Question 3 of 7: Transformer Losses, Tests and Regulation
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2014 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value; any five constitute a
complete paper and only the first five appearing in the answer book are marked.
All seven are solved here, because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation (the ABCD
two-port, the “cantilever” transformer equivalent, the two-reaction
salient-pole model, and the equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the
long-line model (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — network reduction, sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformer equivalent circuits and tests (Ch. 2),
synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.1 Canadian Electrical Code Section 10
(grounding and bonding), CSA C22.3 No. 1 Overhead Systems, and
IEEE Std 142 (Green Book) for industrial system grounding.
Check — two printing defects in the source.
Problem 7(a) prints the active load as “2.24.1 p.u.”; it is read here as
2.241 p.u. The reading is not load-bearing: taking 2.24 p.u.
instead moves the initial power angle by 0.005° and the maximum swing by
0.01°. Problem 6(b) and 6(c) each print “a single line to ground fault
… on phases B and C”, which is self-contradictory; the fault
involving two phases and ground is the double line-to-ground
fault, and that is what is solved. The single-line-to-ground value is carried
alongside so that either reading is served.
Problem 3: Transformer Losses, Tests and Regulation (5 + 5 + 5 + 5 points)
Part (a) — The effect of frequency on transformer losses
Transformer losses divide into core (no-load) losses and winding (load) losses,
and frequency enters each differently. The core losses are hysteresis and eddy
current. Hysteresis loss obeys Steinmetz's law, $P_h = k_h f B_{\max}^{\,n}$, where the exponent
$n$ lies between 1.5 and 2.0 for modern grain-oriented silicon steel. Eddy-current
loss in a lamination of thickness $t$ obeys $P_e = k_e f^{2}B_{\max}^{2}t^{2}$. At first sight both rise
with frequency, but that reading is incomplete, because in a transformer supplied
from a constant voltage the flux density is not an independent variable: Faraday's
law gives $V = 4.44 f N A B_{\max}$, so $B_{\max}\propto V/f$.
Substituting that constraint is what makes the answer physically useful. At
constant applied voltage the hysteresis loss varies as
$$P_h\propto f\left(\frac{V}{f}\right)^{n}=V^{n}f^{-(n-1)}$$
so with $n \approx 1.6$ it falls roughly as $f^{-0.6}$ when the frequency is raised.
The eddy-current loss varies as
$$P_e\propto f^{2}\left(\frac{V}{f}\right)^{2}=V^{2}$$
so it is essentially independent of frequency at constant voltage. Total
core loss therefore decreases modestly as frequency rises and increases sharply as
it falls. The practical corollary is the one that matters on an exam and in the
field: operating a 60-Hz transformer at 50 Hz at rated voltage raises the flux
density by 20 per cent, drives the core toward saturation, and can multiply the
magnetising current several-fold — which is why nameplates specify volts per
hertz and why over-excitation (volts/hertz) protection exists on generator step-up
units. The converse also holds: a 50-Hz design is safe on 60 Hz at rated
voltage.
The winding losses behave in the opposite sense. The direct-current copper loss
$I^{2}R$ is frequency-independent, but skin and proximity effects raise the effective
conductor resistance approximately with $\sqrt{f}$ at power frequencies, and the stray
losses produced by leakage flux in the tank, clamps and core edges scale roughly as
$f^{2}$. In a 60-Hz power transformer these effects are small; in a transformer feeding
a harmonic-rich load such as a variable-frequency drive they dominate, which is the
reason for the K-factor and factor-K derating conventions. Finally, the leakage
reactances themselves are proportional to frequency, so the per-unit impedance and
hence the voltage regulation of the unit change with frequency even when the losses
do not.
Parts (b), (c) and (d) — Cantilever model calculations
Given.
Quantity
Symbol
Value (referred to the 2200-V side)
Rating
$S$
25 kVA, 2200/220 V, 60 Hz, single-phase
Primary and referred secondary resistance
$R_1,\ R_2'$
$2.7\ \Omega$ each
Primary and referred secondary leakage reactance
$X_{l1},\ X_{l2}'$
$10.5\ \Omega$ each
Magnetising reactance
$X_m$
$20\,000\ \Omega$
Core-loss resistance
$R_c$
$37\,500\ \Omega$
Turns ratio
$a$
$2200/220 = 10$
Short-circuit test
—
20 V on the secondary, primary shorted
Open-circuit test
—
2250 V on the primary, secondary open
Load, part (d)
—
15 kVA at 220 V, 0.8 pf lagging
Find. The ammeter and wattmeter readings for the short-circuit
test conducted from the secondary, the same two readings for the open-circuit test
conducted from the primary, and the primary voltage when the transformer supplies
15 kVA at 220 V and 0.8 power factor lagging.
Figure 3 — The cantilever equivalent circuit of the transformer, referred to the 2200-V side. Shorting the primary removes the shunt branch from the calculation; opening the secondary removes the series branch.
Approach. In the cantilever model the whole excitation branch
sits across the primary terminals and the combined series impedance sits
between that node and the referred secondary. Each test therefore isolates exactly
one branch: shorting the primary kills the excitation branch, and opening the
secondary kills the series branch.
