Question 2 of 7: Salient-Pole Machine on an Infinite Bus
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2014 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value; any five constitute a
complete paper and only the first five appearing in the answer book are marked.
All seven are solved here, because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation (the ABCD
two-port, the “cantilever” transformer equivalent, the two-reaction
salient-pole model, and the equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the
long-line model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — network reduction, sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformer equivalent circuits and tests (Ch. 2),
synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, and
IEEE Std 142 (Green Book) for industrial system grounding.
Check — two printing defects in the source.
Problem 7(a) prints the active load as “2.24.1 p.u.”; it is read here as
2.241 p.u. The reading is not load-bearing: taking 2.24 p.u.
instead moves the initial power angle by 0.005° and the maximum swing by
0.01°. Problem 6(b) and 6(c) each print “a single line to ground fault
… on phases B and C”, which is self-contradictory; the fault
involving two phases and ground is the double line-to-ground
fault, and that is what is solved. The single-line-to-ground value is carried
alongside so that either reading is served.
Problem 2: Salient-Pole Machine on an Infinite Bus (5 + 15 points)
Part (a) — Salient-pole versus cylindrical-rotor machines
The distinction is geometric and its consequences are entirely magnetic. A
cylindrical-rotor (round-rotor) machine has a uniform air gap:
the field winding is distributed in slots cut into a solid forged cylinder, so
the reluctance seen by the armature magnetomotive force is the same whatever its
position relative to the field axis. One reactance therefore describes the
machine, the synchronous reactance $X_s$, and it is large — typically 1.0 to
2.0 per unit — because the small uniform gap is efficient at linking flux.
These machines are the two- and four-pole turbo-generators driven by steam or gas
turbines at 3600 or 1800 r/min, where the mechanical strength of a solid
rotor is essential.
A salient-pole machine has projecting poles and hence a
strongly non-uniform gap: the gap is small along the pole (the direct axis) and
large in the interpolar space (the quadrature axis). Two reactances are needed,
and because the direct axis presents the lower reluctance,
$X_d > X_q$ always — the ratio $X_d/X_q$ is typically 1.5 to 2.5 for a hydro
generator, and the machine in this problem has $12/9 = 1.33$. Salient-pole machines are
the many-pole, low-speed units driven by hydraulic turbines and diesel engines,
which is the dominant generation type in British Columbia, Quebec, Manitoba and
Newfoundland.
The consequence for power transfer is the appearance of a second term. A
cylindrical-rotor machine delivers $P=(EV/X_s)\sin\delta$, a pure sinusoid whose maximum
$EV/X_s$ occurs at a power angle of exactly $90^{\circ}$ and which vanishes
when the field is removed. The salient-pole machine adds a
reluctance (saliency) term:
$$P=\frac{EV}{X_d}\sin\delta+\frac{V^{2}}{2}\left(\frac{1}{X_q}-\frac{1}{X_d}\right)\sin 2\delta$$
This second term exists because the rotor prefers to align its low-reluctance
axis with the stator field, so it produces torque even with the field current
zero — the principle of the reluctance motor. Three practical consequences
follow. The maximum power is larger than the cylindrical-rotor value for
the same $E$ and $X_d$. The angle at which it occurs is less than
$90^{\circ}$, because the double-frequency term peaks at $45^{\circ}$ and drags
the composite peak back. And the synchronising torque $dP/d\delta$ near the origin is
higher, so the salient-pole machine is inherently stiffer against small
disturbances.
Part (b) — Maximum power and the angle at which it occurs
Given.
Quantity
Symbol
Value
Direct-axis synchronous reactance
$X_d$
$12\ \Omega$/phase
Quadrature-axis synchronous reactance
$X_q$
$9\ \Omega$/phase
Infinite-bus voltage (line-to-line)
$V_{LL}$
34.5 kV
Excitation voltage (line-to-neutral)
$E$
30 kV
Armature resistance
$R_a$
neglected (usual for a synchronous machine)
Find. The power angle $\delta$ at which the active power
delivered to the infinite bus is a maximum, and the value of that maximum power.
Figure 2 — Three-phase power-angle characteristic. The dashed cylindrical-rotor term peaks at 90°; the dotted reluctance term peaks at 45° and pulls the composite maximum back to 78.3°.
Approach. Write the two-reaction power-angle expression on a
per-phase basis, differentiate with respect to $\delta$, and solve the resulting
quadratic in $\cos\delta$ for the physically admissible root.
Put the bus voltage on a per-phase basis and evaluate the two
coefficients. The excitation is already line-to-neutral, so only the bus
voltage needs converting:
$$V=\frac{34\,500}{\sqrt{3}}=19{,}918.6\ \text{V (line-to-neutral)}$$
$$\begin{aligned}
k_1&=\frac{EV}{X_d}=\frac{(30\,000)(19{,}918.6)}{12}=49.7965\ \text{MW/phase}\\
k_2&=\frac{V^{2}}{2}\left(\frac{1}{X_q}-\frac{1}{X_d}\right)
=\frac{(19{,}918.6)^{2}}{2}\left(\frac{1}{9}-\frac{1}{12}\right)=5.5104\ \text{MW/phase}
\end{aligned}$$
The reluctance coefficient is 11.1 per cent of the fundamental coefficient, so
it is a real contributor rather than a rounding correction.
Differentiate the power-angle expression and set the derivative to
zero. With $P=k_1\sin\delta+k_2\sin 2\delta$,
$$\frac{dP}{d\delta}=k_1\cos\delta+2k_2\cos 2\delta=0$$
Using the identity $\cos 2\delta = 2\cos^{2}\delta - 1$ and writing
$c=\cos\delta$, the stationarity condition becomes a quadratic:
$$4k_2c^{2}+k_1c-2k_2=0$$
Solve the quadratic and discard the inadmissible root.
Substituting the two coefficients in MW,
$$c=\frac{-k_1\pm\sqrt{k_1^{2}+32k_2^{2}}}{8k_2}
=\frac{-49.7965\pm 58.7483}{44.0833}$$
which gives $c=0.20307$ and $c=-2.4623$. The second root lies outside
$[-1,1]$ and is rejected; it is the artefact of turning a trigonometric equation
into an algebraic one. The admissible root gives
$$\boxed{\delta_{\max}=\cos^{-1}(0.20307)=78.284^{\circ}}$$
As predicted in part (a), the peak has been pulled back from $90^{\circ}$ by the
saliency.
Evaluate the maximum power. Substituting the angle into the
two-term expression, per phase,
$$\begin{aligned}
P_{\max}&=k_1\sin78.284^{\circ}+k_2\sin(2\times78.284^{\circ})\\
&=48.7590+2.1913=50.9503\ \text{MW/phase}
\end{aligned}$$
and for the three-phase machine
$$\boxed{P_{\max}=3(50.9503)=152.851\ \text{MW}}$$
Check the result against the round-rotor value. Had the
machine been cylindrical with the same $X_d$, the maximum would have been
$3k_1=149.39$ MW at $\delta=90^{\circ}$. The saliency therefore buys
2.3 per cent more peak power and moves the peak
11.7° earlier — the qualitative statement of part (a) reproduced
numerically, which is the check that the two halves of the answer agree.