22-Elec-B7 Power Systems Engineering · December 2014
Question 3 of 7: Transformer Losses versus Frequency, and Voltage along a Feeder
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2014 — 07-Elec-B7 Power Systems Engineering. Open book, three hours,
any non-communicating calculator permitted. Seven problems; the paper states that any
five constitute a complete paper and that only the first five appearing in the answer
book are marked, and that all questions are of equal value.
All seven are solved here, because the set is a study resource rather than a
sitting.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed.,
IEEE Press/Wiley — the source of this paper's notation and method: the ABCD
two-port and long-line model, the two-reaction salient-pole machine, per-unit
transformer modelling, the linearised load flow, sequence networks and the equal-area
criterion.
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the long-line
model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7), symmetrical
components and unsymmetrical faults (Ch. 8–9), transient stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis, McGraw-Hill
— network reduction, sequence networks and fault calculation.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed., McGraw-Hill
— transformer losses and equivalent circuits (Ch. 2), synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, CSA Z462
Workplace Electrical Safety (arc-flash energy from the fault currents
computed here), and IEEE Std 142 for industrial system grounding.
Question 3 (Problem 3): Transformer Losses versus Frequency, and Voltage along a Feeder (5 + 10 + 10 points)
Part (a) — how frequency affects the several transformer losses.
It matters a great deal what is held constant while the frequency changes.
The core flux density follows from the applied voltage through
$V \approx 4.44\,fNA B_{max}$, so at constant applied voltage
$B_{max}\propto 1/f$.
Hysteresis loss obeys the Steinmetz relation
$P_{h}=k_{h}fB_{max}^{\,x}$ with $x$ between 1.6 and 2.0. At constant volts per
hertz — a machine or transformer fed from a variable-frequency source at
constant flux — it rises in direct proportion to frequency. At constant applied
voltage the two effects oppose each other and the loss falls roughly as
$f^{\,1-x}$, i.e. as $1/f^{0.6}$ to $1/f$.
Eddy-current loss obeys $P_{e}=k_{e}f^{2}B_{max}^{2}t^{2}$, where $t$ is
the lamination thickness. At constant volts per hertz it rises as the square of
frequency; at constant applied voltage the $B^{2}$ term cancels the $f^{2}$ term
exactly and the eddy loss is essentially independent of frequency,
depending only on the voltage and the lamination design.
Winding (copper) loss is nominally $I^{2}R$ and so frequency independent,
but only at power frequency. Skin effect and proximity effect raise the effective
a.c. resistance roughly as $\sqrt{f}$ once the conductor is more than a skin depth
thick, which is why high-frequency designs use foil, Litz wire or many strands. The
same mechanism, plus increased leakage-flux penetration, raises the stray load
loss in the tank and clamping structure faster than in proportion to frequency.
The net practical result is the familiar one: a 50 Hz transformer operated at 60 Hz
and the same voltage runs at lower flux and lower core loss, whereas a 60 Hz unit
operated at 50 Hz and the same voltage saturates and its core loss climbs sharply.
Given. A feeder of 0.17 + j2.2 Ω supplies the high-voltage side of a 400 MVA, 225 kV : 24 kV, 50 Hz, three-phase Y–Δ transformer whose series reactance is 6.08 Ω referred to the high-voltage terminals; the load is 375 MVA at 0.89 power factor leading, at 24 kV line to line.
Given data
Quantity
Symbol
Value
Feeder impedance
Zf
0.17 + j2.2 Ω
Transformer rating
Sbase
400 MVA, 225 kV : 24 kV, 50 Hz, three phase, Y–Δ
Series reactance referred to the high-voltage terminals
XT
6.08 Ω
Load
SL
375 MVA at 0.89 power factor leading
Load voltage (line to line, low-voltage side)
VL
24 kV
Find. The line-to-line voltage at the high-voltage terminals of the transformer, and then at the sending end of the feeder.
Figure 3 — feeder, transformer and load. Everything is referred to the high-voltage side, where the transformer reactance is quoted.
Approach. Normalise both impedances on the transformer rating, express the load as a current phasor, and add the two series drops in turn.
Check — the transformer voltage
rating as printed. The source prints the transformer as
“22 5kV: 24kV”, with a space where a decimal point or a third digit
belongs. It is read here as 225 kV : 24 kV. The reading is settled by
the reactance the same sentence gives: 6.08 Ω referred to the high-voltage
terminals is 0.0480 p.u. on a 400 MVA, 225 kV base, which is an ordinary value for a
large transmission transformer, whereas on a 22.5 kV base the same 6.08 Ω would
be 4.8 p.u. — a physically impossible leakage reactance. The 225 kV reading is
therefore the only self-consistent one.
Choose a per-unit base and convert the two impedances.
Taking 400 MVA and the transformer ratings as the base,
$$\begin{gathered}Z_{base,HV}=\dfrac{(225)^{2}}{400}=126.5625\ \Omega
\;\Rightarrow\;X_{T}=\dfrac{6.08}{126.5625}=0.048040\ \text{p.u.}, \\ Z_{f}=0.001343 + j0.017383\ \text{p.u.}\end{gathered}$$
Because the transformer ratings are the bases, the low-voltage side of the
transformer has its own base of 24 kV and the load voltage is exactly 1.0 p.u.
Express the load as a current phasor.
With $V_{L}=1.0\angle 0°$ p.u. and a load of 0.9375 p.u. at 0.89 power factor
leading, the current leads the voltage by
$\phi=\cos^{-1}(0.89)=27.1268°$:
$$\begin{aligned}I&=\dfrac{S}{V_{L}}\angle+\phi=0.9375\angle 27.1268° \\ &=0.834375 + j0.427463\ \text{p.u.}\end{aligned}$$
On the low-voltage side that is 9021.1 A of line current, and 962.3 A on the
high-voltage side.
Part (b) — add the transformer reactance drop.
Referring the load voltage to the high-voltage side (per unit, the referral is
automatic) and adding the series drop,
$$\begin{aligned}V_{HV}&=V_{L}+jX_{T}I \\ &=1.0+(-0.020535 + j0.040083) \\ &=0.979465 + j0.040083\ \text{p.u.}\end{aligned}$$
$$\boxed{|V_{HV}|_{LL}=(0.980285)(225)=220.564\ \text{kV}}$$
The drop has a negative real part because the load current leads: the
reactance drop $jX_TI$ points partly backwards along the voltage phasor, which is the
whole reason a leading load raises the far-end voltage.
Part (c) — add the feeder drop.
The same current flows in the feeder, so
$$\begin{aligned}V_{S}&=V_{HV}+Z_{f}I \\ &=0.979465 + j0.040083+(-0.006310 + j0.015078) \\ &=0.973155 + j0.055161\ \text{p.u.}\end{aligned}$$
$$\boxed{|V_{S}|_{LL}=(0.974717)(225)=219.311\ \text{kV}}$$
Both voltages come out below the 225 kV nominal even though the load
voltage is exactly nominal on its own base. That is the leading power factor at work:
a capacitive load makes the sending end the low-voltage end, the reverse of the
familiar lagging case.