Combine the series elements once, for use in parts (b) and (d).
Because the two halves of the winding impedance are in series in the cantilever
arrangement,
$$\begin{aligned}R_{eq}&=R_1+R_2'=2.7+2.7=5.4\ \Omega \\ X_{eq}&=X_{l1}+X_{l2}'=10.5+10.5=21.0\ \Omega\end{aligned}$$
$$Z_{eq}=5.4+j21.0=21.6832\angle 75.579^{\circ}\ \Omega\ \text{(referred to the 2200-V side)}$$
Part (b) — Recognise what the short-circuit test measures.
With the primary terminals shorted, the excitation branch — which in the
cantilever model is connected directly across those terminals — has zero
voltage across it and therefore draws no current. The only impedance the secondary
source sees is $Z_{eq}$ referred down through the square of the turns ratio:
$$\begin{aligned}Z_{eq,\text{sec}}&=\frac{Z_{eq}}{a^{2}}=\frac{5.4+j21.0}{100}
=0.05400+j0.21000\ \Omega \\ |Z_{eq,\text{sec}}|&=0.216832\ \Omega\end{aligned}$$
Evaluate the two secondary-side instrument readings.
The ammeter reads the magnitude of the current and the wattmeter reads the real
power, which in the absence of any excitation current is entirely
$I^{2}R$ dissipated in the equivalent resistance:
$$\begin{aligned}
I_{sc}&=\frac{V_{sc}}{|Z_{eq,\text{sec}}|}=\frac{20}{0.216832}=92.237\ \text{A}\\
P_{sc}&=I_{sc}^{2}R_{eq,\text{sec}}=(92.237)^{2}(0.0540)=459.42\ \text{W}
\end{aligned}$$
$$\boxed{\begin{aligned}\text{ammeter}&=92.237\ \text{A} \\ \text{wattmeter}&=459.42\ \text{W}\end{aligned}}$$
The reading is credible: rated secondary current is
$25\,000/220=113.64$ A, so 20 V drives the test to
81.2 per cent of rated current, which is where a short-circuit test is
normally run.
Part (c) — Recognise what the open-circuit test measures.
With the secondary open no current can flow in the series arm, so the applied
2250 V appears entirely across the parallel combination of $R_c$ and $jX_m$.
The two branch currents are in quadrature, the core-loss current being in phase
with the applied voltage and the magnetising current lagging it by
$90^{\circ}$:
$$\begin{aligned}
I_{h+e}&=\frac{V_{oc}}{R_c}=\frac{2250}{37\,500}=0.0600\ \text{A}\\
I_m&=\frac{V_{oc}}{X_m}=\frac{2250}{20\,000}=0.1125\ \text{A}
\end{aligned}$$
Evaluate the two primary-side instrument readings.
The ammeter reads the phasor sum of two quadrature components, and the wattmeter
reads only the component in phase with the voltage:
$$I_{oc}=\sqrt{I_{h+e}^{2}+I_m^{2}}=\sqrt{(0.0600)^{2}+(0.1125)^{2}}=0.12750\ \text{A}$$
$$P_{oc}=\frac{V_{oc}^{2}}{R_c}=\frac{(2250)^{2}}{37\,500}=135.0\ \text{W}$$
$$\boxed{\begin{aligned}\text{ammeter}&=0.12750\ \text{A} \\ \text{wattmeter}&=135.0\ \text{W}\end{aligned}}$$
The no-load power factor is $0.0600/0.12750=0.4706$ lagging, and the exciting current
is only 1.12 per cent of the rated primary current
$25\,000/2200=11.36$ A — both are the expected orders of magnitude
for a distribution transformer of this size, which is the check that the branch
assignment is right.
Part (d) — Refer the load current to the primary side.
At 15 kVA and 220 V the secondary current is
$15\,000/220=68.182$ A, lagging the secondary voltage by
$\cos^{-1}0.8=36.870^{\circ}$. Taking the referred secondary voltage
$aV_s=10(220)=2{,}200$ V as the reference phasor, the referred current is
$$I_s/a=\frac{68.182}{10}\angle-36.870^{\circ}=6.8182\angle -36.870^{\circ}\ \text{A}$$
Add the series drop to obtain the primary voltage.
In the cantilever model the primary terminal voltage is the referred secondary
voltage plus the drop across the series arm; the excitation current does not enter,
because it is drawn from the primary node itself and produces no drop in $Z_{eq}$:
$$V_p=aV_s+\left(\frac{I_s}{a}\right)Z_{eq}
=2{,}200+(6.8182\angle -36.870^{\circ})(21.6832\angle 75.579^{\circ})$$
$$V_p=2{,}200+115.364+j92.455=2{,}315.364+j92.455\ \text{V}$$
$$\boxed{V_p=2{,}317.21\angle 2.287^{\circ}\ \text{V}}$$
The magnitude is 2,317.2 V, so the transformer needs
5.33 per cent above the referred secondary voltage to deliver this load
— a normal regulation for a 25-kVA unit at 0.8 lagging power factor, and
noticeably worse than it would be at unity power factor because the reactive
component of the current works against the dominant reactance of $Z_{eq}$.