Question 7 of 7: Transient Stability under a Sustained Fault
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2014 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value; any five constitute a
complete paper and only the first five appearing in the answer book are marked.
All seven are solved here, because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation (the ABCD
two-port, the “cantilever” transformer equivalent, the two-reaction
salient-pole model, and the equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the
long-line model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — network reduction, sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformer equivalent circuits and tests (Ch. 2),
synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, and
IEEE Std 142 (Green Book) for industrial system grounding.
Check — two printing defects in the source.
Problem 7(a) prints the active load as “2.24.1 p.u.”; it is read here as
2.241 p.u. The reading is not load-bearing: taking 2.24 p.u.
instead moves the initial power angle by 0.005° and the maximum swing by
0.01°. Problem 6(b) and 6(c) each print “a single line to ground fault
… on phases B and C”, which is self-contradictory; the fault
involving two phases and ground is the double line-to-ground
fault, and that is what is solved. The single-line-to-ground value is carried
alongside so that either reading is served.
Problem 7: Transient Stability under a Sustained Fault (5 + 10 + 5 points)
bolted three-phase at the mid-point of Line 3, sustained
Find. The initial power angle; whether the machine stays in
synchronism when a three-phase fault at the middle of Line 3 is never cleared; and
the maximum angle the rotor reaches during the resulting swing.
Figure 7 — Equal-area construction. The amber area A1 is the accelerating energy from δ0 to δ1; the green area A2 is the decelerating energy absorbed up to the turning point δm, which is reached well short of δlim.
Approach. Build the pre-fault and during-fault transfer
reactances, draw the two power-angle curves, and apply the equal-area criterion.
Because the fault is sustained there is no third (post-fault) curve: the
faulted characteristic serves as both the accelerating and the decelerating curve,
and the critical angle is read off it.
Part (a) — Pre-fault transfer reactance and initial angle.
The two identical 0.08 lines are in parallel and the rest is in series:
$$X_{pre}=0.03+0.05+\frac{(0.08)(0.08)}{0.08+0.08}=0.03+0.05+0.04=0.12$$
$$P_{\max,1}=\frac{EV}{X_{pre}}=\frac{(1.42)(1.00)}{0.12}=11.8333\ \text{pu}$$
Setting the electrical power equal to the mechanical input at steady state,
$$\sin\delta_0=\frac{P_m}{P_{\max,1}}=\frac{2.241}{11.8333}=0.189380
\;\Rightarrow\;\boxed{\delta_0=10.917^{\circ}}$$
The machine is operating well down the stable side of its characteristic, at only
18.9 per cent of its pre-fault pull-out power.
Part (b) — Transfer reactance during the fault. A bolted
three-phase fault at the mid-point of Line 3 grounds a new node F reached through
half of that line, $0.08/2=0.04$, from the parallel bus. The remaining network is a
star centred on that bus, with arms
$$x_a=0.03+0.05=0.08\ \text{(toward }E\text{)},\quad
x_b=0.08=0.08\ \text{(Line 2, toward }V\text{)},\quad
x_c=0.04\ \text{(toward F)}$$
Converting this star to a delta between $E$, $V$ and F, the arm that matters
is the one directly joining $E$ to $V$:
$$X_f=\frac{x_ax_b+x_bx_c+x_cx_a}{x_c}
=\frac{(0.08)(0.08)+(0.08)(0.04)+(0.04)(0.08)}{0.04}=0.32$$
The other two delta arms run from $E$ and from $V$ to the faulted node,
which is at zero potential; being shunt branches at fixed-voltage nodes they carry
no part of the transferred power and are discarded. Hence
$$P_{\max,2}=\frac{EV}{X_f}=\frac{1.42}{0.32}=4.4375\ \text{pu}$$
The transfer capability has fallen to 37.5 per cent of its pre-fault
value — severe, but note that it has not fallen to zero, which it
would have done had the fault been on the bus itself.
Test for stability before integrating anything. Because
$P_{\max,2}=4.4375$ still exceeds $P_m=2.241$, the faulted characteristic can
supply the mechanical input at some angle, so the machine is not automatically
lost; if the reverse had been true the answer would be "unstable" with no further
work. The two angles that bound the swing are
$$\begin{aligned}\delta_1&=\sin^{-1}\frac{P_m}{P_{\max,2}}=\sin^{-1}(0.505014)=30.332^{\circ} \\ \delta_{lim}&=180^{\circ}-\delta_1=149.668^{\circ}\end{aligned}$$
Both are read off the faulted curve, because with a sustained fault that
is the only characteristic the machine ever sees again.
Evaluate the accelerating area. Between $\delta_0$ and
$\delta_1$ the mechanical input exceeds the electrical output and the rotor
accelerates:
$$A_1=\int_{\delta_0}^{\delta_1}\left(P_m-P_{\max,2}\sin\delta\right)d\delta
=P_m(\delta_1-\delta_0)+P_{\max,2}\left(\cos\delta_1-\cos\delta_0\right)$$
With the angles in radians ($\delta_0=0.190531$, $\delta_1=0.529398$),
$$A_1=(2.241)(0.338867)+(4.4375)(0.863111-0.981904)=0.23226$$
Evaluate the largest available decelerating area. Beyond
$\delta_1$ the electrical output exceeds the input and the rotor decelerates, and the
area remains available until the angle reaches $\delta_{lim}$, past which the machine
would accelerate irrecoverably:
$$A_{2,\max}=P_{\max,2}\left(\cos\delta_1-\cos\delta_{lim}\right)-P_m(\delta_{lim}-\delta_1)
=2.99257$$
Apply the equal-area criterion.
$$A_{2,\max}=2.99257\;\gg\;A_1=0.23226$$
$$\boxed{\text{The system remains stable: the available decelerating area exceeds
the accelerating area by a factor of }12.9}$$
Physically, the fault is electrically remote enough — it sits at the midpoint
of one of two parallel lines, so the healthy line and the far half of the faulted
line still deliver power — and the machine was lightly loaded to begin with,
at only 18.9 per cent of its pre-fault capability. Both facts work in the same
direction.
Part (c) — Find the maximum angle of oscillation.
The rotor swings until the accelerating and decelerating areas are exactly equal, so
the net area from $\delta_0$ to the turning point $\delta_m$ vanishes:
$$P_m(\delta_m-\delta_0)+P_{\max,2}\left(\cos\delta_m-\cos\delta_0\right)=0$$
$$(2.241)(\delta_m-0.190531)+(4.4375)(\cos\delta_m-0.981904)=0$$
This is transcendental and is solved numerically (bisection on the interval
$[\delta_1,\delta_{lim}]$, in which the left-hand side changes sign exactly once):
$$\boxed{\delta_m=0.892748\ \text{rad}=51.151^{\circ}}$$
The swing stops 98.5° short of the limiting angle 149.668°, confirming
part (b) from a second direction. In the absence of damping the rotor would then
oscillate about 30.332° indefinitely; real damping torque, and in practice the
protection that would clear the fault long before the first swing completed, bring
it to rest there.