Question 4 of 7: Plastic design of the steel rigid frame, and its footing
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, December 2015 — 07-Str-A5 Advanced
Structural Design. Three hours, "closed book" (textbooks and design handbooks permitted, no
notes). Seven questions; any five constitute a complete paper and all are of equal value, the
printed mark split being 20 marks each. All loads shown on Figures 1–4 are unfactored.
All seven questions are answered here.
Design data printed on page 1 and used throughout.
Concrete \(f'_c = 30\ \text{MPa}\); structural steel \(F_y = 350\ \text{MPa}\);
reinforcing steel \(f_y = 400\ \text{MPa}\); prestressed concrete \(f'_{ci} = 35\ \text{MPa}\)
at transfer and \(f'_c = 50\ \text{MPa}\) in service, \(n = 6\);
\(f_{pu} = 1750\ \text{MPa}\), \(f_{py} = 1450\ \text{MPa}\),
\(f_{p,\text{initial}} = 1200\ \text{MPa}\), losses \(= 240\ \text{MPa}\), hence
\(f_{pe} = 960\ \text{MPa}\) and the loss ratio \(\eta = 0.80\).
Check: load factors and figure data. The paper states only that "all loads
shown are unfactored" and gives no load classification, so every printed load is treated as a
specified live load and factored at 1.5, while member and element self weight is
treated as dead and factored at 1.25 (NBCC 2020 Case 2, \(1.25D + 1.5L\)). Resistance factors
are \(\phi = 0.90\) (steel), \(\phi_w = 0.67\) with the additional 0.67 of CSA S16
Cl. 13.13.2.2 (welds), \(\phi_{sc} = 0.80\) (shear studs), \(\phi_c = 0.65\),
\(\phi_s = 0.85\), \(\phi_p = 0.90\) (CSA A23.3). Figure 2 has a free tip at A, a roller at B and a pin at C; Figure 4 has a
hatched fixed base at A and a hatched fixed end at C, with the 200 kN arrow pointing
towards the frame at mid-height of the column.
Reference texts for 07-Str-A5.
CSA S16:19, Design of Steel Structures, with the CISC Handbook of Steel
Construction (11th ed.) — Cl. 13.3 (compression), 13.4 (shear), 13.5–13.6
(flexure and lateral–torsional buckling), 13.8 (beam–columns), 13.13 (welds),
14.3–14.6 (plate girders), Cl. 17 (composite beams).
Given. From Figure 4: an L-shaped rigid frame with a 10 m column AB fixed at
A and a 9 m beam BC fixed at C. A 200 kN horizontal load acts at mid-height of the column, a
600 kN load acts vertically at the joint B, and two 450 kN loads act on the beam at 3 m and 6 m
from B. The column has capacity \(M_p\) and the beam \(2M_p\).
Given data (Figure 4)
Quantity
Value
Column AB height / beam BC span
10.0 m / 9.0 m (3 + 3 + 3)
Horizontal load at 5 m up the column
200 kN, specified
Vertical load at joint B
600 kN, specified
Vertical loads on the beam at 3 m and 6 m
450 kN each, specified
Supports
A fixed, C fixed
Plastic capacities
column \(1M_p\), beam \(2M_p\)
Soil bearing capacity
350 kPa
Find. (a) steel sections for BC and AB from a plastic collapse analysis;
(b) the plan size and thickness of the footing at A.
Approach. Because C is fully fixed and the beam is axially rigid, joint B
cannot translate, so there is no sway mechanism; enumerate the remaining independent mechanisms,
take the largest required \(M_p\), confirm it with a statically admissible moment field, select
Class 1 sections, and size the footing from the service base moment and axial load.
Factored loads and possible hinge locations. \(H_f = 1.5(200) = 300\) kN,
\(P_{B,f} = 900\) kN and the two beam loads become 675 kN each. Hinges can form at A, at
the column load point D (5 m), at B, at E (3 m along the beam), at F (6 m) and at C — six
locations against three redundancies, so three independent mechanisms. At the corner B only two
members meet, so the joint moment cannot exceed the weaker member's capacity, \(M_p\).
Why there is no sway mechanism. A sway would require B to move horizontally,
but the beam is axially rigid and C is fixed, so the 200 kN is carried into C as beam axial
force. The column therefore behaves as a member restrained in position at both ends, and its
mechanism is a "beam" mechanism with hinges at A, D and B.
