Question 4 of 7: Bus Types and a Three-Bus Power Flow
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2014 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value; any five constitute a
complete paper and only the first five appearing in the answer book are marked.
All seven are solved here, because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation (the ABCD
two-port, the “cantilever” transformer equivalent, the two-reaction
salient-pole model, and the equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the
long-line model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — network reduction, sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformer equivalent circuits and tests (Ch. 2),
synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, and
IEEE Std 142 (Green Book) for industrial system grounding.
Check — two printing defects in the source.
Problem 7(a) prints the active load as “2.24.1 p.u.”; it is read here as
2.241 p.u. The reading is not load-bearing: taking 2.24 p.u.
instead moves the initial power angle by 0.005° and the maximum swing by
0.01°. Problem 6(b) and 6(c) each print “a single line to ground fault
… on phases B and C”, which is self-contradictory; the fault
involving two phases and ground is the double line-to-ground
fault, and that is what is solved. The single-line-to-ground value is carried
alongside so that either reading is served.
Problem 4: Bus Types and a Three-Bus Power Flow (5 + 5 + 5 + 5 points)
Part (a) — Bus types in the conventional power-flow formulation
Every bus in a power-flow study carries four variables — the voltage
magnitude $|V|$, the voltage angle $\delta$, the net real-power injection $P$ and the
net reactive-power injection $Q$. Two of the four are specified as data and two
are computed; which two are specified is what defines the bus type, and the
classification exists because the power-flow equations are nonlinear and need
exactly $2n$ independent specifications to be determinate.
Bus type
Also called
Specified
Computed
Typical use
Slack
Swing, reference
$|V|$ and $\delta$ (usually $1.0\angle 0^{\circ}$)
$P$ and $Q$
One bus per study; takes up the loss mismatch and sets the angle reference
Voltage-controlled
Generator, PV, P-$|V|$
$P$ and $|V|$
$Q$ and $\delta$
Any bus with a generator, synchronous condenser or static var compensator regulating voltage
Load
PQ
$P$ and $Q$
$|V|$ and $\delta$
The great majority of buses; includes buses with no injection at all ($P = Q = 0$)
There is exactly one slack bus in a study, and it is needed for two reasons.
The angles are only meaningful relative to something, so one bus must supply the
angular reference; and the network losses are unknown until the solution is
found, so one generator must be left free to absorb the mismatch between total
generation and total load plus losses. In practice the largest and most stable
machine in the system is chosen. A voltage-controlled bus reverts to a load bus
during the iteration if its computed reactive output would exceed the generator's
limit — the machine can no longer hold the scheduled voltage, so $Q$ is
fixed at the limit and $|V|$ is released. In this problem bus 1 is the slack bus,
bus 3 has both its magnitude and its angle stated (so it behaves as a second
reference), and bus 2 is a load bus whose angle has been given to the candidate,
which is what makes the whole system solvable in closed form instead of by
Newton–Raphson iteration.
Parts (b), (c) and (d) — Solving the three-bus network
Given.
Quantity
Symbol
Value (per unit)
Bus 1 voltage (slack)
$V_1$
$1.0\angle 0^{\circ}$
Bus 3 voltage
$V_3$
$1.05\angle 32^{\circ}$
Line 1–2 reactance
$x_{12}$
$j0.20$
Line 2–3 reactance
$x_{23}$
$j0.08$
Real-power injection at bus 2
$P_2$
$-4.0$ (a 4.0 pu load)
Voltage angle at bus 2 (stated)
$\delta_2$
$-5^{\circ}$
Line resistance and charging
—
neglected
Find. The voltage magnitude and the reactive injection at bus
2, and the real and reactive power generated at buses 1 and 3.
Figure 4 — The three-bus system. Bus 1 is the slack bus, bus 2 is the load bus whose angle is given, and bus 3 has both magnitude and angle specified.
Approach. Build the bus admittance matrix, write the injection
equations in polar form, and exploit the fact that with $\delta_2$ given the real-power
equation at bus 2 is linear in $|V_2|$ — so no iteration is needed
anywhere in this problem.
Assemble the bus admittance matrix. With pure series
reactances and no shunt elements the branch admittances are
$$\begin{aligned}y_{12}&=\frac{1}{j0.20}=-j5.0 \\ y_{23}&=\frac{1}{j0.08}=-j12.5\end{aligned}$$
so, using $Y_{ii}=\sum y_{ik}$ and $Y_{ik}=-y_{ik}$, the susceptance entries
needed below are
$$B_{11}=-5.0,\quad B_{12}=B_{21}=+5.0,\quad B_{22}=-17.5,\quad
B_{23}=B_{32}=+12.5,\quad B_{33}=-12.5$$
Part (b) — Write the real-power injection at bus 2.
