22-Elec-B7 Power Systems Engineering · December 2014
Question 6 of 7: Sequence Networks and a Single Line-to-Ground Fault
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2014 — 07-Elec-B7 Power Systems Engineering. Open book, three hours,
any non-communicating calculator permitted. Seven problems; the paper states that any
five constitute a complete paper and that only the first five appearing in the answer
book are marked, and that all questions are of equal value.
All seven are solved here, because the set is a study resource rather than a
sitting.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed.,
IEEE Press/Wiley — the source of this paper's notation and method: the ABCD
two-port and long-line model, the two-reaction salient-pole machine, per-unit
transformer modelling, the linearised load flow, sequence networks and the equal-area
criterion.
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the long-line
model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7), symmetrical
components and unsymmetrical faults (Ch. 8–9), transient stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis, McGraw-Hill
— network reduction, sequence networks and fault calculation.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed., McGraw-Hill
— transformer losses and equivalent circuits (Ch. 2), synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, CSA Z462
Workplace Electrical Safety (arc-flash energy from the fault currents
computed here), and IEEE Std 142 for industrial system grounding.
Question 6 (Problem 6): Sequence Networks and a Single Line-to-Ground Fault (15 + 10 points)
Given. Two generators with X1 = X2 = 0.20 and X0 = 0.05 p.u. feed a two-bus system through transformers of 0.05 p.u.; two parallel lines join the buses, with 0.10 p.u. positive and negative sequence and 0.30 p.u. zero sequence. From Figure (3), T1 is grounded wye on both sides and T2 has its delta on the generator side. Prefault voltage 1.0 p.u.
Given data
Quantity
Symbol
Value
Generators, positive and negative sequence
X1 = X2
0.20 p.u.
Generators, zero sequence
X0
0.05 p.u.
Transformers
XT1 = XT2
0.05 p.u.
Lines, positive and negative sequence
X12
0.10 p.u.
Lines, zero sequence
X12
0.30 p.u.
Transformer connections
T1 / T2
grounded Y – grounded Y / grounded Y – delta
Fault
—
single line to ground, mid-point of the lower line 1–2
Find. The Thevenin equivalent of each of the three sequence networks seen from a fault at the mid-point of the lower line, and the resulting single line-to-ground fault current in per unit.
Figure 7 — single-line diagram for the unsymmetrical fault study. Only the transformer neutrals and the grounded-wye generator can supply zero-sequence current.
Figure 8 — the two sequence networks seen from the fault point. The delta winding of the second transformer isolates the far generator from the zero-sequence network.
Figure 9 — the three Thevenin equivalents in series, which is the connection a single line-to-ground fault imposes on the sequence networks.
Approach. Build each sequence network according to what the transformer connections admit, reduce each to its Thevenin reactance at the fault point, then connect the three in series as a ground fault requires.
Part (a) — read the connections before drawing anything.
The sequence networks differ only in what the transformer connections allow.
Transformer T1 is grounded wye on both sides, so zero-sequence current passes
through it and generator G1 — itself a grounded wye machine —
is part of the zero-sequence network. Transformer T2 has its delta on the machine
side, which provides a circulating path for zero-sequence current but blocks it from
reaching G2. The generator zero-sequence reactance 0.05 therefore enters the
calculation once, on the G1 side only; on the G2 side the only path to the reference
is the grounded neutral of T2 itself.
Positive- and negative-sequence Thevenin reactance.
Each machine reaches its bus through
$X_{N1}=X_{N2}=0.20+0.05=0.25$, the upper line contributes 0.10 between the buses,
and the faulted lower line is split into two halves of 0.050 each. Because the two
sides are identical, the two buses are at the same potential when current is injected
at F, so no current flows in the upper line and it drops out:
$$\begin{aligned}X_{1}&=X_{2}=\dfrac{(0.050+0.25)}{2} \\ &=\boxed{j0.1500\ \text{p.u.}}\end{aligned}$$
A bus-impedance inversion that keeps the upper line in the network returns the same
value, confirming that the symmetry argument is exact and not an approximation.
Zero-sequence network — the two shunt arms are now unequal.
On the bus-1 side the path to the reference is $0.05+0.05=0.10$; on the bus-2 side
it is the transformer alone, $0.05=0.05$. The lines carry their zero-sequence value
0.30, so the halves are 0.150 each. The symmetry argument no longer applies, and the
(1, 2, reference) triangle must be transformed. With
$\Sigma_{0}=0.30+0.10+0.05=0.45$,
$$\begin{gathered}Z_{1}^{(0)}=0.06666667, \\ Z_{2}^{(0)}=0.03333333, \\ Z_{N}^{(0)}=0.01111111\end{gathered}$$
Combine the zero-sequence arms.
$$\begin{gathered}\text{arm A}=0.150+0.06666667=0.21666667, \\ \text{arm B}=0.150+0.03333333=0.18333333\end{gathered}$$
$$\begin{aligned}&X_{0} \\ &=\dfrac{(\text{arm A})(\text{arm B})}{\text{arm A}+\text{arm B}}+Z_{N}^{(0)}
\\ &=0.09930556+0.01111111 \\ &=\boxed{j0.110417\ \text{p.u.}}\end{aligned}$$
The zero-sequence reactance is smaller than the positive-sequence value, which is the
usual situation on a system with solidly grounded transformer neutrals close to the
fault, and it is the reason the ground fault current below exceeds the three-phase
value.
Part (b) — connect the three networks for a single line-to-ground fault.
A bolted single line-to-ground fault on phase a forces
$I_{b}=I_{c}=0$ and $V_{a}=0$, which in sequence quantities means the three networks
are connected in series and carry equal currents:
$$\begin{aligned}I_{a1}&=I_{a2}=I_{a0}=\dfrac{E}{j\left(X_{1}+X_{2}+X_{0}\right)}
\\ &=\dfrac{1.0}{j(0.1500+0.1500+0.110417)} \\ &=-j2.436548\ \text{p.u.}\end{aligned}$$
Faulted-phase current.
The phase current is the sum of the three equal sequence components:
$$\boxed{I_{f}=I_{a}=3I_{a1}=-j7.309645\ \text{p.u.},\qquad |I_{f}|=7.309645\ \text{p.u.}}$$
For comparison, a three-phase fault at the same point would draw
$1/X_{1}=6.6667$ p.u. The ground fault is the more severe of the two here, purely
because $X_{0}\lt X_{1}$; on a system whose transformers were both delta-connected on
the bus side the zero-sequence network would be open and the ground fault current
would be zero instead.