NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · December 2014

Question 6 of 7: Sequence Networks and a Single Line-to-Ground Fault

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, December 2014 — 07-Elec-B7 Power Systems Engineering. Open book, three hours, any non-communicating calculator permitted. Seven problems; the paper states that any five constitute a complete paper and that only the first five appearing in the answer book are marked, and that all questions are of equal value. All seven are solved here, because the set is a study resource rather than a sitting.

Reference texts.

Question 6 (Problem 6): Sequence Networks and a Single Line-to-Ground Fault (15 + 10 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. Two generators with X1 = X2 = 0.20 and X0 = 0.05 p.u. feed a two-bus system through transformers of 0.05 p.u.; two parallel lines join the buses, with 0.10 p.u. positive and negative sequence and 0.30 p.u. zero sequence. From Figure (3), T1 is grounded wye on both sides and T2 has its delta on the generator side. Prefault voltage 1.0 p.u.

Given data
QuantitySymbolValue
Generators, positive and negative sequenceX1 = X20.20 p.u.
Generators, zero sequenceX00.05 p.u.
TransformersXT1 = XT20.05 p.u.
Lines, positive and negative sequenceX120.10 p.u.
Lines, zero sequenceX120.30 p.u.
Transformer connectionsT1 / T2grounded Y – grounded Y / grounded Y – delta
Fault—single line to ground, mid-point of the lower line 1–2

Find. The Thevenin equivalent of each of the three sequence networks seen from a fault at the mid-point of the lower line, and the resulting single line-to-ground fault current in per unit.

G1 G2 grounded Y – grounded Y grounded Y – Δ 1 2 positive-sequence X = 0.10 (upper line) X = 0.10 F single line-to-ground fault at the mid-point of the lower line 1–2 generators X₁ = X₂ = 0.20, X₀ = 0.05; transformers 0.05; lines X₁ = 0.10, X₀ = 0.30
Figure 7 — single-line diagram for the unsymmetrical fault study. Only the transformer neutrals and the grounded-wye generator can supply zero-sequence current.
positive- (= negative-) sequence 0.25 0.25 line 0.10 0.050 + 0.050 reference bus X₁ = X₂ = j0.1500 pu F zero sequence 0.10 0.05 line 0.30 0.150 + 0.150 reference bus X₀ = j0.11042 pu F
Figure 8 — the two sequence networks seen from the fault point. The delta winding of the second transformer isolates the far generator from the zero-sequence network.
1.0 prefault X1 j0.1500 X2 j0.1500 X0 j0.11042 Ia1 series connection for a single line-to-ground fault: I₁ = I₂ = I₀ = 2.4365 pu
Figure 9 — the three Thevenin equivalents in series, which is the connection a single line-to-ground fault imposes on the sequence networks.

Approach. Build each sequence network according to what the transformer connections admit, reduce each to its Thevenin reactance at the fault point, then connect the three in series as a ground fault requires.

  1. Part (a) — read the connections before drawing anything. The sequence networks differ only in what the transformer connections allow. Transformer T1 is grounded wye on both sides, so zero-sequence current passes through it and generator G1 — itself a grounded wye machine — is part of the zero-sequence network. Transformer T2 has its delta on the machine side, which provides a circulating path for zero-sequence current but blocks it from reaching G2. The generator zero-sequence reactance 0.05 therefore enters the calculation once, on the G1 side only; on the G2 side the only path to the reference is the grounded neutral of T2 itself.
  2. Positive- and negative-sequence Thevenin reactance. Each machine reaches its bus through $X_{N1}=X_{N2}=0.20+0.05=0.25$, the upper line contributes 0.10 between the buses, and the faulted lower line is split into two halves of 0.050 each. Because the two sides are identical, the two buses are at the same potential when current is injected at F, so no current flows in the upper line and it drops out: $$\begin{aligned}X_{1}&=X_{2}=\dfrac{(0.050+0.25)}{2} \\ &=\boxed{j0.1500\ \text{p.u.}}\end{aligned}$$ A bus-impedance inversion that keeps the upper line in the network returns the same value, confirming that the symmetry argument is exact and not an approximation.
  3. Zero-sequence network — the two shunt arms are now unequal. On the bus-1 side the path to the reference is $0.05+0.05=0.10$; on the bus-2 side it is the transformer alone, $0.05=0.05$. The lines carry their zero-sequence value 0.30, so the halves are 0.150 each. The symmetry argument no longer applies, and the (1, 2, reference) triangle must be transformed. With $\Sigma_{0}=0.30+0.10+0.05=0.45$, $$\begin{gathered}Z_{1}^{(0)}=0.06666667, \\ Z_{2}^{(0)}=0.03333333, \\ Z_{N}^{(0)}=0.01111111\end{gathered}$$
  4. Combine the zero-sequence arms. $$\begin{gathered}\text{arm A}=0.150+0.06666667=0.21666667, \\ \text{arm B}=0.150+0.03333333=0.18333333\end{gathered}$$ $$\begin{aligned}&X_{0} \\ &=\dfrac{(\text{arm A})(\text{arm B})}{\text{arm A}+\text{arm B}}+Z_{N}^{(0)} \\ &=0.09930556+0.01111111 \\ &=\boxed{j0.110417\ \text{p.u.}}\end{aligned}$$ The zero-sequence reactance is smaller than the positive-sequence value, which is the usual situation on a system with solidly grounded transformer neutrals close to the fault, and it is the reason the ground fault current below exceeds the three-phase value.
  5. Part (b) — connect the three networks for a single line-to-ground fault. A bolted single line-to-ground fault on phase a forces $I_{b}=I_{c}=0$ and $V_{a}=0$, which in sequence quantities means the three networks are connected in series and carry equal currents: $$\begin{aligned}I_{a1}&=I_{a2}=I_{a0}=\dfrac{E}{j\left(X_{1}+X_{2}+X_{0}\right)} \\ &=\dfrac{1.0}{j(0.1500+0.1500+0.110417)} \\ &=-j2.436548\ \text{p.u.}\end{aligned}$$
  6. Faulted-phase current. The phase current is the sum of the three equal sequence components: $$\boxed{I_{f}=I_{a}=3I_{a1}=-j7.309645\ \text{p.u.},\qquad |I_{f}|=7.309645\ \text{p.u.}}$$ For comparison, a three-phase fault at the same point would draw $1/X_{1}=6.6667$ p.u. The ground fault is the more severe of the two here, purely because $X_{0}\lt X_{1}$; on a system whose transformers were both delta-connected on the bus side the zero-sequence network would be open and the ground fault current would be zero instead.
Problem 6 — results
QuantitySymbolResult
(a) positive-sequence Thevenin reactanceX1j0.150000 p.u.
(a) negative-sequence Thevenin reactanceX2j0.150000 p.u.
(a) zero-sequence Thevenin reactanceX0j0.110417 p.u.
(b) sequence currentIa1 = Ia2 = Ia02.4365 p.u. (lagging 90°)
(b) fault current|If| = 3|Ia1|7.3096 p.u.
Three-phase fault at the same point (comparison)|IF,3φ|6.6667 p.u.