22-Elec-B7 Power Systems Engineering · December 2014
Question 2 of 7: Salient-Pole versus Cylindrical Rotor, and Two Operating Points
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2014 — 07-Elec-B7 Power Systems Engineering. Open book, three hours,
any non-communicating calculator permitted. Seven problems; the paper states that any
five constitute a complete paper and that only the first five appearing in the answer
book are marked, and that all questions are of equal value.
All seven are solved here, because the set is a study resource rather than a
sitting.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed.,
IEEE Press/Wiley — the source of this paper's notation and method: the ABCD
two-port and long-line model, the two-reaction salient-pole machine, per-unit
transformer modelling, the linearised load flow, sequence networks and the equal-area
criterion.
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the long-line
model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7), symmetrical
components and unsymmetrical faults (Ch. 8–9), transient stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis, McGraw-Hill
— network reduction, sequence networks and fault calculation.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed., McGraw-Hill
— transformer losses and equivalent circuits (Ch. 2), synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, CSA Z462
Workplace Electrical Safety (arc-flash energy from the fault currents
computed here), and IEEE Std 142 for industrial system grounding.
Question 2 (Problem 2): Salient-Pole versus Cylindrical Rotor, and Two Operating Points (5 + 10 + 10 points)
Part (a) — salient-pole versus cylindrical-rotor machines.
A cylindrical-rotor (turbo) machine has a uniform air gap, so the reluctance seen by
the armature magnetomotive force is the same wherever the rotor happens to be
standing. One reactance therefore describes it completely: the direct- and
quadrature-axis synchronous reactances are equal, $x_d = x_q = x_s$, and the
steady-state power transfer to a bus of voltage $V$ is the familiar single sine term
$P = E_{af}V\sin\delta / x_d$, whose maximum $E_{af}V/x_d$ occurs at exactly
90° of rotor angle.
A salient-pole machine, the low-speed hydro construction, presents a much larger
air gap between the poles than under them. The quadrature axis is therefore the
high-reluctance axis and $x_q$ is typically 0.55 to 0.70 of $x_d$. Blondel’s
two-reaction theory resolves the armature current into direct- and quadrature-axis
components and yields a second, excitation-independent term:
$$\begin{aligned}&P \\ &=\dfrac{E_{af}V}{x_{d}}\sin\delta
+\dfrac{V^{2}}{2}\left(\dfrac{1}{x_{q}}-\dfrac{1}{x_{d}}\right)\sin 2\delta\end{aligned}$$
The second term is the reluctance power: it exists even with the field
unexcited, it peaks at 45° of rotor angle, and it makes the total maximum power
larger than the cylindrical-rotor value while moving the peak to an angle
below 90° (typically 70–80°). Practically, the salient-pole
machine is therefore stiffer at small angles and reaches its stability limit earlier
in angle but at a higher power.
Given. A 125 MVA, 11 kV, 50 Hz synchronous generator with xd = 1.33 p.u. reaches rated open-circuit voltage at 325 A of field current, and feeds a network of 11 kV equivalent voltage through an equivalent reactance of 0.17 p.u. on the machine base while delivering 110 MW.
Given data
Quantity
Symbol
Value
Machine rating
Sbase
125 MVA, 11 kV, three phase, 50 Hz
Synchronous reactance
xd
1.33 p.u.
Field current for rated open-circuit voltage
If0
325 A
External network equivalent voltage
VEQ
11 kV line to line (1.0 p.u.)
External network equivalent impedance
xeq
0.17 p.u. on the machine base
Real power delivered
P
110 MW
Find. For each of two operating conditions — unity power factor at the network equivalent bus, and rated terminal voltage — the excitation voltage, the field current, and the remaining terminal quantities.
Figure 2 — the machine, its synchronous reactance and the external network reactance in cascade between the excitation voltage and the system.
Approach. Treat the machine, its synchronous reactance and the network reactance as one phasor chain, anchoring it at whichever bus the condition specifies and walking to the others.
