CSA S16
Cl. 13.13.2.2 (welds), \(\phi_{sc} = 0.80\) (shear studs), \(\phi_c = 0.65\),
\(\phi_s = 0.85\), \(\phi_p = 0.90\) (CSA A23.3). Figure 2 has a free tip at A, a roller at B and a pin at C; Figure 4 has a
hatched fixed base at A and a hatched fixed end at C, with the 200 kN arrow pointing
towards the frame at mid-height of the column.
Reference texts for 07-Str-A5.
CSA S16:19, Design of Steel Structures, with the CISC Handbook of Steel
Construction (11th ed.) — Cl. 13.3 (compression), 13.4 (shear), 13.5–13.6
(flexure and lateral–torsional buckling), 13.8 (beam–columns), 13.13 (welds),
14.3–14.6 (plate girders), Cl. 17 (composite beams).
Given. From Figure 2, a girder with a 2 m overhang and a 12 m span: the tip A
is free and carries 60 kN, B is a roller 2 m from A, C is a pin 14 m from A, and a 400 kN load
acts at midspan of BC (8 m from A).
Given data (Figure 2 and the page-1 prestressing data)
Find. A gross concrete section, the strand area \(A_{ps}\) and a tendon
profile such that no fibre anywhere carries tension either at transfer or in service.
Figure 2 girder with the permissible cable zone shaded and the adopted harped tendon profile drawn through it.
Approach. Compute the service moments, then size the section from the
cable-zone condition — the requirement that the band
\(M_T/P_e - k_t \le e \le k_b + M_{sw}/P_i\) is not empty — because with "no tension"
enforced at both stages it is the section, not the strand count, that governs; finally lay a
harped tendon inside that band and confirm the ultimate capacity.
Service moments from the applied loads. Taking moments about B for the
overhanging beam, \(R_C(12) + 60(2) = 400(6)\), so \(R_C = 190\ \text{kN}\) and
\(R_B = 270\ \text{kN}\). Hence
$$M_B = -60(2) = -120\ \text{kN}\cdot\text{m}, \qquad
M_{\text{mid}} = R_C(6) = 190(6) = 1140\ \text{kN}\cdot\text{m}$$
The overhang puts the girder into hogging over B and sagging at midspan, so both faces
must be kept in compression.
Choose a trial section and add its self weight. Try a solid rectangle
\(450 \times 1800\): \(A = 810\,000\ \text{mm}^2\), \(S = 2.43 \times 10^{8}\ \text{mm}^3\) and,
since the section is symmetric, both kern distances equal
\(k = S/A = 300\ \text{mm}\). Its self weight is \(0.45(1.8)(24) = 19.44\ \text{kN/m}\), which
adds \(M_{sw} = 330.5\ \text{kN}\cdot\text{m}\) at midspan and \(-38.9\ \text{kN}\cdot\text{m}\)
at B. The total service moments are therefore
\(M_T = 1470.5\ \text{kN}\cdot\text{m}\) at midspan and \(-158.9\ \text{kN}\cdot\text{m}\) at B.
Size the section from the cable zone, not from the strand count. Keeping the
bottom fibre in compression in service requires \(e \ge M_T/P_e - k_t\); keeping the top fibre in
compression at transfer requires \(e \le k_b + M_{sw}/P_i\). Subtracting, a usable zone exists
only when
$$k_t + k_b + \frac{M_{sw}}{P_i} - \frac{M_T}{\eta P_i} \;\ge\; 0
\quad\Longrightarrow\quad
P_i \;\ge\; \frac{M_T/\eta - M_{sw}}{k_t + k_b} = \frac{1838.1 - 330.5}{0.600}
= \boxed{2513\ \text{kN}}$$
This is the real design driver: a smaller section closes the zone entirely, and no strand count
can reopen it.
Strands. Adopt \(n = 17\) low-relaxation strands of 15.2 mm diameter,
\(A_{ps} = 17(140) = \boxed{2380\ \text{mm}^2}\), giving
$$P_i = 2380(1200) = 2856\ \text{kN}, \qquad P_e = 2380(960) = 2284.8\ \text{kN}$$
At midspan the cable zone is then
$$\frac{M_T}{P_e} - k_t = \frac{1470.5\times10^6}{2.285\times10^6} - 300 = 343.6\ \text{mm}
\;\le\; e \;\le\; 300 + \frac{330.5\times10^6}{2.856\times10^6} = 415.7\ \text{mm}$$
so take \(e_{\text{mid}} = 400\ \text{mm}\) below the centroid, comfortably inside the band and
leaving 500 mm of concrete below the duct.
Confirm the stresses at both stages. Using
\(f = -P/A \mp Pe/S \pm M/S\) with compression negative:
$$\text{transfer, midspan:}\quad f_{\text{top}} = -0.19\ \text{MPa}, \quad f_{\text{bot}} = -6.87\ \text{MPa}$$
$$\text{service, midspan:}\quad f_{\text{top}} = -5.11\ \text{MPa}, \quad f_{\text{bot}} = -0.53\ \text{MPa}$$
Every value is compressive, so the "no tension" requirement is met, and the peaks sit well below
the permissible \(0.6f'_{ci} = 21\ \text{MPa}\) at transfer and \(0.45f'_c = 22.5\ \text{MPa}\)
in service.
Profile through the overhang and the anchorages. Over B the moment is
hogging, so the tendon must rise: the top fibre stays in compression only while
\(e \le k + M_B/P_e = 300 - 69.5 = \boxed{230.5\ \text{mm}}\). At A and C the moment is zero, so
the anchorages must lie inside the kern, \(|e| \le 300\ \text{mm}\). A harped (trapezoidal)
profile therefore serves: \(e = 0\) at A, 200 mm at B, 400 mm at midspan and 0 at C. A single
parabola would not, because the moment diagram of an overhanging beam with one point load is
made of straight lines and a parabola cuts across them; the shaded band in the figure above shows
the harped line staying inside the zone at every quarter point, for instance
\(31.8 \le 300 \le 383\ \text{mm}\) at 3 m from B.
Ultimate flexural check. With \(k_p = 2(1.04 - f_{py}/f_{pu}) = 0.423\),
\(d_p = 900 + 400 = 1300\ \text{mm}\), \(\alpha_1 = 0.775\) and \(\beta_1 = 0.845\) for
\(f'_c = 50\ \text{MPa}\), equilibrium gives \(c = 347\ \text{mm}\),
\(f_{pr} = 1552\ \text{MPa}\) and
$$M_r = \phi_p A_{ps} f_{pr}\left(d_p - \tfrac{\beta_1 c}{2}\right) = \boxed{3835\ \text{kN}\cdot\text{m}}$$
against \(M_f = 1.5(1140) + 1.25(330.5) = 2123\ \text{kN}\cdot\text{m}\). The service no-tension
rule, not strength, governs this girder — which is the usual outcome for a fully
prestressed member.
Question 2 — final results
Item
Value
Section
Rectangular 450 × 1800 mm, \(k_t = k_b = 300\) mm
Minimum \(P_i\) for a non-empty cable zone
2513 kN
Strands / area
17 – 15.2 mm strands, \(A_{ps} = 2380\ \text{mm}^2\)
\(P_i\) / \(P_e\)
2856 kN / 2284.8 kN
Cable zone at midspan
343.6 – 415.7 mm; adopt \(e = 400\) mm
Maximum \(e\) over support B
230.5 mm; adopt 200 mm
Profile
Harped: 0 at A, 200 mm at B, 400 mm at midspan, 0 at C