NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · December 2014

Question 3 of 7: Transformer Losses versus Frequency, and Voltage along a Feeder

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, December 2014 — 07-Elec-B7 Power Systems Engineering. Open book, three hours, any non-communicating calculator permitted. Seven problems; the paper states that any five constitute a complete paper and that only the first five appearing in the answer book are marked, and that all questions are of equal value. All seven are solved here, because the set is a study resource rather than a sitting.

Reference texts.

Question 3 (Problem 3): Transformer Losses versus Frequency, and Voltage along a Feeder (5 + 10 + 10 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Part (a) — how frequency affects the several transformer losses. It matters a great deal what is held constant while the frequency changes. The core flux density follows from the applied voltage through $V \approx 4.44\,fNA B_{max}$, so at constant applied voltage $B_{max}\propto 1/f$.

Hysteresis loss obeys the Steinmetz relation $P_{h}=k_{h}fB_{max}^{\,x}$ with $x$ between 1.6 and 2.0. At constant volts per hertz — a machine or transformer fed from a variable-frequency source at constant flux — it rises in direct proportion to frequency. At constant applied voltage the two effects oppose each other and the loss falls roughly as $f^{\,1-x}$, i.e. as $1/f^{0.6}$ to $1/f$.

Eddy-current loss obeys $P_{e}=k_{e}f^{2}B_{max}^{2}t^{2}$, where $t$ is the lamination thickness. At constant volts per hertz it rises as the square of frequency; at constant applied voltage the $B^{2}$ term cancels the $f^{2}$ term exactly and the eddy loss is essentially independent of frequency, depending only on the voltage and the lamination design.

Winding (copper) loss is nominally $I^{2}R$ and so frequency independent, but only at power frequency. Skin effect and proximity effect raise the effective a.c. resistance roughly as $\sqrt{f}$ once the conductor is more than a skin depth thick, which is why high-frequency designs use foil, Litz wire or many strands. The same mechanism, plus increased leakage-flux penetration, raises the stray load loss in the tank and clamping structure faster than in proportion to frequency. The net practical result is the familiar one: a 50 Hz transformer operated at 60 Hz and the same voltage runs at lower flux and lower core loss, whereas a 60 Hz unit operated at 50 Hz and the same voltage saturates and its core loss climbs sharply.

Given. A feeder of 0.17 + j2.2 Ω supplies the high-voltage side of a 400 MVA, 225 kV : 24 kV, 50 Hz, three-phase Y–Δ transformer whose series reactance is 6.08 Ω referred to the high-voltage terminals; the load is 375 MVA at 0.89 power factor leading, at 24 kV line to line.

Given data
QuantitySymbolValue
Feeder impedanceZf0.17 + j2.2 Ω
Transformer ratingSbase400 MVA, 225 kV : 24 kV, 50 Hz, three phase, Y–Δ
Series reactance referred to the high-voltage terminalsXT6.08 Ω
LoadSL375 MVA at 0.89 power factor leading
Load voltage (line to line, low-voltage side)VL24 kV

Find. The line-to-line voltage at the high-voltage terminals of the transformer, and then at the sending end of the feeder.

sending end VS 0.17 + j2.2 Ω feeder HV bus VHV 225 kV : 24 kV Y – Δ, X = 6.08 Ω LV bus load 375 MVA 0.89 pf leading
Figure 3 — feeder, transformer and load. Everything is referred to the high-voltage side, where the transformer reactance is quoted.

Approach. Normalise both impedances on the transformer rating, express the load as a current phasor, and add the two series drops in turn.

Check — the transformer voltage rating as printed. The source prints the transformer as “22 5kV: 24kV”, with a space where a decimal point or a third digit belongs. It is read here as 225 kV : 24 kV. The reading is settled by the reactance the same sentence gives: 6.08 Ω referred to the high-voltage terminals is 0.0480 p.u. on a 400 MVA, 225 kV base, which is an ordinary value for a large transmission transformer, whereas on a 22.5 kV base the same 6.08 Ω would be 4.8 p.u. — a physically impossible leakage reactance. The 225 kV reading is therefore the only self-consistent one.
  1. Choose a per-unit base and convert the two impedances. Taking 400 MVA and the transformer ratings as the base, $$\begin{gathered}Z_{base,HV}=\dfrac{(225)^{2}}{400}=126.5625\ \Omega \;\Rightarrow\;X_{T}=\dfrac{6.08}{126.5625}=0.048040\ \text{p.u.}, \\ Z_{f}=0.001343 + j0.017383\ \text{p.u.}\end{gathered}$$ Because the transformer ratings are the bases, the low-voltage side of the transformer has its own base of 24 kV and the load voltage is exactly 1.0 p.u.
  2. Express the load as a current phasor. With $V_{L}=1.0\angle 0°$ p.u. and a load of 0.9375 p.u. at 0.89 power factor leading, the current leads the voltage by $\phi=\cos^{-1}(0.89)=27.1268°$: $$\begin{aligned}I&=\dfrac{S}{V_{L}}\angle+\phi=0.9375\angle 27.1268° \\ &=0.834375 + j0.427463\ \text{p.u.}\end{aligned}$$ On the low-voltage side that is 9021.1 A of line current, and 962.3 A on the high-voltage side.
  3. Part (b) — add the transformer reactance drop. Referring the load voltage to the high-voltage side (per unit, the referral is automatic) and adding the series drop, $$\begin{aligned}V_{HV}&=V_{L}+jX_{T}I \\ &=1.0+(-0.020535 + j0.040083) \\ &=0.979465 + j0.040083\ \text{p.u.}\end{aligned}$$ $$\boxed{|V_{HV}|_{LL}=(0.980285)(225)=220.564\ \text{kV}}$$ The drop has a negative real part because the load current leads: the reactance drop $jX_TI$ points partly backwards along the voltage phasor, which is the whole reason a leading load raises the far-end voltage.
  4. Part (c) — add the feeder drop. The same current flows in the feeder, so $$\begin{aligned}V_{S}&=V_{HV}+Z_{f}I \\ &=0.979465 + j0.040083+(-0.006310 + j0.015078) \\ &=0.973155 + j0.055161\ \text{p.u.}\end{aligned}$$ $$\boxed{|V_{S}|_{LL}=(0.974717)(225)=219.311\ \text{kV}}$$ Both voltages come out below the 225 kV nominal even though the load voltage is exactly nominal on its own base. That is the leading power factor at work: a capacitive load makes the sending end the low-voltage end, the reverse of the familiar lagging case.
Problem 3 — results
QuantitySymbolResult
Per-unit transformer reactanceXT0.048040 p.u.
Per-unit feeder impedanceZf0.001343 + j 0.017383 p.u.
Load currentI0.9375 p.u. ∠ 27.127° (leading)
(b) high-voltage terminal voltage|VHV|0.98028 p.u. = 220.564 kV line to line
(c) feeder sending-end voltage|VS|0.97472 p.u. = 219.311 kV line to line