Mechanism 1 — column. Rotate AD by \(\theta\) so D moves \(5\theta\)
sideways, DB rotating back by \(\theta\):
$$M_p\theta + M_p(2\theta) + M_p\theta = 300(5\theta)
\;\Rightarrow\; M_p = \frac{1500}{4} = 375\ \text{kN}\cdot\text{m}$$
Mechanisms 2 and 3 — beam, hinge at E then at F. With a hinge at E the
segment BE rotates \(\theta\) and EC rotates \(0.5\theta\), so the hinge rotations are
\(\theta\) at B, \(1.5\theta\) at E and \(0.5\theta\) at C, and the load at F drops
\(1.5\theta\):
$$M_p\theta + 2M_p(1.5\theta) + 2M_p(0.5\theta) = 675(3\theta) + 675(1.5\theta)
\;\Rightarrow\; M_p = \frac{3037.5}{5} = \boxed{607.5\ \text{kN}\cdot\text{m}}$$
Repeating with the hinge at F gives \(11M_p\theta = 6075\theta\), i.e.
\(M_p = 552.3\ \text{kN}\cdot\text{m}\). Combining the column and beam mechanisms cannot help:
both rotate the corner hinge in the same sense, so nothing cancels there.
Confirm by the lower-bound theorem. The kinematic method gives an upper
bound on the collapse load, so the required \(M_p\) is the largest of the three values,
607.5 kN·m. Check that a statically admissible field exists: put
\(M_C = -2M_p = -1215\), \(M_E = +1215\) and \(M_B = -607.5\); equilibrium of the beam then
requires \(V_C = 742.5\ \text{kN}\), which leaves
\(M_F = -1215 + 3(742.5) = 1012.5\ \text{kN}\cdot\text{m} \le 2M_p\). Nowhere is a capacity
exceeded, so 607.5 kN·m is exact.
(a) Beam BC. The beam needs \(2M_p = 1215\ \text{kN}\cdot\text{m}\), so
$$Z_{\text{req}} = \frac{1215 \times 10^{6}}{0.9(350)} = 3.86 \times 10^{6}\ \text{mm}^3$$
Adopt a welded I with flanges \(250 \times 22\) and web \(560 \times 10\)
(\(Z = 3.985 \times 10^{6}\ \text{mm}^3\), \(d = 604\ \text{mm}\)), giving
\(M_r = \phi ZF_y = \boxed{1255\ \text{kN}\cdot\text{m}} \ge 1215\). It is Class 1
(\(b/t = 5.45 < 7.75\); \(h/w = 56.0 < 58.8\)), which plastic design requires, and its shear
resistance \(V_r = 1128\ \text{kN}\) covers the 742.5 kN at C.
(a) Column AB. Plastic design asks only for \(M_p = 607.5\), so
\(Z_{\text{req}} = 1.93 \times 10^{6}\ \text{mm}^3\); flanges \(200 \times 20\) with a
\(400 \times 10\) web give \(Z = 2.08 \times 10^{6}\) and
\(M_r = \boxed{655\ \text{kN}\cdot\text{m}}\). Question 5 shows that this section, chosen on
flexure alone, is not adequate once its axial load is included — the two questions
are deliberately sequential and the point is developed there.
Base actions for the footing. At collapse the column is a propped cantilever
carrying 300 kN at mid-height with the hinge moment \(M_p\) at B, so
\(M_A = -3H_fL/16 + M_p/2 = -258.8\ \text{kN}\cdot\text{m}\) and the base shear is 115.1 kN;
both \(|M_A|\) and the mid-height moment (316.9 kN·m) stay below \(M_p\), confirming that
no further hinge forms. Bearing pressure, however, is a serviceability check, so use the elastic
service analysis of the frame (slope deflection, no sway):
\(M_A = 167.8\ \text{kN}\cdot\text{m}\), beam shear at B = 369.0 kN, hence a column axial of
\(600 + 369.0 + 9.2 = 978\ \text{kN}\) including the column's own weight.
(b) Footing size. Try a square pad \(2.2 \times 2.2 \times 0.65\ \text{m}\),
weighing 75.5 kN, so \(P = 1054\ \text{kN}\) and
$$e = \frac{M_A}{P} = \frac{167.8}{1054} = 0.159\ \text{m} \;<\; \frac{B}{6} = 0.367\ \text{m}$$
so the whole base stays in contact and
$$q_{\max} = \frac{P}{B^2}\left(1 + \frac{6e}{B}\right) = \boxed{312\ \text{kPa}} \le 350\ \text{kPa},
\qquad q_{\min} = 123\ \text{kPa} > 0$$
For thickness, check two-way shear at ULS: with \(d = 555\ \text{mm}\) the critical perimeter is
\(b_o = 3500\ \text{mm}\), \(V_f = 1283\ \text{kN}\) and
\(V_c = 0.38\phi_c\lambda\sqrt{f'_c}\,b_od = 2628\ \text{kN}\), so 650 mm is ample.