For a purely reactive network the general polar injection equation
$P_i=\sum_k |V_i||V_k|\left(G_{ik}\cos\theta_{ik}+B_{ik}\sin\theta_{ik}\right)$
collapses to the sine terms only. The self term vanishes because
$\sin 0 = 0$, leaving
$$P_2=|V_2|\left[|V_1|B_{21}\sin(\delta_2-\delta_1)
+|V_3|B_{23}\sin(\delta_2-\delta_3)\right]$$
Every quantity in the bracket is known, so the equation is linear in $|V_2|$.
Solve for the voltage magnitude at bus 2. Substituting
$\delta_2=-5^{\circ}$ and $\delta_3=32^{\circ}$,
$$\begin{aligned}
|V_1|B_{21}\sin(-5^{\circ})&=(1.0)(5.0)(-0.087156)=-0.435779\\
|V_3|B_{23}\sin(-37^{\circ})&=(1.05)(12.5)(-0.601815)=-7.898822
\end{aligned}$$
$$-4.0=|V_2|(-8.334601)\;\Rightarrow\;\boxed{|V_2|=0.4799\ \text{pu}}$$
The result is low, and it should be: 4.0 pu is a heavy load to draw through
reactances of $j0.20$ and $j0.08$, and the deep angular spread already implied by
$\delta_3=32^{\circ}$ is the signature of a stressed network. It is the correct
answer to the question as posed, not an arithmetic slip.
Compute the reactive injection at bus 2. The companion
equation for a lossless network is
$Q_i=-\sum_k |V_i||V_k|B_{ik}\cos\theta_{ik}$, and here the self term does not
vanish:
$$\begin{aligned}
Q_2&=-\left[B_{21}|V_2||V_1|\cos(-5^{\circ})+B_{22}|V_2|^{2}
+B_{23}|V_2||V_3|\cos(-37^{\circ})\right]\\
&=-\left[2.390504+(-4.030774)+5.030639\right]
\end{aligned}$$
$$\boxed{Q_2=-3.3904\ \text{pu}}$$
The negative sign means bus 2 absorbs 3.390 pu of reactive power,
so the load there is 0.763 power factor lagging — unsurprising at this voltage, since the
reactive demand of the two lines is charged against the load bus.
Part (c) — Evaluate the generation at bus 1. Bus 1
connects only to bus 2, so its injections involve a single off-diagonal term:
$$\begin{aligned}
P_1&=|V_1||V_2|B_{12}\sin(\delta_1-\delta_2)=(1.0)(0.4799)(5.0)\sin(5^{\circ})=0.2091\\
Q_1&=-\left[B_{11}|V_1|^{2}+B_{12}|V_1||V_2|\cos(5^{\circ})\right]
=-\left[-5.0+2.390504\right]=2.6095
\end{aligned}$$
$$\boxed{\begin{aligned}P_1&=0.2091\ \text{pu} \\ Q_1&=2.6095\ \text{pu}\end{aligned}}$$
Bus 1 delivers almost no real power — its angle is only 5° ahead of bus
2 across a comparatively large reactance — but it supplies substantial
reactive power, which is what holds its own terminal voltage at 1.0 pu against
the depressed voltage next door.
Part (d) — Evaluate the generation at bus 3.
By the same pair of equations across the $j0.08$ line:
$$\begin{aligned}
P_3&=|V_3||V_2|B_{32}\sin(\delta_3-\delta_2)=(1.05)(0.4799)(12.5)\sin(37^{\circ})=3.7909\\
Q_3&=-\left[B_{33}|V_3|^{2}+B_{32}|V_3||V_2|\cos(37^{\circ})\right]=8.7506
\end{aligned}$$
$$\boxed{\begin{aligned}P_3&=3.7909\ \text{pu} \\ Q_3&=8.7506\ \text{pu}\end{aligned}}$$
Bus 3 carries essentially the whole load, as its 37° lead over bus 2 across
the stiffer line demands.
Check the two balances. The network is lossless in real
power, so the three real injections must sum to zero, and the reactive injections
must sum to the reactive absorbed by the two line reactances:
$$P_1+P_2+P_3=0.2091-4.0+3.7909=-0.000000\ \checkmark$$
$$Q_1+Q_2+Q_3=7.9697\quad\text{versus}\quad
I_{12}^{2}x_{12}+I_{23}^{2}x_{23}=1.3706+6.5991=7.9697\ \checkmark$$
Both close to the last figure carried, which confirms the admittance signs and
the angle conventions simultaneously — the single most valuable check
available in a power-flow calculation.