Part (b) — put the loading on the machine base.
Per unit on the machine rating,
$$P=\dfrac{110}{125}=0.8800\ \text{p.u.}$$
Unity power factor at the network equivalent voltage means the current is in
phase with $V_{EQ}=1.0\angle 0°$, so
$$I_{a}=\dfrac{P}{V_{EQ}}=0.8800\angle 0°\ \text{p.u.}$$
Walk the current back through the network reactance to the terminals.
The terminal voltage sits one network reactance upstream of the equivalent bus:
$$\begin{aligned}V_{t}&=V_{EQ}+jx_{eq}I_{a}=1.0+j(0.17)(0.8800) \\ &=1.0000 + j0.1496 \\ &=\boxed{1.0111\angle 8.5084^\circ\ \text{p.u.}}\end{aligned}$$
which is 11.122 kV line to line.
Continue through the synchronous reactance to the excitation voltage.
Both reactances are in cascade with the same current, so
$$\begin{aligned}E_{af}&=V_{EQ}+j(x_{eq}+x_{d})I_{a} \\ &=1.0+j(1.50)(0.8800)=1.0000 + j1.3200\end{aligned}$$
$$\boxed{E_{af}=1.6560\angle 52.8533^\circ\ \text{p.u.}}$$
Convert the excitation voltage to a field current, then read the terminal power factor.
On the air-gap line the open-circuit voltage is proportional to field current, and
325 A produces 1.0 p.u., so
$$\begin{aligned}I_{f}&=|E_{af}|\,I_{f0}=(1.6560)(325) \\ &=\boxed{538.2\ \text{A}}\end{aligned}$$
The machine terminal power factor is not unity, because unity was imposed one
reactance away. The current lags $V_t$ by the terminal-voltage angle:
$$\begin{aligned}\text{p.f.}_{t}&=\cos(8.5084°) \\ &=0.9890\ \text{lagging}\end{aligned}$$
Part (c) — fix the terminal voltage instead and find the new angle.
Now $|V_t| = 1.0$ p.u. and the same 110 MW crosses $x_{eq}$ to the equivalent bus.
The power transfer across a pure reactance between two known magnitudes gives the
angle directly:
$$\begin{aligned}P&=\dfrac{|V_{t}||V_{EQ}|}{x_{eq}}\sin\delta_{t}
\;\Rightarrow\;\sin\delta_{t} \\ &=\dfrac{(0.8800)(0.17)}{(1.0)(1.0)}
\;\Rightarrow\;\delta_{t} \\ &=8.6037°\end{aligned}$$
so $V_{t}=0.988747 + j0.149600$ p.u.
Recover the armature current from the voltage drop it must produce.
The current is whatever flows through $x_{eq}$ under that voltage difference:
$$\begin{aligned}I_{a}&=\dfrac{V_{t}-V_{EQ}}{jx_{eq}} \\ &=\dfrac{-0.011253 + j0.149600}{j0.17} \\ &=0.880000 + j0.066196
\\ &=\boxed{0.8825\angle 4.3019^\circ\ \text{p.u.}}\end{aligned}$$
On the 125 MVA, 11 kV base the rated current is 6560.8 A, so this is 5789.8 A.
Excitation voltage, field current and power factor for this condition.
Adding the drop across the synchronous reactance,
$$\begin{aligned}E_{af}&=V_{t}+jx_{d}I_{a}=0.900705 + j1.320000\; \\ &\Rightarrow\;\boxed{E_{af}=1.5980\angle 55.6922^\circ\ \text{p.u.}}\end{aligned}$$
$$\begin{gathered}I_{f}=(1.5980)(325)=519.4\ \text{A}, \\ \text{p.f.}_{t}=\cos(8.6037°-4.3019°)=0.9972\ \text{lagging}\end{gathered}$$
Holding the terminal voltage down to 1.0 p.u. instead of letting it float to
1.0111 p.u. costs about 18.8 A of field current, which is the practical point of the
comparison.